My WebLink
|
Help
|
About
|
Sign Out
Home
Browse
Search
6000 23RD DR W TEAGUE 2021-02-23
>
Address Records
>
23RD DR W
>
6000
>
TEAGUE
>
6000 23RD DR W TEAGUE 2021-02-23
Metadata
Thumbnails
Annotations
Entry Properties
Last modified
2/23/2021 2:31:05 PM
Creation date
2/23/2021 2:24:01 PM
Metadata
Fields
Template:
Address Document
Street Name
23RD DR W
Street Number
6000
Tenant Name
TEAGUE
Imported From Microfiche
No
There are no annotations on this page.
Document management portal powered by Laserfiche WebLink 9 © 1998-2015
Laserfiche.
All rights reserved.
/
74
PDF
Print
Pages to print
Enter page numbers and/or page ranges separated by commas. For example, 1,3,5-12.
After downloading, print the document using a PDF reader (e.g. Adobe Reader).
View images
View plain text
• <br /> PUBLIC WORKS <br /> August 27, 2017 <br /> Justin Robertson <br /> BNBuilders <br /> 2601 Fourth Ave. STE 350 <br /> Owner: Nicholson Machine &Technology <br /> Job Address: 6000 23rd DR W <br /> Plan Check No: B1708-030 <br /> RE: Corrections Letter <br /> Dear Mr. Robertson, <br /> In response to the application for a building permit, the plans have been examined and you are <br /> advised that revisions may be necessary before a permit can be issued. Please review and <br /> respond to the comments below. <br /> In order for the processing of your application to continue, it will be necessary to provide the <br /> Building Division with two new sets of revised construction documents reflecting the corrections <br /> requested. Please include a response letter which indicates how the corrections were resolved. <br /> General <br /> 1. Glazing within 24" of doors(closed position) should be shown as safety glazing on the <br /> plans. Section 2406.4.2 <br /> 2. The maximum occupant load of multi-purpose room #123 should be shown posted by <br /> the room entrance. Section 1004.3 <br /> 3. Both doors in exit vestibule 122 should be shown with panic hardware if the doors have <br /> locks or latches. Section 1010.1.10 <br /> 4. Stair risers should be shown to be a maximum of 7" in height. Section 1011.5.2 <br /> 5. Exit signs should be shown on the plans. Section 1013.1 <br /> 6. It should be clarified that the shell is an existing, heated and fully-insulated space. <br /> WSEC <br /> All codes cited refer to the 2015 International Building Code (IBC), the 2015 International Fire <br /> Code (IFC), the 2015 International Mechanical Code (IMC), and the 2015 Washington State <br /> Energy Code (WSEC), as amended by the State of Washington and adopted by the City of <br /> Everett. The current IBC referenced standard for accessible design is the 2009 "Accessible and <br /> Usable Buildings and Facilities" (ICC/ANSI A117.1). Federal ADA regulations and standards may <br />
The URL can be used to link to this page
Your browser does not support the video tag.