• 411 <br /> A H B L <br /> October 8, 2019 <br /> Mr. Drew Martin, PE, SE <br /> Associate Engineer/Commercial Plans Examiner <br /> City of Everett Permit Services cm/Engitleers <br /> 3200 Cedar Street <br /> Everett, WA 98201-4516 <br /> ,Structural Engene.ers <br /> Project: Glacier Peak Compass TI, AHBL No. 2190664.20 Landscape A.r;i.Errs <br /> Subject: Response to Comments dated September 27, 2019 <br /> Plan Check Number: B1909-009, First Building Review <br /> Cpinalrinity Planners <br /> Dear Mr. Martin: <br /> Land u,veyarn <br /> This letter is in response to your comments dated September 27, 2019, regarding the above <br /> referenced project. The comments are included below(verbatim)for your reference. Our Neighbors <br /> responses are shown in bold after each comment. <br /> Structural <br /> 1. Sheet S1.1 shows modifications to the existing concrete tilt-up wall panels that include <br /> cutting new openings in the panels. The panels are the vertical lateral force resisting <br /> system (LFRS)for the building and have been designed as Special Reinforced Concrete <br /> Shear Walls using a response modification factoe of R=5.0 (i.e., bearing wall system per <br /> ASCE 7-10 Table 12.2-1 Item A.1). The following comments shall be addressed: <br /> a. Calculations substantiating the performance of the modified lateral force <br /> resisting system, and in particular the modified wall panels, shall be submitted <br /> for review per IEBC Section 807.5. Note that construction for this building is <br /> currently being performed under Permit No. B1801-035. The 10% DCR limit <br /> and reduced seismic loads per the exception shall not apply. See IEBC Section <br /> 807.2, IBC Sections 1604.1, 1604.4, and 1901.2, and ACI 318-14 Sections <br /> 18.10 and 18.11. <br /> Response: The original building was recently designed and constructed using the <br /> IBC 2015 and so the IBC was continued to be used for the attached calculation <br /> addendum. Existing wall panels are still well within acceptable loading for the <br /> original special concrete shear wall requirements. <br /> TACOMA <br /> • <br /> l� 2215 North 301h Street <br /> / / Suite 300 <br /> Tacoma,WA 98403-3350 <br /> 253.383.2422; . <br /> www,alibi,corn <br />