9/11/2020 Page 1 <br /> City of Everett <br /> 9:02:27AM <br /> INSPECTION ACTIVITY REPORT <br /> Permit No. E2004-011 Site Address 1219 RUCKER AVE <br /> Applied 4/2/2020 Applicant FORECAST ROOFING&SOLAR(ELEC) Lot <br /> Approved 4/2/2020 Owner POTTERF JAMES SAMUEL Block <br /> Issued 4/8/2020 Contractor FORECAST ROOFING&SOLAR(ELEC) Tract <br /> Parent Permit No. Description Generator and critical loads subpanel installation <br /> Notes Installing a manual transfer switch and generator with a critical load subpanel <br /> Scheduled Completed Tyne Inspector Result Remarks Inspector's Comments <br /> 7/22/2020 7/22/2020 ELEC 09-FINAL SKB CORRECTION eTRAKiT Inspection 7/20/2020 8:17 AM FORECAST <br /> Request ROOFING&SOLAR(ELEC) <br /> Call contact for access.They will open <br /> basement door where work was performed <br /> Contact Name:Sam Potted <br /> Site Address: 1219 RUCKER AVE <br /> Phone:2063993245 <br /> e-Mail:sam.potted@gmail.com <br /> (7/22/2020 12:04 PM SKB) <br /> Provide a load calculation for the 30 amp <br /> sub panel.All grounded conductors" <br /> neutrals"must originate from the sane <br /> panel as the hot. <br /> 9/8/2020 9/8/2020 ELEC 09-FINAL SKB APPRVD-PERN eTRAKiT Inspection 8/27/2020 9:47 AM FORECAST <br /> Request ROOFING&SOLAR(ELEC) <br /> Access available.Please call contact for <br /> access details <br /> Contact Name:Sam Potted <br /> Site Address: 1219 RUCKER AVE <br /> Phone:2063993245 <br /> e-Mail:office@forecastsolar.com <br /> INSP12 <br />