Laserfiche WebLink
8/12/2020 <br />City of Everett <br />Page 2 <br />10:33:47AM` <br />r <br />INSPECTION ACTIVITY REPORT <br />5/21/2020 5/21/2020 <br />ELEC 09-FINAL SKB CORRECTION eTRAKiT Inspection <br />5/20/2020 4:27 PM Robel Estifanos <br />Request <br />Second ground rod installed North of the <br />gas line and properly grounded, old <br />conductor removed from attic, damaged <br />conductor replaced with new wire, furnace <br />reworked, Water properly bonded through <br />the crawl space. <br />Contact Name: Robel Estifanos <br />Site Address: 8621 XAVIER WAY <br />Phone:2068513596 <br />e-Mail: robel.estifanos@outlook.com <br />(5/21/2020 2:30 PM SKB) <br />The grounding electrode conductor must be <br />continuous it cannot be spliced as it is <br />where it extends to the second ground rod. <br />Properly ground the grounded bus. Properly <br />bond service nipple . Install proper straps <br />per WAC 230 ( 2 hole straps are not <br />allowed as a means of support on a mast. <br />Conductors must be in a junction box or <br />removed in the attic where the ends is <br />exposed. The furnace must have a <br />disconnect swithc in the attic. Provide a <br />receptacle in the attic for the furnace. <br />5/29/2020 5/29/2020 <br />ELEC 09-FINAL MCB APPRVD-PERK eTRAKiT Inspection <br />5/28/2020 11:49 AM Robel Estifanos <br />Request <br />requesting final inspection. All items has <br />been reworked, furnace inspected. if <br />possible requesting AM inspection. Thanks <br />for the time and support in advance. <br />Contact Name: Robel Estifanos <br />Site Address: 8621 XAVIER WAY <br />Phone:2068513596 <br />e-Mail: robel.estifanos@outlook.com <br />8/12/2020 8/12/2020 <br />ADMIN USE KLC APPROVAL <br />ONLY" <br />INSPI2 CaWSYSTEMS <br />