June 21, 2019 <br />Mr. Tony Lee <br />Page 3 of 3 <br />Reference: PRMCE 9th Floor. Additional Requested Fire Dampers. <br />o The developed "pressure differentials" over the life -safety doors between the "Patient Zone A" <br />and the "Connector" should be considered with the possibility of the doors not closing. <br />Elimination of Flexible Ductwork in Supply Air Duct System (at Diffusers): <br />o All supply air ductwork is no less than 26 gage thickness. This will provide the proper fire <br />resistance and prevent the ductwork from failing within the code required time period. <br />o The system is designed for a "defend -in -place" strategy and is not de -energized during a fire <br />event. This means that fire and smoke cannot travel back into the ductwork and potential <br />migrate from on smoke zone to another smoke zone. Even if the fire burns through the flex <br />duct, the hot gases cannot travel back through the system. <br />o On other hospital projects with the same control strategy we have typically seen the <br />requirement for elimination of the flex duct upstream on the rated room only — not <br />downstream. This interpretation of the code was due to the defend -in -place control strategy. <br />Stantec Consulting Services Inc. <br />Finn Jakobsen <br />Project Manager <br />Phone: 206-494-5061 <br />Finn.Jakobsen@stantec.com <br />Design with community in mind <br />>f v:120481active12048204361coe review commentslmemo for coe.docx <br />• 3�3 <br />