5. The structure appears to an in-plane vertical irregularity of the lateral force resisting <br /> system. Per ASCE 7-10 Sec 12.3.3.4, having this type of irregularity requires an <br /> increase of 25% to design demands related to connections of diaphragms and collectors <br /> to the vertical lateral force resisting system. <br /> 6. In the direction where the moment frames are taking direct shear, please demonstrate <br /> how the redundancy factor, p, is 1.0 as it appears that the removal two connections in a <br /> single beam would render the moment frame unable to resist lateral forces and place <br /> cL the full shear demand on one line of plywood shear walls. Please clarify or provide a <br /> redundancy factor of 1.3 at this level where required. <br /> 7. It appears that the overall height of the structure is greater than 30'-0". Please <br /> demonstrate that a Type 5b vertical irregularity is not present in the structure per Sec <br /> 12.3.3.2 of ASCE 7-10. <br /> 8. Per ASIC 341-10, the use of an ordinary steel moment frame requires the design of fully <br /> restrained or partially restrained moment connections per El, Item 6. Please indicate <br /> which types of connections are provided for the moment frame connections and provide <br /> calculations supporting the design assumptions. Please revise details as required. <br /> 9. Please provide checks for uplift as it does not appear to accounted for in the design of <br /> the footings. wh, 6e,1 , ? <br /> 10. It appears that the steel moment frame beams are conflicting with the glu-lam beams <br /> indicated on Sheet 2.1 of the architectural drawings. Please clarify beam locations. <br /> 11. On Detail F of Sheet 7 of the architectural drawings, please provide a design calculation <br /> for the guardrail connections to the new deck in accordance with IBC 2015 Sec 1607.8. <br /> Details should be provided on the plans. Section 107.2.1 <br /> In order for the processing of your application to continue, it will be necessary to provide the <br /> Building Division with two new sets of revised construction documents reflecting the corrections <br /> requested. Please include a response letter which indicates how the corrections were resolved. <br /> All codes cited refer to the 2015 International Building Code (IBC), 2015 International Existing <br /> Building Code (IEBC), the 2015 International Fire Code (IFC), the 2015 International Mechanical <br /> Code (IMC), and the 2015 Washington State Energy Code (WSEC), as amended by the State of <br /> Washington and adopted by the City of Everett. The current IBC referenced standard for <br /> accessible design is the 2009 "Accessible and Usable Buildings and Facilities" (ICC/ANSI <br /> A117.1). Federal ADA regulations and standards may be more restrictive. <br /> CITY OF EVERETT • 3200 Cedar Street • Everett,WA 98201 • (425)257-8813 • Page 3/4/ <br />