Sabrina Fandler <br /> From: Sabrina Fandler <br /> Sent: Friday, November 22, 2019 3:04 PM <br /> To: s\AE hclly2@umifireprotection.cem- <br /> Cc: Tim Markham; Kurtis Brown <br /> Subject: Sprinkler Permits for 1622 E Marine View Dr(Riverview Apartments)-Corrections <br /> Required <br /> Attachments: Transmittal Sheet 11-21-19.pdf <br /> Hello Unlimited Mechanical Inc, <br /> The nine sprinkler permits packages for the Riverview Apartments at 1622 E Marine View Dr all require corrections. I am <br /> outlining all of the corrections in this email for ease: <br /> Building/Permit# What the approved civil&building What the sprinkler plans show and how it needs <br /> plans specify to be corrected <br /> Building A/K1911-004 2" Fire service line with DCDA inside Cut sheet shows 2.5"-10" DCVA. Need to revise <br /> building per COE Standard Drawing cut sheet to be for a 2" DCDA.See COE Standard <br /> #523, NFPA 13R. Drawing#523 for reference. <br /> Building B/ K1911-005 2" Fire service line with DCDA inside Cut sheet shows 2.5"-10" DCVA. Need to revise <br /> building per COE Standard Drawing cut sheet to be for a 2" DCDA.See COE Standard <br /> #523, NFPA 13R. Drawing#523 for reference. <br /> Building C/K1911-006 2" Fire service line with DCDA inside Plans show 4" pipe entering building and <br /> building per COE Standard Drawing reducing down to a 2.5". Plans reference NFPA <br /> #523, NFPA 13. 13R. Cut sheet shows a C300 2.5"-10" DCVA and <br /> plans reference a C200 DCVA. Need to revise <br /> plans to show a 2"coming in, revise cut sheet to <br /> be for a 2" DCDA per COE Standard Drawing <br /> #523, and revise plans to reference NFPA 13. <br /> Building D/K1911-007 2" Fire service line with DCDA inside Plans show 4" pipe entering building and <br /> building per COE Standard Drawing reducing down to a 2.5". Plans reference NFPA <br /> #523, NFPA 13. 13R.Cut sheet shows a C300 2.5"-10" DCVA and <br /> plans reference a C200 DCVA. Need to revise <br /> plans to show a 2" coming in, revise cut sheet to <br /> be for a 2" DCDA per COE Standard Drawing <br /> #523, and revise plans to reference NFPA 13. <br /> Building E/K1911-008 2" Fire service line with DCDA inside Cut sheet shows 2.5"-10" DCVA. Need to revise <br /> building per COE Standard Drawing cut sheet to be for a 2" DCDA.See COE Standard <br /> #523, NFPA 13R. Drawing#523 for reference. <br /> Building F/K1911-009 2" Fire service line with DCDA inside Cut sheet shows 2.5"-10" DCVA. Need to revise <br /> building per COE Standard Drawing cut sheet to be for a 2" DCDA.See COE Standard <br /> #523, NFPA 13R. Drawing#523 for reference. <br /> Building G/K1911-010 2" Fire service line with DCDA inside Plans show 4" pipe entering building and <br /> building per COE Standard Drawing reducing down to a 2.5". Plans reference NFPA <br /> #523, NFPA 13. 13R. Cut sheet shows a C300 2.5"-10" DCVA and <br /> plans reference a C200 DCVA. Need to revise <br /> plans to show a 2" coming in, revise cut sheet to <br /> be for a 2" DCDA per COE Standard Drawing <br /> #523, and revise plans to reference NFPA 13. <br /> 1 <br />