Laserfiche WebLink
Riverview Carriage Houses C & D I WSEC Air Barrier Testing Report <br /> RIVERVIEW CARRIAGE RESIDIENTAL UNIT TESTS: ACH50 (Air Changes Per Hour) must be > 5 for the standard <br /> energy code or>_ 3 for the enhanced standard. <br /> Volume CF Measured Allowable ACH 50 <br /> Carriage Unit No. Leakage @ 50 Leakage @ 50 Result <br /> Per Unit Pa Pa Result <br /> C C101 15080 CF 531.3 CFM 754 CFM .11 Pass <br /> C C102 15080 CF 545.4 CFM 754 CFM 2.17 Pass <br /> D D101 15080 CF 546.7 CFM 754 CFM 2.18 Pass <br /> D D102 15080 CF 471.8 CFM 754 CFM 1.88 Pass <br /> Unit C101 Unit C102 <br /> retro e'1 `_ tei. • <br /> i 014 ,,,,,,:ir, sI <br /> 545.4 <br /> •. ..wa.�tt.� ' <br /> t roar earl 6 9' ■avf' x rye"1 <br /> }' I <br /> WAN <br /> 3 I 4 <br />