E 6 C. Riverview E I WSEC Air Barrier Testing Report <br /> o v o < <br /> Zone Summaries <br /> The following tables are a more detailed summary of test results across all 2 zones including Low and High <br /> bounds of that value's 95% confidence interval in addition to the average (Mid.)value. See the Test Procedure <br /> section for more detail about the Leakage Coefficient and Pressure Exponent. <br /> Table 3: Zone "ends" Test Results (Positive and Negative Pressure) with Confidence Intervals <br /> Parameter Low Mid. High Limit Test <br /> Total Leakage @ 75 Pa 0.196 CFM/ft2 0.198 CFM/ft2 0.200 CFM/ft2 < 0.25 CFM/ft2 PASS <br /> Pressure Exponent,n 0.678 0.709 0.740 0.45 < n<0.85 PASS <br /> Leakage Coefficient, Co 224.14 255.72 287.31 <br /> ELA @ 75 Pa 2.474 ft2 2.499 ft2 2.524 ft2 <br /> Table 4: Zone "mid" Test Results(Positive and Negative Pressure) with Confidence Intervals <br /> Parameter Low Mid. High Limit Test <br /> Total Leakage @ 75 Pa 0.241 CFM/ft2 0.242 CFM/ft2 0.242 CFM/ft2 <0.25 CFM/ft2 PASS <br /> Pressure Exponent,n 0.677 0.688 0.699 0.45<n<0.85 PASS <br /> Leakage Coefficient,Co 223.50 234.35 245.21 <br /> ELA @ 75 Pa 2.089 ft2 2.097 ft2 2.105 ft2 <br /> ASTM E779-15 Test Procedure <br /> ASTM E779-15 defines a power-law model relating differential pressure across a building envelope(dP) induced <br /> by fans with the corresponding airflow(Q)through an orifice with a leakage coefficient C and pressure exponent <br /> n: <br /> Q= C(dP)" <br /> Ideally, a test consists of pressurizing and depressurizing a building with fans at differential pressures from 30 <br /> Pa to 75 Pa. Zero-airflow measurements before and after the test adjust measured dP to correct for any bias <br /> pressures detected (Wind,stack effect, etc). <br /> Pressurization airflow measurements Q are converted to volumetric standard airflows Qo of the inside air by <br /> correcting for temperature and barometric pressure. Likewise, depressurization test measurements are <br /> Page 3 1 12 <br />