Laserfiche WebLink
Riverview E I WSEC Air Barrier Testing Report <br /> SULU Y E C A <br /> Table 12: Zone "mid" Depressurized Airflow Data <br /> Target dP (Pa) Corrected dP Measured Airflow(CFM) Leakage(CFM) <br /> -75.0 -75.6 4,053 4,023 <br /> -70.0 -70.4 3,869 3,840 <br /> -65.0 -65.2 3,691 3,664 <br /> -60.0 -60.4 3,515 3,489 <br /> -55.0 -55.4 3,330 3,305 <br /> -50.0 -50.3 3,144 3,121 <br /> -45.0 -45.3 2,902 2,880 <br /> -40.0 -40.1 2,683 2,662 <br /> Figure 2: Zone "mid" Graph of Standard Airflow vs Differential Pressure <br /> 5500 - Pressurization Trendline <br /> Pressurization Data • <br /> 5000 `- Depressurization Trendline _ _ ! <br /> ■ Depressurization Data <br /> 4500 - <br /> u <br /> a, 4000 - _ - <br /> rn <br /> 1 3500 - .•'' - ,•' . <br /> . <br /> -- <br /> i - - <br /> 3000 -''' - <br /> - <br /> ..7 <br /> - <br /> 2500 , <br /> I I , I I , <br /> 35 40 45 50 55 60 65 70 75 80 <br /> Differential Pressure (Pa) <br /> Page 9 I 12 <br />