11/16/2020 Page 1 <br /> City of Everett <br /> 7:03:30AM <br /> INSPECTION ACTIVITY REPORT <br /> Permit No. K1911-010 Site Address 1622 E MARINE VIEW DR BLDG G <br /> Applied 11/14/2019 Applicant UNLIMITED MECHANICAL INC Lot <br /> Approved 2/13/2020 Owner RIVERVIEW I LLC Block <br /> Issued 2/14/2020 Contractor UNLIMITED MECHANICAL INC Tract <br /> Parent Permit No. B1812-032 Description FIRE SUPPRESSION SYSTEM(4 UNITS) <br /> Notes <br /> Scheduled Completed Twee Inspector Result Remarks Inspector's Comments <br /> 3/5/2020 3/5/2020 10:4: SPRINKLER SAG CORRECTION (03/04/2020 15:36 NES) <br /> 02-HYDRO TEST Shelly 425-583-4775 <br /> Building G <br /> Also schedule Bldg E-Notated in <br /> K1911-008 <br /> (3/5/2020 10:56 AM SAG) <br /> Hydro ok <br /> Electrical and duct touching sprinkler pipe <br /> Void spaces on South side must be filled to <br /> remain un sprinklered <br /> Full 13 <br /> 4/29/2020 4/29/2020 SPRINKLER BRA PARTIAL APPR (4/29/2020 2:22 PM BRA) <br /> 03-SPRINKLER Ok to cover <br /> 6/29/2020 6/29/2020 SPRINKLER SAG PARTIAL APPR eTRAKiT Inspection 6/26/2020 2:54 PM Shelley Johnson <br /> 01-UNDERGROUN Request <br /> Contact Name:Shelley Johnson <br /> Site Address: 1622 E MARINE VIEW DR <br /> BLDG G <br /> Phone:4255834775 <br /> e-Mail:shelleymj85@hotmail.com <br /> (6/29/2020 3:18 PM SAG) <br /> Fire Main and FDC Flush OK UMUArrow <br /> Const <br /> 10/7/2020 11/10/2020 SPRINKLER SAG APPRVD-PERN eTRAKiT Inspection 10/1/2020 4:24 PM Shelley Johnson <br /> 04-SPRINKLER Request <br /> Contact Name:Shelley Johnson <br /> Site Address: 1622 E MARINE VIEW DR <br /> BLDG G <br /> Phone:4255834775 <br /> e-Mail:shelleymj85@hotmail.com <br /> (10/7/2020 1:43 PM SAG) <br /> Local bells ok <br /> No communication with central station <br /> (11/10/2020 9:42 AM SAG) <br /> Final Ok for TCO <br /> INSP12 CRWsY STEMS <br />