Laserfiche WebLink
J <br /> SE 1 /4, NE 1 /4 SEC 1 1 , T. 28 N., R. 4 E., W.M. <br /> PanelNamn: CPl PANELSCHFDU1f Ctr. S.E.Rated LLIGHTING LUMINAIRE (FIXTURE) SCHEDULE <br /> Location: COMFORT STATION 208Y/120 Volt Section: 1 of 1 Cat�{ <br /> Fed From: SERVICE CABINET 3 Phase,4 Wire Surface Mounted PanelboardP(S) <br /> 18 kAC Sym 200 Amp Main Circuit Breaker225 Am,Bus Capacity Copper Bus100%Neutral TYPE MANUFACTURER/ CATALOG NUMBER NO TYPE MTG. VOLT WATTS DESORPTION/REMARKS <br /> Ckt Ckt Brkr P Ckt Brkr Ckt Ll FNLSME MISL4-4-LED4-2OSTD0490UNV-0-EDC1 1 LED SP 120 45 481 PENDANT MOUNTED WORK UGHT,CWB <br /> 4 B S:Y 14(S H7 TES) L l ~` I I .I .I 21 1 r : :US:' , 1 2 Q L2 METALLUX 220W-2-135-48-1-ED-S92HT 1 LED W 120 45 41-WALL MOUNTED DIRECT DOWN LIGHT <br /> 3 - 1.50 ' 1.20 20/ 1 LD)TNG:BOSOMY 2,5,8,13 4 Min 27001m INTEGRAL ORNER,WHITE FINISH,3500K, <br /> 0.90 20/ 1 NM:BOSOMY 3,6,9 6 L3 HE MUMS LX4RT-L-48-L12-S-A-DRV-UNV I LED R 120 40 RECESS IN SOFFIT CANOPY 4'LIGHT <br /> 7 COMFORT STATION EF-1 20 1' 0.90 a ' <br /> 9 COMFORT STATION RECEPTACLE • 20/ 1 0.54 DAMP LOCATION LISIED,CWB,WHITE FINISH <br /> 11 COMFORT STATION UGHTING 20/ 1 0.00 0.50 70/ 2 BUSBAY 11 (SWIFT SHELTER)LOAD CENTER 1 Q L4 LUMINS EC613-L1W48R0-120-CRT-AC6- 1 TED P 120 _ 50 12'PEDISTRNN ROUND POLE WRH(1)LEAD <br /> 13 TELECOM RECEPTACLE 20/ 1 1.00 0.50 PAA4-PAA412-CART Mn 25281m THROW,CWB,GREY FINISH <br /> 15 TELECOM RECEPTACLE 20/ 1 1.00 b . <br /> "17 IRRIGATION CONTROLLER 20/ 1 0.70 c 0.92 20/ 2 IP-1 18 L5 ,EATON McGRAW EDISON-T4W GALLEON AE-5-El-T4FT-SL2-BK 5 LED P _ 120 213 20'ALUMINUM ROUND POLE WITH(1)HEAD,CROSSWALK <br /> 19 EUH-1 30/ 2 2.50 a 0.92 - 20 Min 203131m TYPE N FORWARD THROW,CWB,GREY FINISH <br /> 21 - - 2.50 b 0.50 20/ 1 FNAC CONTROLS 22 L5A EATON McGRAW EDISON-T4W GALLEON AE-3-El-T4FT-SL2-BK 3 LED P 120 157 20'ALUMINUM ROUND POLE WITH(I)HEAD,CROSSWALK <br /> 23 COMFORT STATION RECEPTACLE 20/ 1 0.36 c 0.45 20/ 1 SITE UGHTING EAST 24 Min 153731m TYPE N FORWARD THROW,CWB,GREY FINISH <br /> 25 COMFORT STATION LIGHTING 20/ 1 0.27 a 1.00 20/ 2 EUH-4 26 <br /> 27 EUH-2 30/ 2 2.00 b 1.00 - 28 L6A DESENPIAN TITAN COMPACT S6383 1400-US 2 LED R 120 56 4810(4Y1-RECESS IN BEAM MOUNTED CANOPY DOWNLGT <br /> 29 - 2.00 c 0.80 20/ 1 EAS1-4 POWER 30 <br /> 31 EUH-3 30/ 2 2.50 a 1.63 20/ 1 SITE UGHTING SOUTH 32 4000I( DAMP LOCATION LISTED,CWB,WHITE FINISH,SIDE <br /> 33 - - 2.50 b 1.50 20/ 1 SITE UGHTING-CENTRAL 34- QUICK DISCONNECT CONNECTON,VANDEL RESISTANT LENS <br /> 35 CORNER SHELTER CANOPY LIGHTING 20/ 1 0.70 c 1.10 20/ 1 SITE LIGHTING WEST 36 L7 EATON McGRAW EDISON-T4W GALLEON AE-10-E1-T4FT-SL2-BK 10 LED P 120 528 25'ALUMINUM ROUND POLE WITH(1)HEAD <br /> 37 SITE UGHTING NORTH 20/ 1 0.90 a 0.00 30/ 3 SPD 38 Min 498421m TYPE N FORWARD THROW,CWB,GREY MEN <br /> 39 SITE UGHTNG NORTH ICONIC MARKER 20/ 1 0.23 b 0.00 - - 40 L8 PHILLIPS STONCO WRN24W-L-U-SC2-GY 1 LED S 120 28 COMPACT SURFACE CANOPY LED LUMINAIRE <br /> 41 COUNTER RECEPTACLE 20/ 1 0.80 c 0.00 - - 42 DAMP LOCATOR USTED,CWB,GREY FlHISH <br /> . Si � _exf� k edt (e . &g . L9 SOLD STATE LUMINAIRES(S51) BLXGA2AC-4-UNV-4K-120 I LED R 120 54 481.-RECESS CANOPY LED LUMINARE <br /> UghUng 17.91 NA 125% 22.39 kVA 1. Panel shall be fully rated to minimum of 18KNC. DAMP LOCATION USTED.PRONDE WTIH QUICK DISCONNECT <br /> Receptacles 0.90 INA 50%>10kVA 0.90 kVA CONNECTOR. PROVIDE WITH SPECIAL END MOUNTING CUPS <br /> NI Motors 1.70 WA 100% 1.70 kVA <br /> Lrgst Motor 1.83 WA 125% 2.29 kVA L10 TRAXON-NANO LINER ALLEGRO ACXB XB-21-120V-40 degree I LED S 120 33 361 WHITE CANOPY SKIP ACCENT LED LUMINAIRE. <br /> Kitchen 0.00 kVA 100% 0.00 kVA <br /> Miscellaneous 22.87 WA 100% 22.87 kVA WET LOCATION LASTED. INTEGRAL POWER SUPPLY, <br /> Non-Coincident 0.00 kVA -100% 0.00 kVA 111 HYDREL RHYTHM RHY4-BPCB-WHT41K-MVOLT-NFL-ASM- I LED S 120 33 ENTRY SIGN LANDSCAPE LUMINAIRE, <br /> Total 45.21 IcM4 50.15 kVA <br /> 125.5 Ape 139.2 Amps EARM6-IASR-BLA WET LOCATON USTED. POWER SUPPLY IN DEDICATED <br /> CUSTOM BOX LOCATED IN GRADE <br /> 1.12 SOLD STATE LUMINAIRES(SSL) BXGA2AC-2-UNV-4K-140 1 LED R 120 22 241-RECESS CANOPY LED LUMINAIRE <br /> DAMP LOCATION USIED.PRO/DE WITH DUCK DISCONNECT <br /> CONNECTOR. PROVIDE WITH SPECIAL END MOUNTING CUPS <br /> LIGHTING CONTROL PANEL SCHEDULE L C P MOUNTING LEGEND: S-SURFACE W-WALL MOUNTED R-RECESSED P-POLE SP-SUSPENDED <br /> LOCATION: COMFORT STATION MECHANICAL ROOM NOTES: <br /> I. All LED LAMPS TO BE 4000K UNLESS OTHERWISE NOTED. <br /> MOUNTING: SURFACE 2. COORDINATE ALL FIXTURE TRIMS WITH COUNG TYPES AND VOLTAGES. <br /> FED FROM: DPI 3. CWB=COED WEATHER BNIAST/LIRNER <br /> 4. PROVIDE IANDHOLE AND 1'C IN PIE FOR CAMERA ON LUMINAIRES L4,L5 AND L7 <br /> 5. ALL ETOEPoOR POLE MOUNTED LUMINAIRES MUST BE DARK SKY COMPLAIN. <br /> CNTRL 6. LUMINARES L6A,L8,L9,L10,L12 SHALL OPERATE WITH UNE VOLTAGE ON/OFF ONLY. NO DIMMING REQUIRED. <br /> RELAY AREA CIRCUIT 1 CODE COMMENTS 7. EXTERIOR LUMINAIRES L4,L5,L5A AND L7 SHALL RAVE INTEGRAL ACCUPANY SENSORS THAT WILL DIM LUMINAIRES BY 50%WHEN AREA IS NOT OCCUPIED. <br /> RI COMFORT STATION EXTERIOR LUMINLARES 9 A,B <br /> R2 SPARE A,B <br /> R3 SPARE A,B MOTOR AND EQUIPMENT WIRING SCHEDULE <br /> R4 BOSOMY 3 LUMINAIRES 2 A,B <br /> R5 BUSBAY 4 LUMINAIRES 4 A,8 DISCONNECT STARTER <br /> R6 BOSOMY 5 LUMINAIRES 6 AB PLAN DESCRIPTION LOAD VOLTS PH PANEL WIRE& SIZE FUSE NEMA COMB'I REMARKS <br /> R7 COIRNER SHELTER LUMINAIRES 35 A,B MARK CONDUIT NIPS AMPS SIZE YES NO <br /> R8 BOSBAY 7 LUMINAIRES 32 A,B PER 1E143 RESPONSE EF-1 IXHUAST FAN 3/4HP 120 1 DPI 1/2.C,2110+1110 GA0 20 NOTES I-3 - - - COMBO AUTOMATIC MOTOR STARTER AND DISC SW <br /> R9 SITE LIGHTING NORTH 37 no EUH-1 ELECTRIC UNIT HEATER 5KW 208 1 DPI 1'C,218+1110 GND 30 NOTES 1-3 - - - DISCONNECT <br /> RIO SITE UGHTING NORTH 39 AB EUH-2 ELECTRIC UNIT HEATER 51011 208 1 DPI 1'C,218+1110 GAO 30 NOTES 1-3 - - - DISCONNECT <br /> R11 CONIC WRIER 32 0.8 PER RFl143 RESPONSE EUH-3 ELECTIC UNIT HEATER 5KW 208 1 DPI 1'C,218+1110 GND 30 NOTES 1-3 - - - DISCONNECT <br /> EUH-4 ELECTRIC UNIT HEATER 20 208 1 DPI 3/4"C,2110+1110 CND 30 NOTES 1-3 - - - DISCONNECT I <br /> R12 SITE UGMIG EAST 24 A,B HWOP-1 HOT WATER CIRC PUMP .04 HP 120 1 DPI 3/4"C,2112+1112 CND 30 NOTES 1-3 - - - MANUAL MOTOR STARTER SWITCH I <br /> R13 SITE LIGHTING SOUTH 32 A,B W1-1 WATER HEATER 2KW 120 1 DPI 3/4T,2110+1110 CND 30 NOTES 1-3 - - - DISCONNECT <br /> R14 SITE LIGHTING CENTRAL 34 A,B IP-1 IRRIGATION PUMP 1 HP 208 1 DPI 3/4"C,2110+1110 CND 30 NOTES 1-3 - - - CONTRACTOR TO DETERMINE IF DISCONNECT OR MOTOR STARTER <br /> R15 SITE UGHTNG WEST 36 A,B <br /> 5 R16 SPARE <br /> R17 SPARE <br /> zE RI8-24 SPARE <br /> 9 CONTROL CODE IESCRPTIOENS: REMARKS: <br /> NOTES: <br /> Z A =EXTERIOR BUILDING PHOTOCELL(ON DURING NIGHT)AND TIME CLOCK, 1. SEE PLANS AND PANEL SCHEDULE FOR CIRCUITING. <br /> LOW VOLTAGE SWITCH OVERRIDE WITH SNATCH(Al DXTa 2. PROVIDE WEATHERPRROF DISCONNECT SWITCH. <br /> w B =CON1ROElED FROM DDC SYSTEM 3. PER MANUFACTURER RECOMMENDATION. CALL 2 BUSINESS DAYS BEFORE YOU DIG <br /> AI_ <br /> ,� <br /> C =ON DURING DAY,OFF AFTER HOURS,LOCAL SWITCH, <br /> 9 PHOTOCELL DAYLIGHT STEP SWITCHING <br /> 1 800 424 5555 <br /> UTILITIES UNDERGROUND LOCATION CENTER <br /> CI <br /> E bu4 48. y Barn By Dale SCALE COMMUNITY TRANSIT Drawing He, <br /> a 4 8/15/19 ADDIIg1N1 BUS SHELTERS KM JAL L. VVOO� - •_ [- ',Z` 0,/05/,0 E701 <br /> ▪ 3 8/15/19 as-BUILT oRArnNcs-PHASE, Euw w °hN� i A""'k` y " " NONE SEAWAY TRANSIT CENTER <br /> 2 8/10/la Rh 158 511a swe , �5� °°a C mUnityt n$It` 1 Y.b PERMIT SET y,/os/,7 NA ISlr.t Na <br /> 2/17/17 ADDENDUM, JAL JAL �11 Harbin e r woodharoingeccom BH fl,/o5„ SCHEDULES 6 <br /> 10/ Number a- ELECTRICAL / <br /> o No. Got. RMNon By APVr• 7 20�i 1d0,SS.0� d Total <br />