Laserfiche WebLink
I i <br /> PARTS <br /> A. HYDRANTS AND ALL MATERIALS SHALL CONFORM TO <br /> AWWA STANDARDS AND SHALL BE OF STANDARD <br /> MANUFACTURE(MUELLER SUPER CENTURION#250, <br /> WATEROUS PACER#WB67,OR CITY APPROVED <br /> EQUAL). <br /> B. 5-1/4"VALVE MINIMUM. <br /> C. 1-1/4"OPERATING NUT AND CAP NUT FOR 2-1/2" <br /> O MAX RAKE,1 PER FT PORTS. <br /> FROM GROUND <br /> UNDND LEVEL <br /> D. NATIONAL STANDARD THREAD ON 2-1/2"PORTS. <br /> II E. 5"STORZ FITTING WITH NATIONAL STANDARD THREAD <br /> O (I ' I ON THE 4-1/2"PORT. <br /> ( <br /> F. IF HYDRANT RISES THROUGH CONCRETE,USE <br /> I, © EXPANSION STRIP AROUND HYDRANT BARREL PER STD <br /> PLAN 509.IN ADDITION,INSTALLATION OF THE <br /> 0 HYDRANT ON PRIVATE PROPERTY SHALL EQUAL OR <br /> EXCEED THE STANDARDS FOR INSTALLATION OF <br /> TRAFFIC SAFETY PUBLIC FIRE HYDRANTS IN THE CITY OF EVERETT. <br /> O s I FEATURE BREAK-OFF VALVE BOX AND EXTENSION PER <br /> STANDARD DRAWING 505 <br /> FLANGE,BREAK OFF G. PROVIDE FOR VEHICULAR TRAFFIC PROTECTION WHEN <br /> Ir Y . NUTS AND BOLTS NECESSARY PER STANDARD DRAWING 508. <br /> I i I /// \ �%j H. STEAMER PORT TO BE FACING STREET OR ROADWAY <br /> FOR FIRE ENGINE ACCESS. <br /> 1/2 CU YD WASHED ROCK <br /> 1-1/2"DRAIN ROCK O I. BREAK-OFF FLANGE TO BE 2"4"ABOVE GROUND <br /> DUCTILE IRON TEE LEVEL. <br /> RETAINER (MJxMJxFL)OR <br /> GLANDS - J ` TAPPING TEE(FL) J. INSTALL CONCRETE PAD AROUND HYDRANT IN <br /> \\ - O \Q UNPAVED,SOD AND ASPHALT AREAS PER STANDARD <br /> �r�t�t�0141..� = i' .� DRAWING 508. <br /> A...,' <br /> u�t�tVrrt�tst�t = s 1. <br /> %t,t�tVlttt��i��1 : K. HYDRANT CONNECTION PIPE TO BE DUCTILE IRON <br /> jVttttt�st�tVritvl \ CLASS 52,ANY INTERMEDIATE JOINTS TO BE MJ WITH <br /> a \ \, 1`/ ��� \ /O O RETAINER GLANDS,OR FIELD LOCK GASKETS. <br /> K L. FIRE HYDRANTS SHALL BE PAINTED WITH TWO COATS <br /> OF HIGH GLOSS CATERPILLAR YELLOW,LUXLITE <br /> 3 #6100-516 OR"RUST-OLEUM"#7448 OR APPROVED <br /> F 12"x12"x4" <br /> CONC BLOCK GATE VALVE EQUAL THE PORT CAPS WILL BE PAINTED BLACK. <br /> Y.9 (MJ x FL) M. PROVIDE FOR A MINIMUM OF 3'CLEAR ZONE AROUND <br /> 0 6 MIL PLASTIC SHEETING WRAP HYDRANT. <br /> 0 <br /> UNDISTURBED EARTH <br /> LA <br /> i CITY OF EVERETT <br /> 6 PUBLIC WORKS DEPARTMENT <br /> El <br /> 2' "'VA µµ.�eov NIB 5/9/22018 <br /> a SASS I fl HEFT I PAUIIHEIM I" flB <br /> J mu <br /> ib FIRE HYDRANTg. <br /> Igor INSTALLATION 507 <br /> 1 P> <br /> I I <br /> IIIIII - - MI III - - MI INN - ' NS - - - - NM - - <br />