Laserfiche WebLink
Power Electronics/Switchgear and Networks <br />Change Order Form <br />Project Name:Change order #: <br />CPG Sales Order #:Date of Change: <br />Sales Engineer:Change Impact (weeks): <br />System Type:Distributor - Contact: <br />Change order description: <br />Change order requested: <br />Change Order <br />Factory comments <br />Distributor comments <br />Everett WWTP 3 <br />126396 5/20/21 <br />Marlan Howell *Contact CPM <br />Type 9 Jeff Delauney <br />Cummins to modify sequence of operation and PLC software to accommodate the request to remove control from the utility recloser breaker. <br />This affects the following sequences: <br />• Utility failure <br />• Utility unload <br />• Utility retransfer <br />• Breaker failure sequences <br />• Fail to disconnect <br />Cummins will need to modify the unexpected open and unexpected close logic from the utility recloser to incorporate control from an external <br />source without notification. Breaker fail to close and breaker fail to open will be communicated via SEL2505 per change order #1, making <br />CO#1 mandatory. <br />MATERIALS: <br />N/A <br />0 <br />0 <br />$14,342