GENERAL ELECTRICAL NOTES <br />i GENEHAL <br />1. LXAMINE THE SITE CONDITIONS VERY CAREFI LY AND THE SCOPE OF PROPOSED WORK TOGETHER WITH THE <br />WORK OF ALL OTHER TRADES AND INCLUDE IN THE DID PRICE ALL COSTS FOR WORK SUCH AS EQUIPMENT <br />AND WINING MADE NECESSARY TO ACCOMMODATE THE ELECTRICAL. SYSTEMS SHOWN AND SYSTEMS OF OTHER <br />TRADES. <br />2. SUBMITTAL OF DID INDICATES CONTRACTOR IS COGNIZANT OF ALL JOB SITE CONDITIONS AND WORK TO BE <br />PERFORMEO UNDER THIS CONTRACT. <br />J. PERFORM DETAILED VERIFICATION OF WORK PRIOR TO ORDERING THE ELECTRICAL EQUIPMENT AND <br />COMMENCING CONSTRUCTION. ISSUE A WRITTEN NOTICE TO THE CONSULTANT OF ANY DISCREPANCIES. <br />4. OBTAIN ALL PERMITS. PAY ASSOCIATED FEES AND SCHEDULE INSPECTION. <br />S. PROVIDE ALL LABOR, MATERIAL, EQUIPMENT, INSURANCE. AND SERVICES TO COMPLETE THIS PROJECT IN <br />ACCORDANCE WITH THE CONTRACT DOCUMENTS AND PRESENT IT AS FULLY OPERATIONAL TO THE <br />SATISFACTION OF THE OWNER. <br />6. CARRY OUT WORK IN ACCORDANCE WITH ALL GOVERNING STATE. COUNTY AND LOCAL CODES AND O.S.H.A. <br />7. PRIOR TO BEGINNING WORK COORDINATE ALL POWER AND TELCO WORK WITH THE LOCAL UTILITY COMPANY <br />AS IT MAY APPLY TO THIS STE. ALL WORK TO COMPLY WITH THE RULES AND REW ATIONS OF THE <br />UTILITIES INWLVEA. <br />B. FABRICATION AND INSTALLATION OF THE COMPLETE ELECTRICAL SYSTEM SHALL WE OWRE IN A FIRST CLASS <br />WORKMANSHIP PER NECA STANDARD 1-2000 BY QUALIFIED PERSONNEL EXPERIENCED IN SUCH WORK AND <br />SHALL SCHEDULE THE WORK iN AN ORDERLY MANNER $0 AS NOT TO IMPEDE PROGRESS OF 7"t PROJECT. <br />9. OURINO PROGRESS OF THE WORK, MAINTAIN AN ACCURATE RECORD OF THE INSTALLATION OF THE <br />ELECTRICAL SYSTEMS. LOCATING EACH CiRCUIT PRECISELY AND DIMENSIONING EQUIPMENT. CONDUIT AND <br />CABLE LOCATIONS. UPON COMPLETION OF THE INSTALLATION, TRANSFER All RECORD DATA TO BLACK LINE <br />PRINM OF NNE ORIGINAL DRAWINGS AND SUBMIT THESE DRAWINGS AS RECORD DRAWINGS TO THE <br />CONSULTANT. <br />10, COMPLETE JOB SHALL BE GUARANTEED FOR A PERIOD OF ONE (I YEAR AFTER THE DATE OF JOB <br />ACCEPTANCE BY OWNER. ANY WORK, MATERIAL, OR EQUIPMENT FOUND TO BE FAULTY DURING THAT PERIOD <br />SIAA. OF. CORRECTED AT ONCE UPON WRITTEN NOTIFICATION, AT THE EXPENSE OF THE CONTRACTOR. <br />11. C,FNERN.. CONTRACTOR IS RESPONSIBLE FOR REQUESTING CONNECTION OF COMMERCIA POWER FROM THE <br />POWER COMPANY. ELECTRICAL CONTRACTOR SHALL COORDINATE THIS WORK WITH THE OENFRAL CONTRACTOR. <br />12. COORDINATE EXACT TELEPHONE REQUIREMENTS AND SERVICE ROUTR40 WITH LOCAL TELEPHONE COMPANY. <br />APPLY FOR TELEPHONE SERVICE IMMEDIATELY UPON AWARD OF CONTRACT, <br />TVA= MATERIALS ANO METH00$ <br />1. ALL ELECTRICAL WORK SHALL CONFORM TO THE EDITION OF THE NEC ACCEPTED BY THE LOCAL <br />JURISDICTION AND 70 THE APPLICABLE LOCAL CODES AND REGULATIONS. <br />2. ALL MATERIALS AND EQUIPMENT SHALL BE NEW. MATERIALS AND EQUIPMENT SHAM. BE THE STMOARD <br />PRODUCTS OF MANUFACTURER'S CURRENT DESIGN. ANY FIRST-CLASS PRODUCT MAiJE BY A REPUTABLE <br />MANUFACTURER MAY BE USED PROVIDING IT CONFORMS TO THE CONTRACT REQUIREMENTS AND MEETS THE <br />APPROVAL OF THE CONSULTANT AND THE OWNER. <br />3. ARRANGE CONDUIT, WIRING, EOUPML NT. AND OTHER WORK GENERALLY AS SHOWN. PROMNG PROPER <br />CLEARANCES AND ACCESS. CAREFULLY EXAMINE ALL CONTRACT DRAWINGS AND FIT THE WORK IN EACH <br />LOCATION WITHOUT SUBSTANTIAL ALTERATION. WHERE DEPARTURES ARE PROPOSED BECAUSE OF FIELD <br />CONDITIONS OR OTHER CAUSES. PREPARE AND SUBMIT DETAILED DRAWINGS FOR ACCEPTANCE. <br />4. THE CONTRACT DRAWINGS ARE GENERALLY DAGRAIMMATiC AND ALL OFFSETS, BENDS. FITTINGS AND <br />ACCESSORIES ARE NOT NECESSARILY SHOWN. PROVIDE ALL SUCH ITEMS AS MAY BE REQUIRED TO FIT THE <br />WORK TO INC CONDITIONS. <br />5. MAINTAIN ALL CLTARAKCLS AS REQUIRED BY NEC. <br />6. SEAL AROUND CONDUITS AND AROUND CONDUCTORS WITHIN CONDUITS ENTERING THE PREFAERICATED <br />SHELTER/CARINETS WHERE PENETRATION OCCURS WITH A SILICONE SEAL" TO PREVENT MOISTURE <br />PENETRATION INTO BUILDING/SHELTER. <br />7. SILICONE SEAL AROUND ALL BOLTS AND SCREWS USED TO SECURE EQUIPMENT TO EXTFRiOR OF BUD.DNG. <br />8. MAKE NECESSARY CONNECTIONS FOR BATTERY IN EMERGENCY LIGHT FIXTURE, CONNECT EXTERIOR LIGHT <br />FIXTURE (PROVIDED BY SHELTER MANUFACTURER) TO EXTERNAL JUNCTION BOX. <br />�.(?(y¢t jC'�f}QS.._AI�1Q.,_C,ONNECTORS <br />1, UNLESS K07M OTHERWISE, ALL CONDUCTORS SHALL BE COPPER, MINIMUM SIZE #12 AWC. WITH <br />THERMOPLASTIC INSULATION CONFORMING TO NEMA WC5 OR CROSS -LINKED POLYETHYLENE INSULATION <br />CONFORMING TO NEMA WC7. (.TYPES THHN OR THWN-?), INSULATION SHALL BE RATED FOR 90C <br />CONDUCTORS SHALL BE COLOR CODED IN ACCORDANCE PATH NEC. <br />2. ALL CONDUCTORS USED FOR GROUNDING SHALL BE COPPER AND SHALL HAVE GREEN INSULATIN EXCEPT <br />WHERE NOTED. <br />3 FOR COPPER CONDUCTORS '(8 AWO AND SMALLLR USE 3M SCOTCH -LOX OR T" STA-KON COMPRESSION <br />TYPE CONNECTORS WITH TNT GRAIL OR SEPARATE INSULATION CAPS. FOR COPPER CONDUCTORS LARGER THAN <br />COMPRESSION Cam --CLAMP CONNECTORS UNMEW HFX LESS DR ROLT TYPE PRESSURE SPECIMEO OTTNMMSE ONONNECTORS DRAWNGS. OR DOUBLE <br />4. UNLESS NOTED OTHERWISE ALL LUGS SHALL BE TIN PLATTED COPPER, TWO -HOLE, LONG BARREL. <br />COMPRESSION TYPE, <br />5. CONDUCTOR LENGTHS SHALL BE CONRNUOIJS FROM TERMINATION TO TERMNATKIN WITHOUT SPLICES. <br />SPLICES ARE NOT ACCEPTABLE. IF SPLICES ARE UNAVOIDABLE PRIOR APPROVAL FROM THE ENGINEER MUST <br />BE OBTAINED. <br />S. ALL TERMINATIONS & LUGS SPALL BE TEMPERATURE RATED FOR A MINIMUM 75 DEGREES CELSUS. <br />eaveYlM AND BOXES <br />1. ALL CONDUIT SHALL BE IA LABELED. <br />2. ALL EMPTY CONDUITS INSTALLED FOR FUTURE USE SHALL HAVE A PULL CORD. <br />3. SHEET METAL BOXES SPALL CONFORM TO NEMA DST: CAST -METAL BOXES SWILL CCNFORM TO NEMA 81 AND <br />SHALL BE SIZED 14 ACCORDANCE WITH NEC UNLESS NOTED OTHERWISE. <br />9ROIINDIN,G, <br />i. ALL UGHTNINO PROTECTION MID SAFETY GROUNDING OF THE EiECTRICAL. EQUIPMENT SHALL BE CARRIED OUT <br />IN ACCORDANCE WiTH THE CURRENT NFPA AND VERIZON WIRELESS STANDARDS. <br />2. GROUND LUGS ARE SPECLFIID UNDER SECTION 3 CONDUCTORS AND CONNECTORS'. <br />3. ALL GROUND LUO AND COMPRESSION CONNECTIONS SHALL BE COATED WITH ANn-OXIDANT AGENT. SUCH AS <br />NO-OX. NOALOX, PENDROX DR KOPRSHIELD. <br />4. GROUND ALL EXPOSED METAUJC OBJECTS N BUILDING EXTERIOR INCLUDING BUILDING TIE DOWN BRACKETS, <br />S. PROVIDE LOCK WASHERS FOR ALL MECHANICAL CONNECTIONS FOR GROUND CONDUCTORS. USE STAINLESS <br />STEEL HARDWARE THROUGHOUT. <br />6. DO NOT INSTALL GROUND RING OUTSIDE OF PROPERTY LINE. <br />7. REMOVE ALL PAINT AND CLEAN ALL DIRT FROM SURFACES REQUIRING GROUND CONNECTIONS. REPAINT TO <br />MATCH AFTER CONNECTION IS MADE TO MAINTAIN CORROSION RESISTANCE. <br />S. ALL DMIOR GROUNDING CONDUCTORS INOLU06XC EXTERIOR GROUND RING SFUILL RE #2 AWG SOLID BARE <br />TINNED COPPER UNLESS NOTED OTHERWISE. MAKE ALL GROUND CONNECTIONS AS SHORT AND DIRECT AS <br />POSSIBLE. AVOID SHARP BENDS. THE RADIUS OF ANY FIND SHALL NOT BE LESS THAN 8' AND THE ANGLE <br />OF ANY BEND SHALL NOT EXCEED 90'. GROUNDING CONDUCTORS SHALL BE ROUTED DOWNWARD TOWARD THE <br />BURIED GROUND RiNG, <br />9. BOND ALL IXTERIOR CONDUITS. PIPES AND CYLINDRICAL MLTALUC OBJECTS WITH A PENN-UNION OT SERIES <br />CLAMP. BtACKBURN GUV SERIES CLAMP OR A BURNDY GAR 39WSU SERIES CLAMP ONLY, NO sUBswuriES <br />ACCEPTED. <br />10. ALL GROUND CONNECTIONS SHALL BE APPROVED FOR TPE METALS BEING CONNECTED. <br />11. ALL VERNAL GROUND CONNECTIONS SHALL BE EXOTHERMICALLY WELDED. ALL EXOTHERMIC WELDS TO <br />EXTERIOR CROUNO RING SHALL BE THE PARALLEL TYPE, EXCEPT FOR THE GROUND RODS WHICH ARE WE <br />EXOTHERMIC WLU)S. REPAIR ALL OALVAIVIZED SURFACES THAT HAVE BEEN DAMAGED BY EXOTHERMIC WELDING, <br />USE SPRAY GALVANIZER SUCH AS HOLUB LECTROSOL. /16-501. <br />12, CONTRACTOR 514AIL NOTIFY THE CONSTRUCTION MANAGER WHEN THE BURIED GROUND RING iS INSTALLED SO <br />THE REPRESENTATIVE CAN INSPECT THE GROUND RING BEFORE IT iS BACK TILED WITH SOIL. <br />13. FOR METAL FENCE POST GROUNDING, USE A HEAVY DUTY TYPE GROUNDING CLAMP OR EXOTHERMIC TYRO <br />CONNECTION TO POST, GROUND ALL FENCE POSTS WITHIN V OF EQUIPMENT. <br />14, WHERE MECHANICAL CONNECTORS (TWO -HULL OR CLAMP) ARE USED. APPLY A UDL3RAL PROTECTIVE COATING <br />OF AN ANTi-OXN)E COMPOUND SUCH AS 'NO OXIDE A7 BY D ARBORN CHEMICAL COMPANY ON ALL <br />CONVFCTORS. <br />LTVERCURRENT & 'SRT-GIR12ffL&NQ-fAUU ..(IP 11PT'LICASLEI <br />1. CONTRACTOR SHALL RECORD LOAD READINGS WHEN SUE POWER OR10HATES FROM A 30 SERVICE TO <br />MONITOR & ASSURE A SMANCED LOAD AT THE PRIMARY SUPPLY. RECORDS SHALL BE PROVIDED TO THE <br />SRE/FACdLM OWNER. CONTRACTOR SHALL CONSULT MANUFA&Tl9RER'S PLANS. S40P DRAWINGS AND SPECS <br />FOR INDOUR/OUMOR EQUIPMENT LOCATION & INSTALLATION. ELECSERVICE SHALL BE IN COMPLIANCE <br />WITH ALL RUULES & REGULATIONS OF THE UTILITY CO. ELECT. CONTRACTOR SHALL PROVIDE EQUIPMENT WITH <br />HIGHER SHORT-CIRCUIT FAULT CURRENT RATINGS (W.C.) AS REQUIRED TO MATCH & EXCEED UT1LOY CO. <br />AVA ABLE SYMMETRICAL & ASYMMETRICAL FAULT CURRENT LEVELS. FUSES IN SERVICE SWITCHES SHALL BE <br />CUSS 'RK1', CURRENT UMRING TYPE, 200 MAC., NON-T:M£ DELAY. DISCONNECT S,TTCHFS TO HAVE. <br />REJECTION CLIPS. UNLESS INDICATED OTHERWISE. ELECTRICAL EQUIPMENTS & PRwrenONS SHALL BE <br />STANDARD MID RATED HIGHER THAN INCOMING EQUIPMENT AND/OR UTILITY CO. kAIC RATE AND CONSIDERING <br />ELECTRIC MOTORS FAULT CONTRIBUTION. CONTRACTOR SHALL .NOT BEGIN CONSTRUCTION UNTIL THIS <br />MANDATORY REQUIREMENT IS MET. IF NEW LOAD IS AWED CONTRACTOR SHAD. VERIFY & CONFIRM BEFORE <br />CONSTRUCTION THAT TOTAL UTILITY SERVICE LOAD SHALL KEEP EQUAL To (125% VAX. DETMAND+ NEW LOAD)C <br />80% SERVICE ENTRANCE CONDUCTORS/MAN OVER CURRENT PROTECTION AMPACITY. VA-ICH VER RATING IS <br />LOWER. LIGHTING SHALL MEET NEC, IESNA AND/OR FAA STANDARDS IF APPLICABLE. PHOTOMETRIC LEVELS <br />SHALL COMPLY WiTH LOCAL. STATE & FEDERAL. RUES. ALL ELECTRICAL EQUIPMENT SHALL BE INSTALLED IN <br />ACCESSIBLE AREAS ONLY. THE ELECTRICAL INSTALLATION SHALL MEET ALL STANDARD REQUIREMENTS OF <br />POWER AND TELE- PHONE U nUTY COMPANIES. <br />ou"UN1° t ,", n emu°" <br />LEGEND <br />eSIORe. L wlra LEMI OR MOOIIKAnP10 To NGRR <br />SHMWR L' BP elPilD,a1NI7.0 Nt1Il0U1 PfiaR t11a1itN <br />1A f1WAL PAN RL Ens D Of !Sp <br />1PPCLLfG1n01u MWN TIDE or YORIMN <br />Hnuwab <br />No MCMRt M'i"umNtie p�R"No COM" <br />SYMBOL <br />DESCRIPTION <br />-r�- <br />CIRCUIT BREAKER <br />fICAM or n0 PRo=: <br />[}t <br />NON --FUSIBLE OISCONNECT SWITCH <br />(E)+ <br />FUSIBLE DISCONNECT SWITCH <br />o <br />SURFACE MOUNTED PANEL BOARD <br />Ar <br />TRANSFORMER <br />Ley <br />KILOWATT HOUR ULTER <br />DENOTES CABLE CR CONOUIT <br />TURNING UP IN PLAN VIEW <br />,'.4 <br />• <br />4 iS i <br />DENOTES CABLE OR CONDUIT <br />! tr_ ��M+ a - <br />TURNING DOWN IN PLAN VIEW <br />JB <br />P13 <br />-OFT <br />---w- UGF ----- <br />JUNCTION BOX <br />PULL BOX TO NEC/TELCO STANDARDS <br />OVERHEAD UNLMES <br />UNDERGROUND TELCO <br />_ <br />F.4 J�/- d_?7..7 <br />--- UGP -- <br />UNVDERCROUND POWER <br />- UIGPAUGT - <br />LL40MGROUND POWER/TEL0O <br />CONSTRUCTION <br />\fr• <br />DENOTES REFERENCE NOTE <br />8 <br />01/29/20 <br />ISSUED CONSTRUCTION <br />EXOTHERMIC WELD CONNECTION <br />■ <br />MECHANCCA. CONNECTION (" LUG, C-TAP) <br />7 <br />10/29/19 <br />ISSUED CONSTRUCTION <br />4--» <br />GROUND ROD <br />6 <br />09/20/19 <br />ISSUED CONSTRUCTION <br />GROUND ROO WITH INSPECRON SLEEVES <br />5 <br />07/19/19 <br />ISSUED CONSTRUCTION <br />T'T <br />GROUND BAF2 <br />PIN AND SLEEVE RECEPTACLE <br />12/03%1B <br />ISSUED FOR 9D% CD <br />3 <br />10/11/18 <br />ISSUED FOR REVIEW <br />^-� <br />CRCUND CONDUCTOR <br />2 <br />12/11/17 <br />ISSUED FOR RENEW <br />No. <br />Data <br />Revieton <br />Clients <br />ver'zon <br />ABBREVIATIONS <br />AFG <br />ABOVE FINISHED GRADE <br />a <br />AC <br />AW-TRE INTERRUPTING CAPACITY <br />I \ <br />BEG <br />BELOW FINISHED GRADE <br />L141 ) AClualize <br />C <br />CONDUiT <br />CRCB <br />CETI. REFERENCE GROUND BAR <br />CU <br />COPPER <br />C/W <br />COMPLETE WITH <br />A&E Team: <br />O.T.T. <br />DRY TYPE TRANSFORMER <br />ED <br />EMPTY COMMIT <br />,t1 <br />G <br />GROUND <br />MC7RRISl3FV HERSHFIELD <br />GE <br />GROUNDING ELECTRODE <br />D00676WARTST,SVITE200 <br />6PATT16, WADBI0l <br />DEC <br />OR0144DWC ELECTRODE CONDUCTOR <br />Tel: 206.268.7970 <br />GRC <br />GAIVANUTO RIM CONDUIT <br />UnvWp*r4aoeharWe4.mm <br />MTS <br />MANUAL. TRANSFER SWITCH <br />Project Into <br />NEC <br />NATIONAL ELECIRiCA! CODE <br />SEA <br />O/H <br />OVERHEAD <br />BAGSHAW <br />RNC <br />MID NON-METALLIC CONDUIT (SCHMUF 90 PVT:) <br />2718 EVFREFT AVE <br />SD <br />SERVICE DISCONNECT SWITCH <br />VMWIT, WA 9=1 <br />SE <br />SERVICE ENTRANCE. <br />Growing Me: <br />SN <br />SOLID NEUTRAL <br />TDB <br />TELCO (MOUND BAR <br />TEGB <br />TOWER IXtT GROLMt6 BAR <br />ELECTRICAL <br />ELECTRICAL NOTES <br />TR <br />TRANSFORMER <br />SYMBOLS <br />1VSS <br />TRANSIENT VOLTAGE SURGE StIPPRE'SSOR <br />TYP <br />TYPICAL <br />WP <br />WEATHERPROOF - NEMA 3R <br />Project Number. <br />Stad Dote. <br />U/G <br />UNDERGROUND <br />190001900 <br />11/16/15 <br />PPC <br />POWER PROTECTION SHELTER <br />Orofler <br />DeslOner. <br />8 E-- 9 <br />Citv of Everett Reviewed for Permit �2 �� <br />