• <br /> 11. Provide minimum 100 CFM exhaust fan, vented to the exterior, in the basement kitchen, <br /> show onfloor plan. <br /> SEE CLOUDED NOTE <br /> &:`rovide minimum 50 CFM Fan in new laundry closet at lower level, show on floor plan. <br /> SEE CLOUDED NOTE <br /> 13. All rooms shall be labeled with a unique name, such as"Kitchen #1" and"Kitchen#2", <br /> "Bathroom#1, Bathroom#2,"Living.Room.#1." and "Basement Laving Room" etc. <br /> DONE <br /> 14. All stairs are required to have a 36" landing measured in the direction of travel. The door at <br /> the bottom of the stairs shall be removed. <br /> DENOTED AT THAT DOOR <br /> 15. Provide a section drawing specific to this structure for the following locations, <br /> -The wall between the garage and Bedroom#7(5-1/2" min depth is required for R-21 <br /> insulation). <br /> CALLED OUT IN SECTION AA <br /> - Section at below grade walls showing insulation requirements, P.T. bottom plate and <br /> fireblocking(Horiz&Vert) <br /> TALL CONCRETE WALLS; NO INSULATION <br /> REQUIERED FOR BELOW NEW ADDITION <br /> N orr pa_0(/ipeo <br /> - Section at proposed ramp to include construction, handrail and guardrail attachment and <br /> placement. <br /> SEE SECTION DD <br /> -Provide detail for flashing and waterproofing at the proposed deck. <br /> SEE DETAIL SHEET A001 <br /> 13 <br />