Laserfiche WebLink
480V, 3PH, 3W, 60HZ INCOMING SERVICE LFG L \ D NOTES: 1 . SEVEN CONDUCTOR CABLE FOR 400HZ USE SHALL BE FACTORY <br /> SEE DRAWING 45-23-E4F ASSEMBLED WITH SIX (6) STRANDED COPPER PHASE CONDUCTORS n . <br /> WITH 600V XHHW INSULATION TWISTED ABOUT A NEUTRAL a) <br /> CONDUCTOR OF THE SAME SIZE, INSULATION TYPE AND MATERIAL o <br /> (SEE NOTE 2). <br /> 600A DISCONNECT SWITCH 600A DISCONNECT SWITCH G -\ =RAL \ OT=S 2. IN ALL CASES THE CONDUCTORS OF THE SEVEN CONDUCTORo <br /> ry <br /> °/ CABLE ASSEMBLIES SHALL BE IDENTIFIED IN A CLOCKWISE <br /> dd dd DIRECTION ABOUT THE NEUTRAL CONDUCTOR AN ABC OR coo <br /> EQUIVALENT IDENTIFICATION SCHEME AND LIKE PHASE CONDUCTOR <br /> PARALLELED AT SOURCE AND LOAD TO ENSURE THAT THE I <br /> (2)3"C,(3)350kcmil + #1/0 GND EA C- (2)3"C,(3)350kcmil + #1/0 GND EA R _F_ R E\ Cl- DRAW! \ G S PARALLELED ARE OF LIKE PHASE CONDUCTORS WILL HAVE A (- <br /> RESISTANCE AND INDUCTIVE REACTANCE HALF THAT OF A SINGLE <br /> PHASE CONNECTOR (SEE DETAIL "A"). <br /> KATO HORIZONTAL SYNCHRONOUS <br /> 3. TRIPLEX CABLE SHALL BE FACTORY ASSEMBLED WITH 3 STRANDED iz <br /> MOTOR GENERATOR (MG) �� _ COPPER CONDUCTORS WITH XHHW INSULATION TWISTED OVER THEIR L <br /> 0 \ STR �,TI 0 \ \ OT S LENGTH THE AMOUNT OF TWIST SHALL BE THAT REQUIRED TO I.1 <br /> INPUT: 480V, 3PH, 3W, 60Hz <br /> FLA - 445AII <br /> 40 ION- RELOCATE 75KVA GATE BOX TO WEST FA PROVIDE A COMPACT CROSS SECTION (DETAIL "B") <br /> POSITION NEAR GRID D/3. DO NOT SPLICE b0 <br /> OUTPUT: 400KVA/300KW IG G CONDUCTORS. 4. TRIPLEX CABLE AND 7 CONDUCTOR CABLES LESS THAN 50' IN <br /> 575V, 3PH, 4W, 400Hz r\i) �' LENGTH MAY BE FIELD ASSEMBLED IN THE SAME MANNER AS THE <br /> FLA - 400A © REMOVE RECEPTACLE FROM SIDE OF EXISTING FACTORY ASSEMBLED CABLES EXCEPT USING SINGLE CONDUCTORS <br /> UNDISTRIBUTED NEUTRAL • <br /> 75KVA GATE BOX. TAPED OR TIE WRAPPED TOGETHER AT 20" INTERVALS TO MAINTAIN <br /> o) L I U o) THE SYMMETRICAL CROSS SECTION. <br /> GROUND TO SAME POINT AS MG SETS 5. REFERENCE TELEDYNE INET NO. 1004395642 <br /> 1 " CONDUIT WITH PARALLELING Z5V22-14G3-D <br /> 3" AL. C,(6)250kcmil + 1 0 GND --� c`CONTROL WIRES, SEE KATO 400HZ DISTRIBUTION PANEL <br /> # / DWG. #653-76001-23 3" AL. C,(6)250kcmil + #1/0 GND (BY INET) <br /> GROUND BUS <br /> 600AF o 600AF o <br /> 600AT o) 600AT o) <br /> 575V, 800A, 30, 3W, 400HZ BUS <br /> L_____ 250AF 250AF I <br /> ,) •) 150AF •) 150AF o) 150AF o) 150AF o) 250AF o) 150AF o) 150AF o) 150AF o <br /> 250AT • 250AT • 100AT 100AT • 100AT • 100AT • 250AT • 100AT 100AT ° 100AT °) <br /> FUTURE <br /> � - - - - -- - ---- - _ _® ® -- -.-.. ...._ - ® _ - - ® - - - - - - - _ SPARE- - -- SPARE <br /> ./' / 3-1/2"AL.C, 7C#4/0 <br /> // // / / / / / / / / / / / / <br /> 3-1/2"ALC,7C #2/0 -- -- / // / f f/ 1 1/2" AL. CONDUIT # #6 # # <br /> / # / / // ,�/ //�� /-�/�/ ��� '' 3 - 2 + 1 GND -- -- 3 - 2 + 1 6 GND <br /> /,i171`)2//ALj/7)/NDM i 3 #1/0 +1 #4 GND 1 -1/2" AL. CONDUIT 1 -1/2" AL. CONDUIT <br /> TO SERVICE CABINET ' <br /> AT COLUMN E3 SERVICE CABINET BY TO SERVICE CABINET TO SERVICE CABINET TO SERVICE CABINET <br /> INET; LOCATED ON AT COLUMN G1B AT COLUMN G3 AT COLUMN E1A <br /> OTHERWISE SAME 1ST DECK OF TOOL 150AF • OTHERWISE SAME OTHERWISE SAME OTHERWISE SAME <br /> AS E1 B 34FME65B00040 AT N/A ) AS E4.5 AS E4.5 AS E1B <br /> COL. D.4/8.5 I <br /> GATE SERVICE rI <br /> _ _ _ I J LDC <br /> 250AF • <br /> _ GATE SERVICE <br /> 180KVA 150AF • 1 250AF • 180KVA <br /> N/A ) 575V 30,3W ) ° N/A ) 575V 30,3W CENTER NEUTRAL CONDUCTOR CONDUIT <br /> LA.E <br /> I I 100AF I I <br /> I <br /> rYTY .e , <br /> 75 KVA, 575V G I CONTROL ' GND WIRE PULLED <br /> SERVICE CABINET 200/115V , CONTROL 0 0 a LOGIC SEPARATELY WITH <br /> 90 KVA 90 KVA CONTROL BY INET 21/ LOGIC CC PROTECTION 90 KVA 90 KVA CONTROL CABLE INTO CONDUIT <br /> LDC LDC LOGIC m PROTECTION C CIRCUITS I LDC LDC LOGIC I <br /> PROTECTION CIRCUITS � <br /> CUBL, SC. 1 I PROTECTION 1 <br /> CIRCUITS I (OL, UBL, SC. I I (OL, CC LIKE PHASE <br /> I I I OV/UV) I C CIRCUITS(OL,UBL,SC. OV/UV)OV/UV) EPO o (OL,UBL,SC. PARALLELEDfb SAT SOURCE <br /> o ( 0 OOV/UV) EPOIs...1,. .:d6 <br /> & LOAD <br /> 0 o K 1 1K o 0 I o o I — <br /> I I <br /> I I , ® , q � =TAIL 99A99 <br /> #4 AWG. L _ '/ _ _ -__J #4 AWG. TO TB 4 AWG. [...1_1_ s SCALE: NONE <br /> TO LOCAL GND. _ // / / / #4 AWG. TO TB LOCAL GROUND # - - - <br /> ///////i/ LOCAL GROUND TO LOCAL GND. _ <br /> /i/// /, / - / - - <br /> ////////// , 2 / / / = CONDUIT <br /> /////i// ' i / / / 7 #4/0 + 1 #2 GND 8 #14 IN 3/4" AL CONDUIT <br /> // // // / // A6/11' / / GND WIRE PULLED <br /> ////j//// , , // / / / / / E,C` 1'' O (E/, IN 3" AL. CONDUIT <br /> SEPARATELY WITH <br /> / / / ,E3 /LN / / / / / / / <br /> / , / , , , , , , , , ///////// / / / / / / — CABLE INTO CONDUIT <br /> / / /'r'5/ 1�/I/tYi / / / / 7#2 8c 1#4 GND 0 JUNCTION BOX <br /> /)k /RAC ' A/1 / / / / // //// / / / / / / / / / / / / / / Q <br /> / / / / / / // / / ' i ///� 100A _ _ (� (BY INET) AIRCRAFT CABLE <br /> / • 0 <br /> k / ///////////// //////// / / PANEL TYP//, o <br /> / ///// / // , ) 100A �, �, <br /> / / // // , <br /> / // / / / / <br /> , //////�// /�/ / / / / / // �// 1 30A :OA 1 AN3114B <br /> //,/,//j //, j� ''� �A�Pr /��/// I o I RECEPTACLE T - 99 99 <br /> /// ,�// // , /' � )94 / // 40-23 40-23 1 - <br /> / i ��//i , / / / , //`/ /,///.� 30A 0A _TAIL B <br /> / / / 0A [ COLUMN G1 COLUMN G1 SCALE: NONE <br /> ,// / / / // o 0 0 <br /> CX N' E.4 �5/ y gg <br /> / / , / / / / I ,3fi <br /> Z2V22-D.4/8.5-T1 fi <br /> LOCATED ON 1ST <br /> t <br /> • <br /> DECK OF <br /> TOOL 34FME65B00040 Awww.brph.corn Copyright©2019 <br /> STATION D7 \ Architects Engineers, Inc. <br /> / 0 0 — _ 0 \ — L I \ _ I A I J RA V/ 19020 33rd Ave W,Suite 530 State of Washington <br /> Certificate of Authorization <br /> Lynnwood,Washington,98036 Architecture No.603235512 <br /> d SCALE: NONE 425-921-3500 Engineering No.3137 <br /> SYM REVISION BY APPROVED DATE SYM REVISION BY APPROVED DATE _ r DRAWN DATE SUBTITLE CURRENT REVISION SYMBOL DATE <br /> BRIE S �� ACCEPTABILITY VIB 09/17/19 <br /> A Issue For Permit — 767 Rate Increase FA VTB SMS 09/17/19 � owes ��� THIS DESIGN AND/OR CHECKED 400HZ ONE LINE REMOVAL DIAGRAM A 09/17/19 <br /> ti Nf�n rse SPECIFICATION IS APPROVED BLB 09/17/19 <br /> SHEET <br /> s s ' n ► �o �' ENGINEER TITLE <br /> opr <br /> ® ( � !' APPROVED BY DEPT. DATE SMS 09/17/19 767 RATE INCREASE - FA 4T <br /> le <br /> ` <br /> CHECKED <br /> 7 5401ai <br /> APPROVED BUILDING 40®O23 JOB NO. COMP NO. <br /> °� ��cISTER�� ti� EVE-18-30055-602 <br /> ���N�L " ' APPROVED ELECTRICAL MASTER EVERETT, WA DWG No. 40-023-E4TR-602 <br />