Q
<br /> Li
<br /> og �, i� 3 CF\ -PAL \ OILS
<br /> o
<br /> 1 . RACEWAYS: 1/2" EMT MINIMUM, UNLESS OTHERWISE
<br /> NOTED. USE COMPRESSION CONNECTORS AND __
<br /> SEE DWG 40-22-1 E60 COUPLINGS. a
<br /> ____r__ 0
<br /> 2. CONDUCTORS SHOWN: #12 AWG, STRANDED COPPER,
<br /> INSU_ATION TYPE THHN/THWN, UNLESS OTHERWISE
<br /> NOTED.
<br /> 1
<br /> I 3. WHERE SPECIFIED, PROVIDE A SEPARATE DEDICATED
<br /> ctr, line of moving line NEUTRAL FOR EACH DEDICATED CIRCUIT. NEUTRALS n,
<br /> SHALL BE WHITE WITH A TRACER COLORED SAME AS LJ
<br /> I ASSOCIATED PHASE CONDUCTOR. Cl_
<br /> o
<br /> 4. COLOR CODE CONDUCTORS: IDENTIFY CONDUCTORS Li—
<br /> WHICH DO NOT HAVE APPROPRIATELY COLORED w
<br /> INSULATION WITH COLOR TAPE WHEREVER CONDUCTORS
<br /> ARE ACCESSIBLE. IDENTIFY INSULATED GROUND CID
<br /> CONDUCTORS IN ACCORDANCE WITH THE LATEST NEC
<br /> (USING TAPE). COLOR CODE AS FOLLOWS:
<br /> 208Y/120V 480Y/277V
<br /> Ao (LEFT BUS IN PNL) BLACK BROWN
<br /> B0 (CENTER BUS IN PNL) RED ORANGE
<br /> j CO (RIGHT BUS IN PNL) BLUE YELLOW
<br /> NEUTRAL WHITE GRAY
<br /> EQUIPMENT GROUND GREEN GREEN
<br /> ISOLATED GROUND GRN/YEL* GRN/YEL*
<br /> *GREEN WITH YELLOW TRACER
<br /> 5. DYMO LABEL EACH RECEPTACE, JUNCTION/OUTLET BOX
<br /> AND SWITCH WITH CIRCUIT IDENTIFICATION. LABEL
<br /> SYSTEM FURNITURE RECEPTACLES FOR PURPOSE, I.E.
<br /> COMPUTER (DEDICATED CIRCUIT) OR GENERAL POWER
<br /> w USE.
<br /> I
<br /> I:
<br /> z N 6 > (1) 2" CONDUIT FROM CHATSWORTH TO CABLE
<br /> o TRAY IN TRANSPORTATION AISLE CEILING AND
<br /> ANOTHER (1) 2 CONDUIT TO EXISTING CABLE TRAY
<br /> 1 o LOCATED IN FLOOR TRENCH.
<br /> w
<br /> ri
<br /> C0 \ STRLCTIO \ \ OT-S
<br /> V O LIT O \1 \ OT-S
<br /> 1 . DEMOLISH RECEPTACLES IN HATCHED
<br /> AREAS AND THEIR ASSOCIATED CONDUIT
<br /> I AND CONDUCTORS BACK TO SOURCE.
<br /> r
<br /> -.
<br /> I
<br /> 1.
<br /> II
<br /> 11
<br /> 3/4" RGS CONDUIT Y W/PULL CORD
<br /> ��r�III
<br /> - ri.,2 9 b
<br /> 9� b l pp% • IF• It IP• • r.• 03 i'l 0 r' •
<br /> 2V22-13E1 .5 37,39 a42)TYTC) TC) T ®
<br /> (DY4111
<br /> / 1 ,I ff'■j'■V 'Iv 'iv ,a wz r
<br /> c a b ,
<br /> 3/ 'C - 4#10, 1#1 OG 1
<br /> Alb
<br /> rePt),4
<br /> 7i ,. . 1E60 1E61 1E62 1E63 1E64
<br /> �2) DUPLEX RECEPTACLES , ►, 4/ —OA, 120V, DEDICATED rrV
<br /> O PANEL 2V22-13E1 .5 �i �� jE6/ 1 E66 i 1 E67 I 1 E68 1 E69
<br /> �' 2 DEDICATED
<br /> Ora
<br /> i , 'i��` ,%� RECEPTACLES I I I I I I I I I I I I I I I I I VArk#�,t�� ,1 osivilt
<br /> �; 1 E70 1 E71 1 E72 1 E73 1 E74
<br /> CHATSWORT� Bb� OP:4r � ,►�► . ► MIII
<br /> jr' 1 E65 E5 6 2OA 12OVOLT II IIIIIIIIII IIIIII % y� la* �.- - _ .f;_i.,.�if,1_ PLAN BLDG. 40.22
<br /> 13UF2/ O W 2V22-13VE1 r1•�,,, .,,---f,- ;.'W -- , ����- . r SCALE. NONE C')
<br /> 1
<br /> 2V22 8BE3.25/25, o
<br /> °? 27 29 o
<br /> - T 3 4 C - 3 10, 1 10G ! 8' 4' 0 4' 8' 16'
<br /> 75KVA 8 6 I / # # I
<br /> �..- X xt� �x - (6) DUPLEX REC. ON (2) DED. CKTS. 2V22-13E3/9b,11 c NW AM
<br /> 2'C 4 4 10 ® SEE DETAIL 1 , SHT. 40-22-E5361
<br /> • ' c SCALE: 1/8"-1 ,_0„
<br /> /' �. 1 .3UF2 11c 3b 9•-' 11c #10 3/4 C ,/ '.
<br /> +48' 2V22-13VE1/6 8
<br /> z
<br /> L .'
<br /> MATC LINE $0116pd3. 5 1. . . * 3 a 3:.I c a €: .,1 .3UF2/3b OT I 1 3UF2/3b I —r SEE G 40-22-1 E70 _,_ f _ r A tt � k _
<br /> 2V22-13VE1/7a / �-- c �� �1_ ;.
<br /> 1 1 .3UF2 3b '� ry
<br /> 3 4 C-TO COMM. CABLE TRAY ABV. 2ND. FLR. CEIL'G - /
<br /> / — 1 .3UF2 3b www.brph.com
<br /> ART AL � 08Y 120� OW_R LA\ Copyr;,ht©2019
<br /> \ 2V22-13E3
<br /> Architects Engineers, Inc.
<br /> \ State of Washington
<br /> SCALE: 1/8"=1 '-0" /♦ 19020' r
<br /> 33rdAveW,Suite530 9
<br /> CCertificate of Authorization
<br /> Lynnwood," _ i / „ ' ' Lynnwood,Washington,98036 Architecture No.603235512
<br /> ` — ./ 425-921-3500 Engineering No.3137
<br /> SYM REVISION BY APPROVED DATE SYM REVISION BY APPROVED DATE AC -DRAWN DATESUBTITLE CURRENT REVISION SYMBOL DATE
<br /> RIE THIS
<br /> BND/OR CHECKED 09/17/19
<br /> �'0ILITY REMOVAL PARTIAL 208Y/120V POWER PLAN A 09/17/19
<br /> A Issue For Permit — 767 Rate Increase FA VTB SMS 09/17/19 wog wnsH��� r� SPECIFICATION IS APPROVED BLB 09/17/19 SHEET
<br /> T ® ,, ,_ 'Q �, a n ENGINEER TITLE 767 RATE INCREASE — FA
<br /> __, A. /6' PPIOVED BY DEPT. DATE SMS 09/17/19
<br /> Ire'�]—� CHECKED 4
<br /> �`�O �� a. ' - ). 19, APPROVED BUILDING 0-0 JOB NO. COMP NO.
<br /> •� �,sz1g ti EVE-18-30055-602
<br /> �sSIONAL ��� APPROVED DWG NO.
<br /> '+ ELECTRICAL MASTER COL D.5-E/.9-3 EVERETT, WA 40-022-1E65R-602
<br />
|