IF THESE SHEETS ARE NOT 24"X 36"THEN DRAWING IS NOT TO SCALE. <br /> ELEVATOR DRAWING NOTES ELEVATOR GENERAL NOTES -_ L. <br /> TYPICAL: <br /> ACCESSIBLE ELEVATOR REQUIREMENTS <br /> _' <br /> c_, <br /> VERIFY ALL DIMENSIONS WITH ELEVATOR MANUFACTURER-REVIEW SHOP DRAWINGS. 2009 ICC/ANSI A117.1: 0 Typical Accessible Requirement Note This Sheet <br /> SEE SHEETS A0.8a-A0.8b FOR FIRE RESISTIVE ASSEMBLIES U <br /> 407.1 General. Elevators shall comply with Section 407 and ASME A 17.1 listed in Section 105.2.5. Elevators <br /> shall be passenger elevators as classified by ASME A 17.1. Elevator operation shall be automatic. <br /> 00 © TYPICAL ELEVATOR All elevators shall accomodate a wheelchair in accordance with IBC CH 11, 'cc/ANSI A 117.1. The following is a partial ) <br /> NOTE THIS SHEET 407.2 Elevator Landing Requirements. Elevator landings shall comply with Section 407.2 list of those requirements[provided for reference. Refer to complete standards to ensure compliance. <br /> ( _ <br /> 1. ACCESSIBLE MEANS OF EGRESS (IBC 1007.2.1 / 1007.4) 407.2.1 Call Controls. Where elevator call buttons or keypads are provided, they shall comply with Sections Call controls(ICC/ANSI 117.1 Sec 407.2.1) : Call Buttons shall be raised or flush. Objects beneath hall call <br /> THE ELEVATOR IS ONE COMPONENT OF THE ACCESSIBLE MEANS OF EGRESS FROM 407.2.1 and 309.4. �� buttons shall protrude 1 inch maximum. Call buttons and keypads shall be located within one of the reach ranges I �__, <br /> LEVELS ABOVE AND BELOW GRADE. specified in Section 308, measured to the centerline of the highest operable part, per wac 36" min. Call buttons <br /> A. THE ELEVATOR SHALL COMPLY WITH THE EMERGENCY OPERATION AND A clear floor space complying with section 305 shall be provided at call controls. shall be 3/4 inch minimum in the smallest dimension. A 30"x 48"clear floor space shall be provided at call <br /> SIGNALING DEVICE REQUIREMENTS OF SECTION 2.27 OF ASME A171. controls. The call button that designates the up direction shall be located above the call button that designates 1 <br /> B. STANDBY POWER SHALL BE PROVIDED IN ACCORDANCE WITH IBC CH. 27 ® / c_ the down direction. Call buttons shall have visible signals to indicate when each call is registered and when each <br /> AND THE NATIONAL ELECTRICAL CODE. call is answered. <br /> C. PROVIDE DIRECTIONAL SIGNAGE INDICATING THE LOCATION OF THE E �\ Hall signals (ICC/ANSI A117.1 Sec 407.2.2): A visible and audible signal shall be provided at each hoistway <br /> OTHER ACCESSIBLE MEANS OF EGRESS(INTERIOR EXIT STAIRWAYS)AT THE ,, N O 2 / entrance to indicate which car is answering a call and the ear's direction of travel. Where in-car signals are <br /> ELEVATOR LANDINGS (IBC 1007.10). -1- cv -D. ACCESSIBLE ELEVATORS SHALL COMPLY WITH ICC/ANSI A117.1 SECTION 407-SEE ,n 1---- E N E 2A,. provided they shall be visible from the floor area adjacent to the hall call buttons. visible signal fixtures shall be <br /> ACCESSIBILITY THIS centered at 72 inches min above the floor. The visible signal elements shall be 2 1/2 inches min measured <br /> 2. HOISTWAY ENCLOSURENOTES PROTECTIONHISSHEET( (IBC 0 3016.4). ): ELEVATOR HOISTWAYalong the vertical centerline of the element. Signals shall be visible from the floor area adjacent to the hall call <br /> ENCLOSURES SHALL BE CONSTRUCTED AS 2-HOUR SHAFT ENCLOSURES/FIRE / button. Audible signals shall sound once for the up direction and twice for the down direction, or shall have <br /> Fig. 407.2.1.1 verbal annunciators that indicate the direction of elevator car travel. Audible signals shall have a frequency of I <br /> BARRIERS. REFER TO SHEET A006-A006a FOR FIRE RATED ASSEMBLIES. (a) Height of Signals (b) Size of Signals <br /> PENETRATIONS(IBC 708.8& IBC 708.8.1): REFER TO SHEET A007 FOR REQUIREMENTS. Height of Elevator Call button 1500 HZ max. Verbal Annunciators shall have a frequency of 300 HZ min and 3000 max. the audible signal <br /> 3. or verbal annunciator shall be 10 DBA min above ambient, but shall not exceed 80 DBA, measured at the hall <br /> 4. ELEVATOR LOBBY(IBC 808.14.1): Fig. 407.2.2.21 <br /> call button. <br /> A. AN ENCLOSED ELEVATOR LOBBY IS NOT REQUIRED WHERE THE BUILDING IS Elevator Visible Signals 9 Hoistway signs(ICC/ANSI A117.1 Sec 407.2.3) : Floor designations shall be provided in tactile characters z <br /> PROTECTED BY AN AUTOMATIC SPRINKLER SYSTEM INSTALLED IN ACCORDANCE complying with Section ICC A117.1 703.3 located on both jambs of elevator hoistway entrances. Tactile <br /> WITH 903.3.1.1 in <br /> characters shall be 2 inches min in height.A tactile star shall be provided on both jambs at the main entry <br /> 5. TWO-WAY COMMUNICATION (IBC 1007.8): A TWO-WAY COMMUNICATION SYSTEM SHALL <br /> level. Per WAC, braille floor designations must be positioned 48" min. and 60" max. above the floor. Where uu <br /> BE PROVIDED AT THE ELEVATOR LANDING ON EACH ACCESSIBLE FLOOR THAT IS ONE tr <br /> OR MORE STORIES ABOVE OR BELOW THE STORY OF EXIT DISCHARGE= LEVELS 2-4. 408.3 Elevator Door Requirements. Elevator hoistway doors shall comply with Section 408.3. signs indicate that elevators do not serve all landings, signs in tactile characters complying with ICC A117.1 z <br /> 703.3 shall be provided above the hall call fixture. p F- F- <br /> A. PROVIDE COMMUNICATION BETWEEN EACH REQUIRED LOCATION AND A I w w <br /> CENTRAL CONTROL POINT LOCATION APPROVED BY THE FIRE 408.3.1 Sliding Doors. Sliding hoistway and car doors shall comply with Sections 407.3.1 through 407.3.3, and a u) rn <br /> Reopening device(ICC/ANSI A117.1 sec 407.3.3): elevator doors shall be provided with a reopening device <br /> DEPARTMENT. WHERE THE CENTRAL LOCATION IS NOT CONSTANTLY 408.3.3. 4 that shall stop and reopen a car door and hoistway door automatically if the door becomes obstructed by an U "-- <br /> ATTENDED,A TIMED AUTOMATIC TELEPHONE DIAL-OUT CAPABILITY TO A q object or person. The reopening device shall be activated by sensing an obstruction passing through the w CC W <br /> MONITORING LOCATION. 408.4.1 Inside Dimensions of Elevator Cars. Elevator cars shall provide a clear floor area of 42 inches (1065 0 LLI Q <br /> B. THE SYSTEM SHALL INCLUDE BOTH AUDIBLE AND VISIBLE SIGNALS. mm) minimum in width, and 54. -inches(1370 mm) minimum in depth. opening at 5 inches nominal and 29 inches nominal above the floor. The reopening device shall not require <br /> C. DIRECTIONS FOR THE USE OF THE TWO-WAY COMMUNICATION SYSTEM, I physical contact to be activated, although contact shall be permitted before the door reverses. The reopening <br /> INSTRUCTIONS FOR SUMMONING ASSISTANCE, AND WRITTEN <br /> EXCEPTIONS: device shall remain effective for 20 seconds min. <br /> IDENTIFICATION OF THE LOCATION SHALL BE POSTED ADJACENT TO THE TWO- 1. Cars that provide a 51 inches(1295 mm) minimum clear floor width shall be .ermitted to pre60 MINI inches Door and Signal timing (ICC/ANSI Al 17.1 Sec 407.3.4): The minimum acceptable time from notification that a w o 0 <br /> WAY COMMUNICATION SYSTEM. ONE ELEVATOR CAR TO ACCOMMODATE (1295mm) - < 5 <br /> car is answering a call until the doors of that car start to close shall be calculated from the following equation: a N N <br /> AMBULANCE STRETCHER (IBC 3016.12): T=D/(1.5 FT/S)or T=D/(455MM/S)= 5 seconds minimum, where T=time in seconds, D=distance, from CO rn <br /> 5. ELEVATOR CAR SHALL BE OF A SIZE AND ARRANGEMENT TO the point in the lobby or corridor 60 inches directly in front of the farthest call button controlling that car to the j <br /> ACCOMMODATE AN AMBULANCE STRETCHER 24"X 84"WITH NOT LESS 80 MIN 68 MIN z centerline of its hoistway door. <br /> THAN 5" RADIUS CORNERS IN THE HORIZONTAL OPEN POSITION. - •}` z Y <br /> 6. THE ELEVATOR SHALL BE IDENTIFIED BY THE INTERNATIONAL SYMBOL FOR con Q w <br /> EMERGENCY MEDICAL SERVICES(STAR OF LIFE). THE SYMBOL SHALL 54 MIN I 2 ec <br /> ) z z / 6 \ Door delay(ICC/ANSI A117.1 Sec 407.3.5): Elevator doors shall remain fully open in response to a car call <br /> NOT BE LESS THAN 3" HIGH AND PLACED INSIDE ON BOTH SIDES OF THE \ / for 3 seconds minimum. <br /> HOISTWAY DOOR FRAME. II <br /> in to •- ._-. ! <br /> 6. FIREFIGHTER'S EMERGENCY OPERATION (IBC 3003.2): ELEVATORS SHALL BE PROVIDED I I I I �7 Door Width (ICC/ANSI A117.1 Sec 407.3.6): Elevator door clear opening width shall comply with Table I DRAWN BY: KL <br /> WITH PHASE I EMERGENCY RECALL OPERATION AND PHASE II EMERGENCY IN-CAR 36 MIN 36 MIN > 407.4.1. Side opening: 36 inch clear opening width. <br /> OPERATION IN ACCORDANCE WITH ASME A 17.1/CSA B44. -42 MIN 36 MIN 'r 1' "r � CHECK: <br /> 9 fi 4' T $ Elevator car requirements car dimensions (ICC/ANSI A177.1 Sec 407.4: Inside dimensions of elevator cars LJ <br /> centered door (b) side off centered door �� shall comply with Table 407.4.1 leveling. Each car shall be equipped with a self-leveling feature that will <br /> ELEVATOR : BASIS OF DESIGN Door (a) (off-centered) (c) any door location (d)any door location automatically bring and maintain the car at floor landings within a tolerance of 1/2 inch under rated loading to <br /> Door Width: 3'-6" zero loading conditions. Illumination: The level of illumination at the car controls, platform, car threshold and <br /> TO BE VERIFIED Door Height: 7'-0" car landing sill shall be 5 foot-candles (54 lux) minimum. j NOTES: <br /> ThyssenKrupp Elevator-Endura A3500 Shaft(Inside Dimensions) 407.4.4 Leveling. Each car shall be equipped with a self-leveling feature that will automatically bring and maintain 9 > <br /> Car controls (ICC/ANSI A117.1 Sec 407.4.6: Controls shall be located within one of the reach ranges PLOT DATE: 7/20/2017 1:04:14 PM <br /> Shaft Width: 8'-4" the car at floor landings within a tolerance of 1/2 inch (13 mm) under rated loading to zero loading conditions. specified in section 308(per wac 36"min above floor). Car control buttons with floor designations shall be <br /> Shaft Depth: 9'-0" raised or flush. Buttons shall be 3/4 inch min in their smallest dimension. Per WAC, buttons must be JOB NO: <br /> Capacity: 4000 lbs 2012 INTERNATIONAL BUILDING CODE arranged from left to right in ascending order; emergency control buttons shall have their centerlines 35 5215 <br /> Speed: 350/500 fpm Pit Depth: 4'-0" MIN. inches min above the floor. Emergency controls, including the emergency alarm, shall be grouped at the <br /> Overhead: 14' -5" 3001.3 Accessibility: Passenger elevators required to be accessible or to serve as part of an accessible means bottom of the panel. Control buttons shall be identified by tactile characters per ICC A117.1 Sec. 703.3. <br /> Car(Inside Dimensions) of egress shall comply with Section 1107 and 1109.7. Tactile character and braille designations shall be placed immediately to the left of the control button to <br /> Width: 5'-8 5/16" Travel Height Max. : 15'-0" which the designations apply. The control button for the emergency stop, alarm, door open, door close, .> .>:;•:«;:>:w. .> <br /> main entryfloor, andphone shall be identified with tactile symbols as shown in Table 407.4.7.1.3 ` �` <br /> Depth: 7' 5" 3002.1 Hoistway enclosure protection. Elevator, dumbwaiter and other hoistway enclosures shall be shaft Y „ ' <br /> Height: 8'-0" enclosures complying with Section 713. mg <br /> / 10 > Car position indicators(ICC/ANSI Sec 407.4.9: Audible and visible car position indicators shall be t <br /> 3002.1.1 Opening protectives. Openings in hoistway enclosures shall be protected as required in Chapter 7. \ provided in elevator cars. Characters shall be 1/2 inches min in height. Indicators shall be located above <br /> the car control panel or above the door.As the car passes a floor and when a car stops at a floor served IN , <br /> 3002.1.2 Hardware. Hardware on opening protectives shall be of an approved type installed as tested, except that by the elevator, the corresponding character shall illuminate. Audible indicators shall comply with Section <br /> 407.4.9.2. for elevators other than destination-oriented elevators that have a rated speed of 200 ft per 1 <br /> approved interlocks, mechanical locks and electric contacts, door and gate electric contacts and door-operating '` <br /> minute or less, a non-verbal audible signal with a frequency of 1500 hz max that sounds as the car asses !ftt <br /> mechanisms shall be exempt from the fire test requirements. g q Y p INI ' "� ;s <br /> p q or is about to stop at a floor served by the elevator shall be permitted. Per WAC, audible signals must be at *, < ns. `i <br /> 3002.4 Elevator car to accommodate ambulance stretcher.Where elevators are provided in buildings four or least 20 dba. <br /> 7 more stories above, or four or more stories below, grade plane, at least one elevator shall be provided for fire Emergency communications(ICC/ANSI Al7.1 407.4.10: emergency two-waycommunication systems <br /> Jensen/Fey <br /> 11 9 Y 9 Y Y <br /> . department emergency access to all floors. The elevator car shall be of such a size and arrangement to between the elevator car and a point outside the hoistway shall comply with ASME/ANSI A17.1. the Architecture and Planning <br /> accommodate an ambulance stretcher 24 inches by 84 inches (610 mm by 2134 mm)with not less than 5-inch highest operable part of a two-way communication system shall comply with Section 308. per WAC: The 7730 LEARY WAY NE <br /> (127 mm) radius corners, in the horizontal, open position and shall be identified by the international symbol for max height of any operable part is 48 inches AFF. Tactile characters and symbols shall be provided REDMOND, WA 98052 <br /> �` emergency medical services(star of life). The symbol shall not be less than 3 inches(76 mm) high and shall be adjacent to the device. Per WAC the characters must be at least 5/8" but no more than 2" high, raised TEL:425.216.0320 FAX:425.216.0329 <br /> placed inside on both sides of the hoistway door frame. 1/32", upper case, san serif type and accompanied by grade 2 braille. In addition, the following WAC <br /> �> A/ requirements apply: If the system is located in a closed compartment, opening the door to the <br /> 3002.3 Emergency signs.An approved pictorial sign of a standardized design shall be posted adjacent to each compartment must: require the use of only one hand w/o tight grasping pinching or twisting of the wrist& <br /> v elevator call station on all floors instructing occupants to use the exit stairways and not to use the elevators in case require a max force of 51bs. the emergency communication system must not based solely upon voice <br /> HOISTWAY of fire. The sign shall read: IN FIRE EMERGENCY, DO NOT USE ELEVATOR. USE EXIT STAIRS. communication since voice-only systems are inaccessible to people with speech or hearing impairments. <br /> SIGNS <br /> An indicator light must be visible when the telephone is activated. This nonverbal means must enable the <br /> Exceptions: message recipient to determine the elevator's location address and, when more than one elevator is <br /> .1; installed, the elevator's number. The emergency communication system must use a line that is capable of <br /> rn 1. The emergency sign shall not be required for elevators that are part of an accessible means of egress communicating with and signaling to a person or service that can respond appropriately to the emergency <br /> - <br /> o i complying with Section 1007.4.4. at all times. A communication device must be installed in the lobby adjacent to the phase 1 key switch. U) <br /> ° '- 2. The emergency sign shall not be rquired for elevators that are used for self evacuation in accordance with This device must be a two way communication device used to communicate with individuals in the J <br /> n° Section 3008. elevator. The height of any communication device(s) located in the lobby must be between 48-60 inches CD <br /> AFF. Additional communication device(s) may also be located in other parts of the building in addition to NI <br /> i! in \ ELEVATOR MACHINE ROOMS: the one located in the lobby. Exception: Elevators that have less than sixty feet of travel do not require an CO (- <br /> intercom. W <br /> Q 1 > 3006.1 Access.An approved means of access shall be provided to elevator machine rooms and overhead 12 \ Car handrails(WAC 296-96-02340): a handrail must provide coverage lengthwise at least 90%from wall W cn <br /> DOOR machinery spaces. / to wall. a handrail must be installed on all car walls not used for normal exits. the handrails must be: <br /> j REOPENING \� CALL A. attached to the wall at a height of between 32-35 inches from the floor. <br /> c,- - - CONTROLS 3006.2 Venting. Elevator machine rooms that contain solid-state equipment for elevator operation shall be B. attached to the wall with a 1 1/2 inch space between the wall and the rail LLin <br /> n z <br /> ^ • • • provided with an independent ventilation or air-conditioning system to protect against the overheating of the C. constructed with the hand grip portion not less than 1 1/4 inches but not more than 2 inches wide LL <br /> electrical equipment. The system shall be capable of maintaining temperatures within the range established for the D. constructed with a cross-section shape that is substantially oval or round 0 i <br /> � ;ER <br /> elevator equipment. E. constructed with smooth surfaces and no sharp corners. V <br /> 3"X 3/8" STEEL ANCHOR.TYP. ® W U) <br /> HALL ELEVATION approaching handrail ends on a blank wall in the interior corners of a car do not have to return toP PLAN 3006.3 Pressurization.The elevator machine room serving a pressurized elevator hoistway shall be pressurized the wall. however, if the handrail is located on the closing door wall of a single-slide or two-speed W <br /> 3"X 3/8"STEEL I/ upon activation of a heat or smoke detector located in the elevator machine room. entrance elevator and it projects an a brupt end towards people entering the car, the handrail end I- <br /> BAR STRINGERS q must return to the wall. '� \ H- <br /> WITH 20"WIDE X - 3006.4 Machine rooms and Machinery spaces: Elevator machine rooms and machinery spaces shall be F. Approaching handrail ends on a blank wall in the interior corners of a car do not have to return to / <br /> 3/4" DIAM RUNGS enclosed with fire barriers constructed in accordance with Section 707 or horizontal assemblies constructed in the wall. However, if the handrails located on the closing door wall of a single-slide or two-speed -1 LLB <br /> @ 12"O.C. - < 7 > accordance with Section 711, or both. The fire-resistance rating shall not be less than the required rating of the entrance elevator and it projects an abrupt end towards people entering the car. The handrail end < N Et <br /> SEE PLAN FOR WALL DETAILS hoistway enclosure served by the machinery. Openings in the fire barriers shall be protected with assemblies must return to the wall. Ha W <br /> / having a fire protection rating not less than that required for the hoistway enclosure doors. W <br /> LOWEST FLOOR / <br /> 3 F-- <br /> \ / / '0 Exceptions: Q <br /> 4/ 3"X 3/8" STEEL ANCHOR.TYP. <br /> 1. Where machine rooms and machinery spaces do not abut and have no openings to the hoistway enclosure <br /> // 9 they serve the fire barriers constructed in accordance with Section 707 or horizontal assemblies constructed N Q LL) <br /> in accordance with Section 711. or both, shall be permitted to be reduced to a 1- hour fire-resistance rating. Q I -I <br /> 1-- -1 W <br /> 2. In buildings four stories or less above grade plane when machine room and machinery spaces do not abut <br /> w CONCRETE PIT SLAB o o y and have no openings to the hoistway enclosure they serve, the machine room and machinery spaces are W <br /> 2 1/2"X 2 1/2"X 3/8" STEEL ANGLE a ON GRADE SEE o o not required to be fire-resistance rated. C) --.1WELDED TO STRINGER- F- STRUCTURAL p p p Et <br /> r Q <br /> BOLT TO PIT FLOOR -a -fl D D <br /> / X X 3006.5 Shunt trip. Where elevator hoistways or elevator machine rooms containing elevator control equipment W T' 0 <br /> / < x are protected with automatic sprinklers, a means installed in accordance with NFPA 72, Section 6.16.4, Elevator > N <br /> / b Shutdown, shall be provided to disconnect automatically the main line power supply to the affected elevator prior to a. <br /> I the application of water. This means shall not be self-resetting. The activation of sprinklers outside the hoistway or <br /> machine room shall not disconnect the main line power supply. (1) <br /> to <br /> co <br /> FIRE ALARM SYSTEM shall have permanently installed audible and visible alarms complying with NFPA 72 (1999 - -- <br /> or 2012 additions) & req'd by local KLities. Alarms must be located in public and common use areas &Guest <br /> • �. rooms designated as"guest rooms w/communication features" @ a min. where employee areas have audible <br /> alarms, the wiring shall be designated so visible alarms can be integrated into the system, unless greater. St"FE--: <br /> 11 > 1007.4 Elevators. In order to be consideredpart of an accessible means of egress, an elevator shall comply with <br /> ELEVATOR PIT LADDER CAR INTERIOR ELEVATION g p Y <br /> rii--� the emergency operation and signaling device requirements of Section 2.27 of ASME A17.1. Standby power shall <br /> be provided in accordance with Chapter 27 and Section 3003. The elevators shall be accessed from either an areaA46 <br /> 1 / 2 " = 1 '-0" ELEVATOR ACCESSIBILITY GUIDELINES of refuge complying with Section 1007.E or a horizontal exit. <br /> THE ABOVE DRAWINGS SHOW THE DESIGN REQUIREMENTS FOR AN ACCESSIBLE ELEVATOR, AND SHOULD BE <br /> USED ONLY AS A GUIDELINE. THIS ELEVATOR MUST CONFORM TO REQUIREMENTS IN ICC/ANSI A117.1 <br /> ACCESSIBLE ELEVATORS SHALL BE DESIGNED AND CONSTRUCTED ACCORDING TO CH. 296-96 OF WA. ADMIN. <br /> CODE&CH. 30 SBC. <br /> 1 <br />