Laserfiche WebLink
Power Electronics/Switchgear and Networks vcv` Power <br /> Change Order Form Generation <br /> Project Name: EverettWWTP Change order#: 3 <br /> CPG Sales Order#: 126396 Date of Change: 5/20/21 <br /> Sales Engineer: Marlan Howell Change Impact(weeks): *Contact CPM <br /> System Type: Type 9 Distributor-Contact: Jeff Delauney <br /> Change order description: <br /> Cummins to modify sequence of operation and PLC software to accommodate the request to remove control from the utility recloser breaker. <br /> This affects the following sequences: <br /> •Utility failure <br /> •Utility unload <br /> •Utility retransfer <br /> •Breaker failure sequences <br /> •Eail to disconnect <br /> Cummins will need to modify the unexpected open and unexpected close logic from the utility recloser to incorporate control from an external <br /> source without notification.Breaker fail to close and breaker fail to open will be communicated via SEL2505 per change order#1,making <br /> CO#1 mandatory. <br /> MATERIALS: <br /> Change order requested: <br /> Change Order $14,342 <br /> Factory comments <br /> 0 <br /> Distributor comments <br /> 0 <br />