(TYPICAL OF 6) EF-43,44,45,46,47,48
<br /> T 0
<br /> ,>
<br /> GAS i > SA EACI >
<br /> OA HEATER
<br /> /
<br /> FOR VFD EMCS SP EMCS
<br /> CONNECTION VFD
<br /> 4 VFD
<br /> El I NO SEE ELECTRICAL FOR TYPICAL VFD
<br /> SHEETS w CONNECTION SEE
<br /> o zo ELECTRICAL SHEETS
<br /> Q a Q
<br /> a w co w 0 O w
<br /> w ° ¢ I-. n w O w 0
<br /> a. Q w > H cn cn
<br /> to Q Q Q Z Q Z
<br /> Q O > a w a w
<br /> Q � N cn cn cn cn
<br /> EMCS EMCS EMCS EMCS EMCS EMCS EMCS EMCS EMCS
<br /> (TYPICAL OF 3)
<br /> MAKEUP AIR UNIT
<br /> MAU-01, 02, 03
<br /> AUTOCLAVE PIT VENTILATION SYSTEM
<br /> MAKEUP AIR UNIT NORMAL OPERATION:
<br /> SYSTEM DESCRIPTION: THREE MAKE-UP AIR UNITS, EACH COMPRISED OF AN OUTSIDE AIR PATH WITH OUTSIDE AIR DAMPER, FILTERS (MERV
<br /> 13), DIRECT FIRED GAS HEATER, VARIABLE SPEED SUPPLY FAN, AND ALL ASSOCIATED APPURTENANCES AND DEVICES DEPICTED ON THE
<br /> CONTROL SYSTEM DIAGRAM. THE EXHAUST FAN SYSTEM IS COMPRISED OF(6)VARIABLE VOLUME EXHAUST FANS WITH VFDS, ONE OF WHICH
<br /> IS FUTURE, AND ALL ASSOCIATED APPURTENANCES AND DEVICES DEPICTED ON THE CONTROL SYSTEM DIAGRAM.
<br /> GENERAL: THE SYSTEM SHALL BE AVAILABLE FOR OPERATION AT ALL TIMES DEFINED BELOW TO MAINTAIN SPECIFIC SPACE PARAMETERS.
<br /> OTHERWISE, THE SYSTEM SHALL BE IN UNOCCUPIED MODE. ALL CONTROLS SHALL BE AUTOMATIC.
<br /> DEFINED OCCUPIED PERIOD: MON-FRI: 4:OOAM-11:OOPM AND SAT-SUN: 5:OOAM-5:OOPM
<br /> MAINTENANCE: WHEN THE MAU SUPPLY FAN IS OFF FOR MAINTENANCE, RESPECTIVE CONTROL DEVICES SHALL BE POSITIONED AS
<br /> FOLLOWS:
<br /> 1. CONTROL VALVES POSITIONED CLOSED.
<br /> 2. OUTDOOR AIR DAMPER POSITIONED CLOSED.
<br /> SYSTEM START/STOP: THE UNITS SHALL BE STARTED/STOPPED BY THE EMCS ACCORDING TO THE SPACE TEMPERATURE SETPOINT AND THE
<br /> CURRENT MODE.
<br /> UNOCCUPIED MODE: THE SYSTEM SHALL REMAIN IN UNOCCUPIED MODE UNLESS THE SPACE PUSH BUTTON STYLE OCCUPANCY SWITCH IS
<br /> PLACED IN THE OCCUPIED POSITION, WHICH SHALL PLACE THE SYSTEM IN OCCUPIED MODE FOR A PERIOD OF 90 MINUTES. AFTER 90
<br /> MINUTES, THE SYSTEM SHALL AUTOMATICALLY RETURN TO UNOCCUPIED MODE. THE SYSTEM SHALL BE DISABLED NORMALLY. ALL DEVICES
<br /> SHALL BE THEIR RESPECTIVE OFF POSITION. THE UNITS SHALL OPERATE IN UNOCCUPIED HEATING AND COOLING MODES AS DESCRIBED
<br /> BELOW.
<br /> UNOCCUPIED HEATING: IF THE AVERAGE SPACE TEMPERATURE FALLS BELOW SETPOINT OF 62°F (ADJ.), THE LEAD MAU SHALL BE
<br /> COMMANDED ON AFTER THE OUTSIDE AIR DAMPER IS CONFIRMED TO BE OPEN. THE SUPPLY FAN SHALL BE RUN AT 100% (ADJ.) SPEED
<br /> (DETERMINED BY TAB CONTRACTOR). THE GAS VALVE SHALL BE OPENED AT 100%AFTER A 2 MIN (ADJ.)TIME DELAY. UNIT SHALL RUN UNTIL
<br /> THE SPACE TEMPERATURE RISES ABOVE 65°F (ADJ.).
<br /> THE EXHAUST FANS ASSOCIATED WITH THE MAU SHALL BE RUN AT FULL SPEED (DETERMINED BY TAB CONTRACTOR). THE LAG MAU'S SHALL
<br /> BE ADDED IF SPACE TEMPERATURE REMAINS BELOW THE SETPOINT FOR ADDITIONAL 15 MIN (ADJ.). EACH MAU SHALL RUN A MINIMUM OF 15
<br /> MINUTES OR UNTIL THE TEMPERATURE SETPOINT IS SATISFIED, WHICHEVER IS GREATER.
<br /> UNOCCUPIED VENTILATION: IF THE AVERAGE SPACE AIR TEMPERATURE RISES ABOVE SETPOINT OF 78°F (ADJ.)AND OUTSIDE AIR TEMP IS
<br /> BELOW 70°F (ADJ.)AND ABOVE 50°F (ADJ.), ONE MAU &TWO EXHAUST FANS ASSOCIATED WITH THE MAU SHALL RUN AT PRESET CONSTANT
<br /> SPEED CORRESPONDING TO 24,000 CFM (DETERMINED BY TAB CONTRACTOR). EACH UNIT SHALL RUN A MINIMUM OF 15 MINUTES OR UNTIL
<br /> THE TEMPERATURE SETPOINT IS SATISFIED, WHICHEVER IS GREATER.
<br /> AUTOCLAVE CYCLE MODE: IF THE EMCS RECEIVES A SIGNAL FROM THE AUTOCLAVE SUPPORT SYSTEM PLC, ONE MAKEUP AIR UNIT AND ONE
<br /> EXHAUST FAN SHALL BE STARTED PER AUTOCLAVE CYCLE. THE MAU FAN SHALL BE COMMANDED TO ITS MINIMUM SPEED OF
<br /> CORRESPONDING TO 24,000 CFM. THE EXHAUST FAN SHALL MODULATE TO MAINTAIN A POSITIVE PRESSURE OF 0.025 IN W.G. (ADJ.) IN THE
<br /> AUTOCLAVE AREA WITH RESPECT TO THE EXTERIOR. WHEN THE EXHAUST FAN REACHES ITS MINIMUM SPEED, THE MAU FAN SPEED SHALL
<br /> MODULATE UPWARD TO MAINTAIN A POSITIVE PRESSURE OF 0.025 IN W.G. (ADJ.)THE GAS VALVE SHALL ENERGIZE AS NECESSARY BASED ON
<br /> THE HEATING MODE DESCRIPTION.
<br /> HEATING MODE: IF THE SPACE TEMPERATURE, AS MEASURED BY THE SPACE TEMPERATURE SENSORS (AVERAGE OF ALL THREE), IS BELOW
<br /> HEATING SETPOINT OF 65°F FOR MORE THAN 5 MINUTES, THE UNIT SHALL BE STARTED AND PLACED IN HEATING MODE. IF THE SPACE
<br /> TEMPERATURE IS 2°F ABOVE THE HEATING SETPOINT FOR MORE THAN 5 MINUTES, THE UNIT SHALL BE STOPPED. IF THE SPACE
<br /> TEMPERATURE IS BELOW THE HEATING SETPOINT FOR A PERIOD OF 10 MINUTES (ADJ.), THE FIRST LAG MAU SHALL BE ENABLED. IF THE
<br /> SPACE TEMPERATURE IS BELOW THE HEATING SETPOINT FOR AN ADDITIONAL 20 MINUTES (ADJ.), THE NEXT LAG MAU SHALL BE ENABLED.
<br /> IF THE SPACE TEMPERATURE IS 2°F (ADJ.)ABOVE THE HEATING SETPOINT, THE FIRST LAG MAU SHALL BE DISABLED. IF THE SPACE
<br /> TEMPERATURE IS STILL 2°F (ADJ.)ABOVE THE HEATING SETPOINT FOR AN ADDITIONAL 10 MINUTES (ADJ.), THE NEXT LAG MAU SHALL BE
<br /> DISABLED. IF THE SPACE TEMPERATURE IS 2°F (ADJ.)ABOVE THE HEATING SETPOINT FOR AN ADDITIONAL 10 MINUTES (ADJ.), THE LEAD MAU
<br /> SHALL BE DISABLED.
<br /> COOLING MODE: IF THE SPACE TEMPERATURE, AS MEASURED BY THE SPACE TEMPERATURE SENSORS (AVERAGE OF ALL THREE) IS ABOVE
<br /> COOLING SETPOINT OF 80°F FOR MORE THAN 5 MINUTES, ONE EXHAUST FAN SHALL BE STARTED AND MODULATED TO MAINTAIN ROOM
<br /> TEMPERATURE SETPOINT, INITIALLY SET AT 80°F. EXHAUST FANS SHALL CONTINUE TO BE ADDED AND RAMPED UP/DOWN SIMULTANEOUSLY IF
<br /> THE SPACE TEMPERATURE REMAINS ABOVE COOLING SETPOINT OF 80°F FOR AN ADDITIONAL 15 MINUTES. IF THE SPACE TEMPERATURE IS
<br /> BELOW COOLING SETPOINT OF 80°F FOR MORE THAN 5 MINUTES, ONE EXHAUST FAN SHALL BE SUBTRACTED FROM THE OPERATION.
<br /> EXHAUST FANS SHALL CONTINUE TO BE SUBTRACTED IF THE AVERAGE SPACE TEMPERATURE REMAINS 5°F BELOW COOLING SETPOINT OF
<br /> 75°F FOR 15 MINUTES. TWO EXHAUST FANS SHALL OPERATE FOR EVERY MAKEUP AIR UNIT AND SET ONE MAU TO A PRESET CONSTANT
<br /> SPEED CORRESPONDING TO 24,000 CFM (ADJ.) (DETERMINED BY THE TAB CONTRACTOR), AND TWO EFS TO A PRESET CONSTANT SPEED
<br /> CORRESPONDING TO 12,000 CFM (ADJ.) (DETERMINED BY THE TAB CONTRACTOR).
<br /> SUPPLY FAN CONTROL: THE EMCS SHALL START/STOP EXHAUST AND MAU FANS BASED ON SYSTEM START/STOP. SUPPLY FAN SHALL NOT BE
<br /> STARTED UNTIL THE OUTSIDE AIR DAMPER HAS BEEN FULLY OPENED. IF THE SUPPLY FAN FAILS TO START/STOP BASED ON SYSTEM
<br /> OPERATION, AS INDICATED BY CURRENT SENSOR, AN ALARM SHALL BE SENT AND DISPLAYED AT THE EMCS.
<br /> HEATING: THE EMCS CONTROLLER SHALL MODULATE THE DIRECT FIRED GAS HEATER BY MODULATING THE GAS HEATING CONTROL VALVE TO
<br /> MAINTAIN THE SPACE TEMPERATURE SETPOINT, INITIALLY SET AT 65°F, AS MEASURED BY THE SPACE TEMPERATURE SENSOR. THE EMCS
<br /> CONTROLLER SHALL MODULATE THE GAS HEATING CONTROL VALVE VIA A 2-10 VDC SIGNAL.
<br /> OUTSIDE AIR DAMPER CONTROL: THE OUTSIDE AIR DAMPER SHALL BE FULLY OPENED WHEN THE SYSTEM IS STARTED AND FULLY CLOSED
<br /> WHEN THE SYSTEM IS STOPPED. DAMPER POSITION SHALL BE PROVED BY END SWITCH INTERNAL TO DAMPER ACTUATOR.
<br /> EXHAUST FAN OPERATION: EXHAUST FANS SHALL BE STARTED/STOPPED ACCORDING TO THE CURRENT MODE IN CONJUNCTION WITH THE
<br /> MAKEUP AIR UNITS. EXHAUST FANS SHALL BE STARTED AFTER A 15 SECOND TIME DELAY. IF ANY EXHAUST FAN FAILS TO START/STOP BASED
<br /> ON SYSTEM OPERATION, AS INDICATED BY CURRENT SENSOR, AN ALARM SHALL BE SENT AND DISPLAYED AT THE EMCS. THE NEXT EXHAUST
<br /> FAN, BASED ON RUN HOURS SHALL BE STARTED.
<br /> LEAD/LAG ROTATION: LAG EQUIPMENT SHALL BE ROTATED DAILY. ``!! ee
<br /> PROVIDE CONTINUOUS MONITORING OF THE FOLLOWING POINTS AND DISPLAY AT THE EMCS: CITY OF EVERETggT yy ' ,
<br /> y�t`�t�WE.O Ff����R�t
<br /> 1. OUTSIDE AIR DAMPER POSITION REV
<br /> 2. SPACE TEMPERATURE (°F)
<br /> 3. HEATING CONTROL VALVE POSITION
<br /> 4. SUPPLY FAN STATUS
<br /> 5. DISCHARGE TEMPERATURE
<br /> LOW OXYGEN EXHAUST PURGE MODE: ON A SIGNAL FROM THE AUTOCLAVE SUPPORT SYSTEM PLC THAT A LOW OXYGEN CONDITION EXISTS, ;.Y..-. ....,,:i
<br /> THREE MAU'S AND FIVE EXHAUST FANS SHALL BE COMMANDED ON AFTER ALL OA DAMPERS ARE CONFIRMED TO BE IN THE OPEN POSITION. �`�5 '. \NG C- $�
<br /> THE MAU FANS SHALL BE COMMANDED TO A PRESET CONSTANT SPEED (DETERMINED BY TAB CONTRACTOR) CORRESPONDING TO 16,200
<br /> .::::, wOF WAskt, v� `'
<br /> CFM EACH WHILE ALL THREE EXHAUST FANS SHALL BE COMMANDED TO A FULL AND CONSTANT PRESET SPEED CORRESPONDING TO 18,000 :'` C
<br /> BRPH
<br /> CFM EACH. IF THE OA TEMPERATURE IS BELOW 35°F (ADJ.), THE GAS VALVE SHALL BE FULLY OPENED TO PROVIDE HEATING. THE LOW1111111 ''Wye '� :
<br /> OXYGEN EXHAUST PURGE MODE SHALL REMAIN ACTIVE UNTIL THE LOW OXYGEN SIGNAL IS RELEASED FROM THE AUTOCLAVE SUPPORT ; , ' f�r-�r �;
<br /> SYSTEM PLC INDICATING THAT THE OXYGEN LEVEL IS MET. www.btph.com Copyright 0 2018 ,
<br /> Architects Engineers, Inc. '°gyp 51476 0 ~/''
<br /> Side at'� sk �GISTV, N' ..:
<br /> t9QZ0331tl__ 530 Ax101plydlWNla fon SSIONAL ' Ct::>::``: :
<br /> 4 ;fit too,603235512 is:.:; ss; 2
<br /> Pk.3137 ✓' Q
<br /> N
<br /> DRAWN DATE SUBTITLE CURRENT REVISION SYMBOL DATE _0
<br /> SYM REVISION BY APPROVED DATE SYM REVISION BY APPROVED DATE of WA Sy ACCEPTABILITY JXK 06/12/18 AUTOCLAVE PIT VENTILATION CONTROLS W2548317 0 06/12/18
<br /> PNCl THIS DESIGN AND/OR CHECKED '
<br /> 0 ISSUE FOR CONSTRUCTION JXK JLC 06/12/18 ( /' JEW 06/12/18 SHEETSPECIFICATION IS APPROVED
<br /> SZ)i w.
<br /> BDE���® 9ENG ENGINEERS INC
<br /> ENGINEER TITLE Boeing 777X CWC BUILDING N
<br /> ENGINEEHSINC. APPROVED BY DEPT. DATE JLC 06/12I18
<br /> IV!N0.3137 CHECKED
<br /> 324 a
<br /> BUILDING 40-58 o APPROVED JOB NO. COMP NO.
<br /> 40-58-M324a
<br /> F tiP� APPROVED DWG No.
<br /> PyrF OF AUZN�� MECHANICAL MASTER EVERETT, WA 40-58-M324a
<br />
|