<br /> •
<br /> MAKEUP AIR UNIT SCHEDULE
<br /> DESIGN CONDITIONS ELECTRICAL DATA BASIS OF DESIGN AUTOCLAVE
<br /> AIR VOLUME OUTPUT UNIT WEIGHT INSTALL
<br /> MARK CFM ESP(IN.WG) TSP(IN.WG) DB(F) WB(F) WINTER DB (F) MOTOR RPM BHP MOTOR HP HEATING TYPE GAS TYPE INPUT(MBH) (MBH) LAT(F) TEMP RISE (F) VOLTS/PH MCA MOP MANUFACTURER MODEL (LBS) PHASE
<br /> MAU-01 36,000 0.25 1.55 85 70 21 1725 26.9 30 DIRECT GAS NATURAL 2,282.1 2,099.5 75 54 460/3 50.9 90 GREENHECK DGX-133-H42 4,582 AUTOCLAVE 1
<br /> MAU-02 36,000 0.25 1.55 85 70 21 1725 26.9 30 DIRECT GAS NATURAL 2,282.1 2,099.5 75 54 460/3 50.9 90 GREENHECK DGX-133-H42 4,582 AUTOCLAVE 1
<br /> MAU-03 36,000 0.25 1.55 85 70 21 1725 26.9 30 DIRECT GAS NATURAL 2,282.1 2,099.5 75 54 460/3 50.9 90 GREENHECK DGX-133-H42 4,582 AUTOCLAVE 2
<br /> NOTES:
<br /> 1. REFER TO SPECIFICATION SECTION 23 73 39-OUTDOOR, DIRECT-FIRED HEATING AND VENTILATING UNITS.
<br /> 2. COORDINATE FAN MOTOR WITH VFD(FURNISHED AND INSTALLED BY DIV 23,WIRED BY DIV 26).
<br /> 3. H-O-A DISCONNECT PROVIDED BY DIV 26.
<br /> 4. HORIZONTAL UNIT CONFIGURATION WITH BOTTOM DISCHARGE SHALL CONSIST OF AN INTAKE SECTION,AN ANGLED FILTER SECTION WITH MERV 13 FILTERS, A GAS-FIRED HEATING COIL SECTION, AND A FAN SECTION. GENERAL NOTES
<br /> 5. EMCS CONTRACTOR SHALL PROVIDE CONTROL POINTS PER CONTROL DIAGRAMS.
<br /> 6. PROVIDE WITH MANUFACTURED INSULATED ROOF CURB.
<br /> 7. PROVIDE WITH EXTERNAL DDC TEMPERATURE CONTROL(2-10 VDC). 1. EQUIPMENT, PIPING, ETC. THAT IS GREYED OUT IS
<br /> EITHER EXISTING OR TO BE INSTALLED WITH
<br /> SUBSEQUENT AUTOCLAVES AT A LATER DATE.
<br /> REFER TO AUTOCLAVE SUBSYSTEM SCHEDULES
<br /> FOR INDICATION OF INSTALLATION PHASE.
<br /> ...,..,,...: .
<br /> •
<br /> .4101:17:i:, • •
<br /> \, O� 4VAsly 4�
<br /> ,,, ,:,,„,.2z.,:,, ,,,a,..) f., 1 1 ,k ., ;::;:..0:-.
<br /> ' � Q �, ���
<br /> www.brph.cotn apyrigfit 2018 r
<br /> Architects'Engineers, Inc. �o 5 i 47s��� �
<br /> Meee'Was gtan :s.; -4' �GISTEg (1\ :.
<br /> 1M dAve„,Ss , C rtet'Adhortze :: S;SIONA L E.'
<br /> 125 �954tt No.3f31
<br /> b n: Ardthectnre No.&J32355t2 - • " z s Q
<br /> co
<br /> DRAWN DATE SUBTITLE CURRENT REVISION SYMBOL DATE
<br /> 5.(M REVISION BY APPROVED DATE SYM REVISION BY APPROVED DATE sy ACCEPTABILITY JXK 06/12/18W2548317 0 06/12/18((I-T.-WA
<br /> 0rTHIS DESIGN AND/OR CHECKED SCHEDULES SHEET0 ISSUE FOR CONSTRUCTION JXK JLC 06/12/18 c JEW 06/12118 SPECIFICATION IS APPROVEDRPHARCHITECTS ENGINEER TITLE Boeing 777X CWC BUILDING E '
<br /> IV itYlr it ir ,s„ - if
<br /> ® ENGINEERS INC. APPROVED BY DEPT. DATE JLC 06/12/18 N12���]Q ip
<br /> BUILDING 40-58
<br /> ., o APPROVED JOB NO. COMP NO.
<br /> 40-58-M2c-a
<br /> DWG NO.
<br /> FrgrF OF A�TH��`tiP� APPROVED MECHANICAL MASTER EVERETT, WA 40-58-M2c-a
<br />
|