Laserfiche WebLink
GENERAL STRUCTURAL NOTES <br />DESIGN CRITERIA <br />CODE: 2015 IBC/IRC & AMENDMENTS AS ADOPTED BY THE REVIEWING AGENCY/COUNTY. <br />ROOF........................................25 PSF SNOW (GROUND) <br />FLOORS <br />RESIDENTIAL .....................40 PSF <br />BALCONY/DECK................60 PSF <br />GENERAL CONDITIONS <br />1. THE CONTRACTOR SHALL EXAMINE THE STRUCTURAL DRAWINGS AND SHALL NOTIFY THE STRUCTURAL <br />ENGINEER OF ANY DISCREPANCIES HE MAY FIND BEFORE PROCEEDING WITH THE WORK. <br />2. THE CONTRACTOR SHALL VERIFY ALL DIMENSIONS, ELEVATIONS AND SITE CONDITIONS BEFORE <br />STARTING WORK. THE ARCHITECT/ENGINEER SHALL IMMEDIATELY BE NOTIFIED IN WRITING OF ANY <br />DISCREPANCIES. <br />3. ALL OMISSIONS OR CONFLICTS BETWEEN THE VARIOUS ELEMENTS OF THE WORKING DRAWINGS SHALL <br />BE BROUGHT TO THE ATTENTION OF THE ARCHITECT AND THE STRUCTURAL ENGINEER BEFORE <br />PROCEEDING WITH ANY WORK SO INVOLVED. <br />4. IN CASE OF CONFLICT, NOTES AND DETAILS OF THESE STRUCTURAL DRAWINGS SHALL TAKE <br />PRECEDENCE OVER THE "GENERAL NOTES" AND/OR "STANDARD DETAILS". <br />5. IF A SPECIFIC DETAIL IS NOT SHOWN FOR ANY PART OF THE WORK, THE CONSTRUCTION SHALL BE THE <br />SAME AS FOR SIMILAR WORK. <br />6. WORKING DIMENSIONS SHALL NOT BE SCALED FROM PLANS, SECTIONS, OR DETAILS ON THESE <br />DRAWINGS. <br />7. THE CONTRACTOR SHALL IMMEDIATELY NOTIFY THE ARCHITECT AND THE STRUCTURAL ENGINEER OF ANY <br />CONDITION WHICH IN HIS OPINION MIGHT ENDANGER THE STABILITY OF THE STRUCTURE OR CAUSE <br />DISTRESS TO THE STRUCTURE. <br />8. THE CONTRACTOR SHALL SUPERVISE AND DIRECT HIS WORK AND HE SHALL BE SOLELY RESPONSIBLE <br />FOR CONSTRUCTION MEANS, METHODS, TECHNIQUES, SEQUENCES AND PROCEDURES. PROVIDE <br />ADEQUATE SHORING AND BRACING OF ALL STRUCTURAL MEMBERS DURING CONSTRUCTION. <br />9. ALL WORK SHALL CONFORM TO THE MINIMUM STANDARDS OF THE LATEST EDITION OF THE <br />INTERNATIONAL BUILDING CODE, AND ALL OTHER REGULATING AGENCIES EXERCISING AUTHORITY OVER <br />ANY PORTION OF THE WORK. <br />10. SPECIFIC NOTES AND DETAILS SHALL TAKE PRECEDENCE OVER GENERAL NOTES AND TYPICAL DETAILS. <br />WHERE THE NOTES, DRAWINGS, AND/OR SPECIFICATIONS DIFFER, THE MORE STRINGENT REQUIREMENT <br />SHALL APPLY. <br />11. REFER TO THE ARCHITECTURAL DRAWINGS FOR INFORMATION NOT COVERED BY THESE GENERAL NOTES <br />OR THE STRUCTURAL DRAWINGS. <br />12. NOTIFY ENGINEER OF ALL FIELD CHANGES PRIOR TO INSTALLATION. <br />13. DISCREPANCIES FOUND BETWEEN STRUCTURAL DRAWINGS AND OTHER DOCUMENTS ARE TO BE NOTED <br />IN WRITING TO THE ENGINEER PRIOR TO CONSTRUCTION. <br />14. ALL CONSTRUCTION SHALL BE DONE WITH MATERIALS, METHODS, AND WORKMANSHIP ACCEPTED AS <br />GOOD PRACTICE BY THE CONSTRUCTION INDUSTRY IN CONFORMANCE TO THE PROVISIONS OF THE <br />"INTERNATIONAL BUILDING CODE" (IBC), AND STANDARDS REFERENCED THEREIN. <br />16, STRUCTURAL STABILITY OFALL NEW AND EXISTING STRUCTURES DURING CONSTRUCTION SHALL BE <br />THE RESPONSIBILITY OF THE CONTRACTOR. THIS INCLUDES EXCAVATIONS, COLUMNS, EQUIPMENT <br />LOADS, MATERIAL LOADS, AND OTHERS. OBSERVATIONS BY THE ENGINEER -OF -RECORD DO NOT <br />INCLUDE INSPECTIONS OF TEMPORARY LOADING AND STABILITY DURING CONSTRUCTION. <br />16. MINIMUM ASSUMED SOIL BEARING CAPACITY ............... 3,000 PSF <br />CONCRETE ANCHORS <br />1. ALL SPECIFIED CONCRETE ANCHORS SHALL BE SIMPSON STRONG TIE, HILTI, OR EQUIVALENT. SPECIAL <br />INSPECTIONS REQUIRED. <br />STRUCTURAL AND MISC. STEEL <br />1. REFERENCE STANDARDS: DESIGN, FABRICATION AND ERECTION ARE TO BE IN ACCORDANCE WITH THE <br />LATEST EDITION OF THE AISC "CODE OF STANDARD PRACTICE FOR STEEL BUILDINGS AND BRIDGES". <br />2. MATERIALS: <br />BOLTS - ASTM A307, UNLESS OTHERWISE NOTED <br />WF BEAMS -ASTM A572-50 (Py = 50,000 PSI) <br />HSS ROUND COLUMNS - ASTM A500 Gr. B (Fy = 42,000 PSI) <br />HSS RECTANGULAR COLUMNS - ASTM A500 Gr. B (Fy = 46,000 PSI) <br />ALL OTHER STEEL-ASTM A36 (Fy = 36,000 PSI) <br />STRUCTURAL STEEL WELDING <br />1. CONFORM TO THE AWS CODES DIA AND D1.3., AND USE ONLY CERTIFIED WELDERS. WELDS NOT <br />SPECIFIED ARE TO BE 1/4" CONTINUOUS FILLET MINIMUM. USE DRY E70 ELECTRODES. <br />ALTERNATES <br />1. ALTERNATE ASSEMBLIES AND MATERIALS WILL BE CONSIDERED FOR REVIEW. ENGINEER MAY REQUEST <br />PAYMENT FOR REVIEW; CONTRACTOR WILL BEAR BURDEN FOR ADDITIONAL PAYMENT AT NO ADDITIONAL <br />COST TO OWNER. <br />JOBSITE SAFETY: <br />1. THE ENGINEER AND/OR ARCHITECT HAVE NOT BEEN RETAINED OR COMPENSATED TO PROVIDE DESIGN <br />AND/OR CONSTRUCTION REVIEW SERVICES RELATED TO THE CONTRACTOR'S SAFETY PRECAUTIONS OR <br />TO MEANS, METHODS, TECHNIQUES, SEQUENCES OR PROCEDURES FOR THE CONTRACTOR TO PERFORM <br />HIS WORK. THE UNDERTAKING OF PERIODIC SITE VISITS BY THE ENGINEER AND/OR ARCHITECT SHALL <br />NOT BE CONSTRUED AS SUPERVISION OF ACTUAL CONSTRUCTION NOR MAKE HIM RESPONSIBLE FOR <br />PROVIDING A SAFE PLACE FOR THE PERFORMANCE OF WORK BY THE CONTRACTOR, SUBCONTRACTORS, <br />SUPPLIERS OR THEIR EMPLOYEES, OR FOR ACCESS, VISITS, USE, WORK, TRAVEL, OR OCCUPANCY BY ANY <br />PERSON. <br />HELICAL PILES <br />1. HELICAL PILES SHALL BE DESIGNED AND MANUFACTURED IN ACCORDANCE WITH THE 2015 INTERNATIONAL <br />BUILDING CODE (IBC). <br />2. HELICAL PILES SHALL BE DESIGNED AND MANUFACTURED BY IDEAL MANUFACTURING, INC., AND SHALL BE <br />IN ACCORDANCE WITH ESR3750. <br />3. ALL MATERIAL PROPERTIES OF HELICAL PILE COMPONENTS SHALL BE IN ACCORDANCE WITH ESR-3750. <br />4. CORROSION PROTECTION OF ALL PILE COMPONENTS SHALL COMPLY WITH THE ICC-ES ACCEPTANCE <br />CRITERIA FOR CORROSION PROTECTION OF STEEL FOUNDATION SYSTEMS USING POLYMER (EAA) <br />COATINGS (AC228). <br />5. ALL HELICAL FOUNDATION COMPONENTS SHALL BE GALVANICALLY ISOLATED FROM CONCRETE <br />REINFORCING STEEL, BUILDING STRUCTURAL STEEL, ORANY OTHER METAL BUILDING COMPONENTS PER <br />AC358 SECTION 3.9. <br />6. THE SHAFT SHALL BE DESIGNED AND FABRICATED TO SUPPORT THE SPECIFIED DESIGN LOADS. <br />7. ONLY MANUFACTURER -APPROVED CONNECTORS, ADAPTORS, AND ACCESSORIES MAY BE USED. <br />8. HELICAL PILES SHALL BE INSTALLED VERTICALLY INTO THE GROUND WITH AN ALLOWABLE ANGLE OF <br />INCLINATION OF 4-1 DEGREE FROM VERTICAL PER SECTION 4.2.1 OF ESR3750. <br />9. MONITOR AND RECORD DEPTH OF PILE PENETRATION. PROVIDE TORQUE MONITORING DEVICE AS PART OF <br />THE INSTALLING UNIT. MONITOR AND RECORD TORQUE APPLIED DURING THE INSTALLATION OF EACH PILE <br />AT SPECIFIC DEPTHS. <br />10. HELICAL PILES SHALL BE INSTALLED TO THE MINIMUM TORQUE VALUE REQUIRED TO PROVIDE THE <br />MINIMUM REQUIRED LOAD CAPACITIES INDICATED ON PLAN INCLUDING A FACTOR OF SAFETY NO LESS <br />THAN TWO (2). THE MAXIMUM INSTALLATION TORQUE SHALL NOT EXCEED THE ALLOWABLE TORSIONAL <br />CAPACITY OF ANY INDIVIDUAL COMPONENT OF THE PILE ASSEMBLY. <br />11. ALL BRACKETS AND HELICAL PILE ASSEMBLY COMPONENTS SHALL HAVE ADEQUATE CAPACITY TO ACHIEVE <br />THE MINIMUM REQUIRED BEARING CAPACITY INCLUDING A FACTOR OF SAFETY NO LESS THAN TWO (2). <br />12. REPAIR BRACKETS MUST BE CONCENTRICALLY LOADED AND THE BRACKET PLATE MUST BE FULLY <br />ENGAGED WITH BOTTOM OF CONCRETE FOUNDATION. <br />13. ALL HELICAL PILE ASSEMBLY COMPONENTS MUST HAVE ADEQUATE STRENGTH TO DEVELOP THE TORQUE <br />REQUIRED FOR INSTALLATION AND ALL INDUCED STRESSES. <br />14. THE PILE QUANTITY, LAYOUT, AND SPACING INDICATED ON PLAN SHALL NOT BE CHANGED WITHOUT <br />WRITTEN APPROVAL FROM THE ENGINEER -OF -RECORD PRIOR TO INSTALLATION. <br />15. CONTINUOUS SPECIAL INSPECTION IN ACCORDANCE WITH 2O15 AND 2012 IBC SECTION 1705.9 MUST BE <br />PROVIDED FOR THE INSTALLATION OF THE HELICAL PILES AND FOUNDATION BRACKETS, ITEMS TO BE <br />RECORDED AND CONFIRMED BY THE SPECIAL INSPECTOR MUST INCLUDE THE FOLLOWING: <br />A. PRODUCT MANUFACTURER <br />B. MANUFACTURER'S CERTIFICATION OF THE INSTALLERS <br />C. PRODUCT TYPE AND CONFIGURATIONS FOR HELICAL PILE LEAD SHAFT SECTIONS, EXTENSIONS, <br />BRACKETS, BOLTS, THREADED RODS, NUTS, WASHERS, AND TORQUES AS SPECIFIED IN THIS <br />REPORT AND THE CONSTRUCTION DOCUMENTS <br />D. INSTALLATION PROCEDURES FOR THE HELICAL PILE SHAFT, INSTALLATION EQUIPMENT USED, AND <br />THE IDEAL FOUNDATION SYSTEMS INSTALLATION INSTRUCTIONS <br />E. ANTICIPATED AND ACTUAL PILING DEPTH <br />F. REQUIRED TARGET INSTALLATION TORQUE OF PILES AND MINIMUM DEPTH OF INSTALLATION <br />G. INCLINATION AND POSITION OF PILES, TOP OF PILE EXTENSION IN FULL CONTACT WITH BRACKET, <br />TIGHTNESS OF ALL BOLTSAND EVIDENCE THAT THE PILE FOUNDATION SYSTEMS ARE INSTALLED <br />BY AN APPROVED IDEAL FOUNDATION SYSTEMS INSTALLER. <br />16. PILES IMPROPERLY INSTALLED BECAUSE OF MISLOCATION, MISALIGNMENT, OR FAILURE TO MEET OTHER <br />- <br />SPECIFIED DESIGNINSTALLATIONCRITERIA ARE NOT ACCEPTABLE. ABANDON REJECTED PILES AND <br />INSTALL ADDITIONAL PILES AS REQUIRED. <br />HELICAL PILE PROOF TESTING <br />THE CAPACITY OF THE INSTALLED PILES SHALL BE VERIFIED BY FIELD TESTING OF A MINIMUM THREE (3) <br />PERCENT OF PILES UP TO FIVE (5) PILES MAXIMUM (ONE (1) MINIMUM) IN ACCORDANCE WITH THE PROCEDURE <br />OUTLINED IN ASTM D1143 AND/OR THE 2015 SEATTLE BUILDING CODE (SBC). THE MAXIMUM TEST LOAD SHALL BE <br />TWO -HUNDRED (200) PERCENT OF THE SPECIFIED DESIGN LOAD. <br />ABBREVIATIONS <br />AB <br />ABV <br />AFF <br />ALT <br />ALUM <br />APPROX <br />AYC <br />BB <br />BF <br />BLDG <br />BLKG <br />BM <br />BOT <br />BP <br />BRG <br />BTWN <br />BSMT <br />B/W <br />CANT <br />cl <br />CLG. <br />Cu <br />CLR <br />CMU <br />COL <br />CONC <br />CONN <br />CONST <br />CONT <br />CTR <br />BET <br />OF <br />DFL <br />DIM <br />DJ <br />DIA <br />ON <br />DS <br />EA <br />EF <br />El <br />ELEV <br />EN <br />EQ <br />ES <br />EW <br />FB <br />FIN <br />FL <br />FLSHG <br />FND <br />FP <br />FT <br />ANCHOR BOLT <br />ABOVE <br />ABOVE FINISH FLOOR <br />ALTERNATE <br />ALUMINUM <br />APPROXIMATE <br />ALASKAN YELLOW CEDAR <br />BOX BEAM <br />BOTTOM FLUSH <br />BUILDING <br />BLOCKING <br />BEAM <br />BOTTOM <br />BOTTOM PLATE <br />BEARING <br />BETWEEN <br />BASEMENT <br />BOTTOM OF WALL <br />CANTILEVER <br />CONTROLJOINT <br />CEILING <br />CEILING JOIST <br />CLEAR <br />CONCRETE MASONRY UNIT <br />COLUMN <br />CONCRETE <br />CONNECTION <br />CONSTRUCTION <br />CONTINUOUS <br />CENTER <br />DETAIL <br />DOUGLAS FIR (SOUTH) <br />DOUGLAS FIR LARCH <br />DIMENSION <br />DOUBLE JOIST <br />DIAMETER <br />DOWN <br />DOWN SPOUT <br />EACH <br />EACH FACE <br />EXPANSION JOINT <br />ELEVATION <br />EDGE NAILING (PANEL) <br />EQUAL <br />EACH SIDE <br />EACH WAY <br />FLUSH BEAM <br />FINISH <br />FLOOR <br />FLASHING <br />FOUNDATION <br />FIREPLACE <br />FOOT <br />FIG <br />FOOTING <br />GA <br />GAUGE <br />GALV <br />GALVANIZED <br />GLB <br />GLULAM BEAM <br />GR <br />GRADE <br />GYP <br />GYPSUM WALLBOARD <br />HOG <br />HOT -DIPPED GALVANIZED <br />HDR <br />HEADER <br />HF <br />HEM FIR <br />HGT <br />HEIGHT <br />HT <br />HEIGHT <br />IN <br />INCH <br />IT <br />JOINT <br />MAX <br />MAXIMUM <br />MIN <br />MINIMUM <br />MISC <br />MISCELLANEOUS <br />NB <br />NON -BEARING <br />NO <br />NUMBER <br />CC <br />ON CENTER <br />PSF <br />POUNDS PER SQUARE FOOT <br />PSI <br />POUNDS PER SQUARE INCH <br />PT <br />PRESSURE TREATED <br />RAF <br />RAFTER <br />REF <br />REFERENCE <br />REINF <br />REINFORCEMENT <br />REQD <br />REQUIRED <br />SF <br />SQUAREFOOT <br />SIM <br />SIMILAR <br />SPF <br />SPRUCE PINE FIR <br />STD <br />STANDARD <br />SYP <br />SOUTHERN YELLOW PINE <br />T/ <br />TOP OF <br />T/C <br />TOP OF CONCRETE <br />T/P <br />TOP OF PLATE <br />T/S <br />TOP OF STEEL <br />T/W <br />TOP OF WALL <br />TF <br />TOP FLUSH <br />TJ <br />TRIPLE JOIST <br />T/BM <br />TOP OF BEAM <br />T/SLABTOP OF SLAB <br />TP <br />TOP PLATE <br />TYP <br />TYPICAL <br />UNO <br />UNLESS NOTED OTHERWISE <br />UPA <br />UNDER POST ABOVE <br />UWA <br />UNDER WALL ABOVE <br />VERT <br />VERTICAL <br />VIF <br />VERIFY IN FIELD <br />W/ <br />WITH <br />WC <br />WESTERN CEDAR <br />WP <br />WATERPROOF <br />WWF <br />WELDED WIRE FABRIC <br />GITY OF EVERE i T -- <br />RFNi1p1Air:n Fnp Pr-,kAllT <br />aStt.THV,pA,•. <br />'. Srofw�E. <br />WI <br />O z <br />Q'; } <br />V, <br />~ w <br />Z o <br />�Ww <br />(7 <br />z <br />�� w <br />Z�Z a <br />' w <br />O�0 <br />\1 <br />KEi2St�"" <br />0? _ <br />222 48th St <br />Everett, WA 98203 <br />=ROJECT NW`B=n <br />S200306-1 <br />gRAtY'2 E -ZT <br />CHEC<ED BY - M RT <br />`~` DY7E-5/18/2020 <br />................................................................... <br />SCALE <br />In <br />LLJ <br />O <br />Z <br />J <br />U <br />n <br />F- <br />r J <br />J Q <br />1 <br />Lu <br />'.,. lLu <br />J <br />