Laserfiche WebLink
4/5/2021 <br />x <br />City of Everett <br />7:16:59AM <br />' INSPECTION ACTIVITY REPORT <br />Vx <br />Permit No. E2103-068 Site Address 1525 75TH ST SW STE 100 <br />Applied 3/11/2021 Applicant INNOVATIVE ELECTRIC Lot <br />Approved 3/11/2021 Owner UTICA REALTY HOLDINGS V LLC Block <br />Issued 3/12/2021 Contractor INNOVATIVE ELECTRIC Tract <br />Parent Permit No. Description 30-amp 480- volt feeder <br />Notes 30-amp 480-volt feeder <br />Page 1 <br />Scheduled Completed TVDe Inspector Result Remarks Inspector's Comments <br />3/18/2021 3/18/2021 ELEC 09-FINAL MCB NO ACCESS eTRAKiT Inspection 3/17/2021 5:32 PM INNOVATIVE <br />Request ELECTRIC <br />3/19/2021 <br />3/19/2021 ELEC 09-FINAL MCB CORRECTION eTRAKiT Inspection <br />Request <br />Contact Name: INNOVATIVE ELECTRIC <br />Site Address: 1515 75TH ST SW STE 300 <br />Phone:4252907803 <br />e-Mail: <br />lEpurchasing@innovative-electric.com <br />(3/18/2021 1:12 PM MCB) <br />Where and what work was donePhone <br />number provided won't accept calls from <br />inspectors phone <br />3/18/2021 8:32 PM INNOVATIVE <br />ELECTRIC <br />Please contact Dennis Stickles, he is with <br />Cascade coffee cell 425-347-3995 for site <br />access. The work performed is a 30-amp <br />circuit for a VRC in the coffee roasting <br />plant. <br />Or call Gunnar with Innovative at <br />206-571-3947 <br />Contact Name: INNOVATIVE ELECTRIC <br />Site Address: 1515 75TH ST SW STE 300 <br />Phone:2065713947 <br />e-Mail: <br />IEpurchasing@innovative-electric.com <br />(3/19/2021 3:54 PM MCB) <br />Grounding bushing over 277v to ground <br />concentric knock outs. Wrong address on <br />permit change before next inspection. <br />INSP12 <br />CRWSYSTEMS <br />