SYMBOL LEGEND: GROUNDING NOTES: <br /> MGB 1. GROUNDING SHALL COMPLY WITH LATEST EDITION OF THE ■ ■M o b I 1 e■ <br /> -rr MASTER GROUND BAR 1/4"x4"x24" NATIONAL ELECTRICAL CODE. <br /> COPPER <br /> AGB 2. MINIMUM BENDING RADIUS FOR GROUND CONDUCTOR IS 8". <br /> T- ACCESSORY GROUND BAR <br /> 1/4"x4"x12"OR 1/4"x4"x20"COPPER 3. NO SPLICES PERMITTED IN GROUND CONDUCTORS. —PROJECT INFORMATION: <br /> EXPOSED WIRING 4. ALL GROUNDING CONNECTORS TO BE CLEAN AND FREE OF PAINT <br /> ----- UNDERGROUND WIRING AT THEIR MATING SURFACES AND INSTALLED PER CASINO CORNER/SNO-PUD <br /> • CADWELD MANUFACTURERS RECOMMENDATIONS. USE PENETROX OR SE016938 <br /> EQUIVALENT ANTIOXIDANT GREASE. <br /> • MECHANICAL CONNECTION 9830 EVERGREEN WAY <br /> 5. ALL GROUND BAR CONNECTIONS ARE TO BE 2 HOLE LUG <br /> COMPRESSION TYPE. STACKED CONNECTIONS ARE NOT EVERETT,WA 98204 <br /> ACCEPTABLE. BACK TO BACK CONNECTIONS ON OPPOSITE SIDES <br /> OF THE GROUND BAR WILL BE PERMITTED. —ISSUED FOR: <br /> 6. ENSURE ALL MECHANICAL CONNECTORS ARE TORQUED TO THE BUILDING PERMIT <br /> MANUFACTURERS SPECIFIED VALUES. <br /> 7. MULTIPLE BONDS ON GROUND RODS TO BE SEPARATED BY —REVISION HISTORY: CNN. <br /> ATLEAST 6". NO. DATE: DESCRIPTION: BY: <br /> 8. MAXIMUM RESISTANCE OF THE COMPLETED GROUND SYSTEM <br /> SHALL NOT EXCEED A RESISTANCE OF 5 OHMS TO EARTH. <br /> 9. GROUND WIRES SHALL NOT BE INSTALLED THROUGH HOLES IN ANY <br /> METAL OBJECTS OR SUPPORTS; TO PRECLUDE ESTABLISHING A <br /> "CHOKE"POINT. <br /> 10.GROUND BARS SHALL NOT BE FIELD MODIFIED. <br /> Y. X �� A' 11.GROUND RING BURIAL DEPTH SHALL BE 30". <br /> k <br /> • 12.A CERTIFIED CONTRACTOR WILL MAKE ALL MEASUREMENTS <br /> /• • <br /> o I REQUIRED TO TEST THE GROUNDING SYSTEM USING A MEGGER OR <br /> I EQUIVALENT. THE ACCEPTABLE RESISTANCE MEASURED FOR THE <br /> ' / ''\ GROUNDING SYSTEM WILL NOT EXCEED 5 OHMS RESISTANCE. <br /> / C a / /' t THREE DISTANCES SHALL BE USED:1 AT 100 FEET,1 AT 70 FEET, <br /> / i \ AND 1 AT 35 FEET. THESE DISTANCES ARE SUBJECT TO A SITE BY <br /> v <br /> / SITE BASIS. T-MOBILE-WTS SHALL BE GIVEN 24 HOURS NOTICE. ALL <br /> / \ COSTS ASSOCIATED WITH GROUND TESTING WILL BEAT THE <br /> . a v. EXPENSE OF THE CONTRACTOR. A <br /> nlsnozo REVISED PER REDLINES BJT <br /> / . <br /> 4 Q\ % /I\ 7/12020 ISSUED DESIGN REVIEW BJT <br /> / 0 1 a 1 <br /> a Q 1 BOND BTS EQUIPMENT TO(E)MGB W/ =PLANS PREPARED BY: <br /> o % #2 GREEN STRANDED THWN(TYP) <br /> o <br /> / o a (SEE SHT.E-2,DETAIL 3) B. J.THOMAS, P.E. <br /> • a '^``a 7607 80TH AVE NE <br /> it a ♦\, MARYSVILLE,WA 98270 <br /> .0. / <br /> • <br /> (E)MGB MOUNTED NEAR BTS CABINETS 206.851.1 106 <br /> • ,��!j�j■ h o\ iS P ■�■ -DRAWN BY: CHK.BY: <br /> .041A vii�� ` v <br /> • • ■4'�`�� 1 �N 0- 0 1 Allititillipe ' BOND FROM(P)ANTENNAS&RADIOS TO(E)AGB <br /> C01v.0...n■ortort a I i�OGS <br /> \ �t1 ■G11I11�■■G�� 00.0�•yr / LLICENSURE: <br /> e�S��S 044 �Oi / (E)AGB AT TOP OF POLE DIRECTLY <br /> >AAB�0�sioWoo.Noi • BELOW ANTEN, •ARRAY ` txo <br /> \•` �jQ■�jV��O/Sp:�S� �� (SEE GROUNDING . E#5) �L - =n F�-1 �' 4g <br /> \\` \ ��':: �4:I1r•/ ■DID___. 11....E �oF Wr <br /> y li z <br /> eo e 37041, <br /> �r <'•t�.UL�I��� � =DRAWING INFORMATION: <br /> testi,`.I.,��, DO NOT SCALE DRAWINGS.CONTRACTOR MUST VERIFY <br /> \ �% ` ' ALL DIMENSIONS AND ADVISE CONSULTANTS OF ANY <br /> _ / '^� •/�� �\�"� ERRORS AND OMISSIONS.ALL PREVIOUS ISSUES OF DRAWING ARE SUPERSEDED BY THE LATEST REVISION.IS <br /> / ;: .� -, ./ THE INFORMATION CONTAINED IN THIS SET OF <br /> P MECHANICAL CONNECTION �� �,•,' DOCUMENTS IS PROPRIETARY BY NATURE.ANY USE OR <br /> ( ) ) DISCLOSURE OTHER THAN WHICH IS RELATED TO NAMED <br /> (SEE GROUNDING NOTES#4&#6) ' CLIENT IS STRICTLY PROHIBITED. <br /> —DRAWING TITLE: <br /> ELECTRICAL <br /> / <br /> / GROUNDING PLAN <br /> FDRAWING NUMBER: <br /> / <br /> / / <br /> eELECTRICAL GROUNDING PLAN E.2I <br /> 22x34 SCALE:1/2"=1W <br /> 11x17 SCALE:1/4"=1' <br />