Laserfiche WebLink
Mr. Liem Tran <br /> Emerald City Dream Homes, LLC <br /> Plan Check Number: B2005-042, First Building Review <br /> July 2, 2020 <br /> Comments <br /> 1. The General Structural Notes on sheet S-1.0 states that the design was performed to the IRC. <br /> However, it appears the structural design has been performed to the IBC and the AWC NDS-15. <br /> The 2015 IBC should be referenced in the notes. See IRC Section 301.1.3. <br /> 2. The construction of the proposed structure is not clear. A sketch is included in the structural <br /> calculations providing an incomplete section through the roof and house. A section should be <br /> included in the construction drawings showing the required construction. The section should <br /> include the elevation(s) and slope for the roof. The location of the east posts should also be <br /> dimensioned. The east side of the structure shall comply with the fire-resistance construction <br /> requirements of IRC Section R302. See IRC Section 106.1.1, and IBC Sections 107.2.1 and <br /> 1603.1. <br /> 3. The vertical load path for the proposed roof includes support by the existing structure on the <br /> west side. Details for the proposed connections, including modifications to the interior wall <br /> covering to install blocking, should be included in the construction drawings. Calculations <br /> substantiating the connections should be submitted for review. See IRC Section 106.1.1 and <br /> IBC Section 107.2.1. <br /> 4. The lateral load path for the roof structure is not clear. The east side appears intended to act <br /> as a cantilever column system for the north-south loading. However, the west side and the <br /> east-west direction appear to rely on the existing structure for lateral support. The structure <br /> should be designed for lateral support per Section 12.8 and 12.1.3. Calculations substantiating <br /> the load path should be submitted for review. The existing structure should be evaluated per <br /> IEBC Section 1103.3. See IBC Sections 101.4.7 and 1613.1. <br /> 5. The 2x10 rafters bear on the 48 beams along the east edge of the proposed structure. <br /> Connection do not appear to be provided. Connections should be specified providing adequate <br /> strength for both lateral load transfer and resistance to uplift. Calculations substantiating the <br /> connection design should be submitted for review. <br /> 6. The roof framing does not appear to be provided with adequate weather protection to prevent <br /> exposure and deterioration, notably around the perimeter. The project should specify flashing <br /> around the perimeter, or alternatively the use of preservative-treated or naturally-durable <br /> wood. Cut ends of wood members should be coated with a preservative treatment comply with <br /> AWPA M4. See IRC Sections R317.1.1 and R903 <br /> 7. The proposed design includes penetrating the existing roof with new posts. Details for flashing <br /> to weatherproof the roof membrane and soffit should be included in the construction <br /> documents. See IRC Section R903.2. <br /> O3200 Cedar Street © 425.257.8810 O everetteps@everettwa.gov <br /> Everett,WA 98201 425.257.8857 fax everettwa.gov/permits <br /> Page 2 of 3 <br />