S • <br /> Mr. Tim Verzal <br /> Carports of Washington, Inc. <br /> Plan Check Number: B1811-013, First Review <br /> December 21, 2018 <br /> Geotechnical <br /> 1. The foundation design on calculation page 22 uses a lateral bearing soil strength of 110 psf. <br /> The"Foundation"section of the General Structural Notes on Sheet S1.0 state that <br /> presumptive soil values from IBC Table 1806.2, and identify the soil as Class 5 (i.e., clay, <br /> sandy clay, etc.). The lateral bearing soil strength shall not exceed 100 psf without <br /> classification of the site soils or performance of a geotechnical investigation by a qualified <br /> geotechnical engineer. The foundation design shall be revised. The lateral bearing soil <br /> strength used in the design shall be stated in the notes on Sheet S1.0. See IBC Sections <br /> 1603.1.6, 1603.1.8, 1803.1, 1803.5.1, 1803.5.2, and 1806.2. <br /> Architectural <br /> General: <br /> 1. The General Structural Notes on Sheet S1.0 do not specify the Occupancy Classification for <br /> the proposed building. The classification appears to be Group U per IBC Section 312.1. The <br /> classifications shall be verified and stated in the construction drawings. See IBC Section <br /> 107.2.1. <br /> 2. The General Structural Notes on Sheet S1.0 do not specify the Type of Construction for the <br /> proposed building. The type shall be determined and stated in the construction drawings. <br /> See IBC Sections 107.2.1 and 602.1. <br /> Fire Protection: <br /> 3. The proposed building has a fire separation distance of 7 feet from the west property line <br /> per the site plan. The building is required to have exterior walls with a minimum one-hour <br /> fire-resistance rating per IBC Table 602. The maximum area of unprotected openings (i.e., <br /> open wall area) is limited to 10% for a non-sprinklered building. The construction drawings <br /> shall include a wall detail providing the required fire rating. The detail shall reference a <br /> listed assembly with a one-hour or greater fire rating. The wall shall extend above the <br /> roofline per IBC Sections 705.6 and 705.11. See IBC Section 107.2.1. <br /> Miscellaneous: <br /> 4. The canopy is composed of six structurally-separate structures. The individual structures <br /> shall be separated to prevent damage. The separation distance shall be determined per <br /> ASCE 7-10 Section 12.12.3. See IBC Sections 1604.1, 1604.4, and 1613.1. <br /> Structural <br /> General: <br /> 1. Structural and geotechnical special inspections are required for this project. A statement on <br /> special inspections shall be submitted with the permit documents. The statement shall <br /> include a table listing each type of special inspection and shall specify the extent of each <br /> O 3200 Cedar Street 0 425.257.8800 0 everettpw@everettwa.gov <br /> Everett,WA 98201 425.257.8882 fax 's everettwa.gov <br />