Laserfiche WebLink
• <br /> • <br /> 4. Provide fireblocking at maximum 10'-0" O.C. horizontal and vertical in concealed spaces <br /> at furred walls per section R302.11 IRC. Show on plans. <br /> a. Notations have been added to the proposed floor plan sheet(A2.2&A2.2a) as well as <br /> the wall sections (Sheet A4.1) calling out for fireblocking @ max of 10'o.c. horz. & <br /> vert. in concealed spaces of furred walls. <br /> 5. Show how roof structure is ventilated. <br /> a. Sheet A3.1 Roof Plan has been added to the set to show how the roof is being <br /> vented. <br /> 6. Provide handrail on stairs with 4 or more risers per section R311.7.8 IRC. Show on plan <br /> and provide stair section showing placement and diameter of handrail. <br /> a. Handrail is show on floor plans (A2.2&2.2a) and referenced to stair section detail <br /> (2/A4.1) <br /> 7. Provide guard per section R312 IRC at stairs, show on plans. <br /> a. Stairs have been revised and shown on floor plans (A2.2&2.2a) and referenced to <br /> stair section detail (2/A4.1) <br /> 8. Landings shall be not less than 3 feet measured in the direction of travel. The plans <br /> show a landing at mid-run of the stairs that is less than 3 feet. Treads that are not <br /> interrupted by a landing (min. 3 feet) are required to be within 3/8"from the shortest <br /> tread to the longest tread. <br /> a. Stairs have been revised and shown on floor plans (A2.2&2.2a) and referenced to <br /> stair section detail(2/A4.1) <br /> 9. Handrails are required to be placed not less than 34" above the tread nosing and not <br /> more than 38" above the tread nosing. With an extended tread at mid-run, the handrail <br /> may not meet the requirements. Please verify. <br /> a. Stairs have been revised and shown on floor plans (A2.2&2.2a) and referenced to <br /> stair section detail(2/A4.1) <br /> 10. The proposed floor plan shows a half wall and references a detail X/AX.X, please <br /> provide a detail for the construction of the half wall. <br /> a. Half wall notation has been revised on A2.2&2.2a and referenced to detail 2/A4.1 <br /> Sincerely, <br /> 2 <br /> �.o�� <br />