<br /> A.WORK INCLUDED: 1.PROVIDE ALL SIGNAGE AS REQUIRED BY NEC&LOCAL JURISDICTION. ■� � .������� ■ .
<br /> THIS SPECIFICATION AND ACCOMPANYING DRAWING CONTEMPLATE THE PROVISIONS AND INSTALLATION, 2.ALL ELECTRICAL WORK SHALL BE PERFORMED IN ACCORDANCE WITH THE PROJECT SPECIFICATIONS,NEC AND ALL
<br /> BY THE ELECTRICAL CONTRACTOR OF ALL LABOR,MATERIALS AND EQUIPMENT REQUIRED TO INSTALL THE APPLICABLE LOCAL CODES.
<br /> ELECTRICAL WORK COMPLETE IN CONNECTION WITH THIS T-MOBILE SITE AND SHALL INCLUDE,BUT NOT BE
<br /> LIMITED TO THE FOLLOWING: 3.CONDUIT ROUTINGS ARE SCHEMATIC.SUBCONTRACTOR SHALL INSTALL CONDUITS SO THAT ACCESS TO EQUIPMENT 19807 NORTH CREEK PKWY N
<br /> Is NOT BLOCKED. BOTHELL,WA 98011
<br /> 1.THE PROVISIONS AND INSTALLATION OF AN ELECTRICAL SERVICE AND ALL ASSOCIATED WIRE AND -
<br /> CONDUIT AS REQUIRED AND/OR INDICATED ON PLANS. 4.WIRING,RACEWAY AND SUPPORT METHODS AND MATERIALS SHALL COMPLY WITH THE REQUIREMENTS OF THE NEC
<br /> AND TELCORDIA.
<br /> 2.ALL UNDERGROUND CONDUITS SHALL BE SCHEDULE 4D PVC.(UNLESS OTHERWISE NOTED).
<br /> 5.ALL CIRCUITS SHALL BE SEGREGATED AND MAINTAIN MINIMUM CABLE SEPARATION AS REQUIRED BY THE NEC AND
<br /> 3.ALL CONDUITS SHALL BE LEFT WITH 200#TEST PULL WIRE.(UNLESS NOTED OTHERWISE)STUB&PLUG TELCORDW. CROWN
<br /> BOTH ENDS OF ALL SPARE CONDUITS UP AT 12"ABOVE GRADE.
<br /> 6.CABLES SHALL NOT BE ROUTED THROUGH LADDER-STYLE CABLE TRAY RUNGS.
<br /> 4.SUBCONTRACTOR SHALL NOTIFY ELECTRIC AND TELEPHONE SERVICES CONTACT AT START OF + CASTLE
<br /> CONSTRUCTION(2 WEEKS MIN.): 7.EACH END OF EVERY POWER,POWER PHASE CONDUCTOR B.E.,HOTS),GROUNDING,AND T1 CONDUCTOR AND
<br /> CABLE SHALL BE LABELED WITH COLOR-CODED INSULATION OR ELECTRICAL TAPE(3M BRAND,1/2 INCH PLASTIC
<br /> POWER CO.: ELECTRICAL TAPE WITH W PROTECTION,OR EQUAL).THE IDENTIFICATION METHOD SHALL CONFORM WITH NEC 8 1505 WESTLAKE AVENUE NORTH,SUITE 800
<br /> CONTACT: OSHA.
<br /> PHONE#: SEATTLE,WA 98109
<br /> 8.ALL ELECTRICAL COMPONENTS SHALL BE CLEARLY LABELED WITH ENGRAVED LAMACOID PLASTIC LABELS.ALL
<br /> EQUIPMENT SHALL BE LABELED WITH THEIR VOLTAGE RATING,PHASE CONFIGURATION,WIRE CONFIGURATION,POWER
<br /> TELEPHONE CO.. OR AMPICITY RATING,AND BRANCH CIRCUIT ID NUMBERS(.E.,PANEL BOARD AND CIRCUT ID'S).
<br /> CONTACT:
<br /> PHONE#: 9.PANEL BOARDS(ID NUMBERS)AND INTERNAL CIRCUIT BREAKERS(CIRCUIT ID NUMBERS)SHALL BE CLEARLY
<br /> LABELED WITH ENGRAVED LAMACOID PLASTIC LABELS.
<br /> 7.ABOVE GRADE RISER CONDUIT SHALL BE GALVANIZED STEEL WITH MATCHING FITTINGS. 15.ALL TIE WRAPS SHALL BE CUT FLUSH WITH APPROVED CUTTING TOOL TO REMOVE SHARP EDGES.
<br /> 8.ALL WIRE SHALL BE(COPPER,600V THHW,90°C)UNLESS NOTED OTHERWISE. 11.POWER,CONTROL,AND EQUIPMENT GROUND WIRING IN TUBING OR CONDUIT SHALL BE SINGLE CONDUCTOR(#14 G P D GROUP
<br /> AWG OR LARGER),600 V,OIL RESISTANT THHN OR THWN-2,CLASS B STRANDED COPPER CABLE RATED FOR 90°C(WET Professional Corporation
<br /> B.CODES,PERMITS AND FEES: AND DRY)OPERATION;LISTED OR LABELED FOR THE LOCATION AND RACEWAY SYSTEM USED,UNLESS OTHERWISE s20 scum M.u,Street
<br /> SPECIFIED. Akron,OH 44311
<br /> 1.ALL REQUIRED PERMITS,LICENSES,INSPECTIONS AND APPROVALS SHALL BE SECURED AND ALL FEES 31R07l2100 Fox 3305722102
<br /> FOR SAME PAID BY SUBCONTRACTOR. 12.SUPPLEMENTAL EQUIPMENT GROUND WIRING LOCATED INDOORS SHALL BE SINGLE CONDUCTOR 06 AWO OR
<br /> LARGER),600 V,OIL RESISTANT THHN OR THWN-2 GREEN INSULATION,CLASS B STRANDED COPPER CABLE RATED FOR
<br /> 2.THE INSTALLATION SHALL COMPLY WITH ALL APPUCABLE CODES AND ORDINANCES;STATE,LOCAL AND 90°C(WET AND DRY)OPERATION;LISTED OR LABELED FOR THE LOCATION AND RACEWAY SYSTEM USED,UNLESS
<br /> NATIONAL,AND THE DESIGN,PERFORMANCE CHARACTERISTICS AND METHODS OF CONSTRUCTION OF ALL OTHERWISE SPECIFIED.
<br /> ITEMS AND EQUIPMENT,SHALL BE IN ACCORDANCE WITH THE LATEST ISSUE OF THE VARIOUS APPUCABLE T-MOBILE SITE NUMBER:
<br /> STANDARD SPECIFICATIONS OF THE FOLLOWING RECOGNIZED AUTHORITIES: 13.POWER AND CONTROL WIRING,NOT IN TUBING OR CONDUIT,SHALL BE MULTI-CONDUCTOR,TYPE TC CABLE(#14
<br /> AWG OR LARGER),600 V,OIL RESISTANT THHN OR THWN-2,CLASS B STRANDED COPPER CABLE RATED FOR 90°C(WET SEO1513A
<br /> AN.S.1.-AMERICAN NATIONAL STANDARDS INSTITUTE AND DRY)OPERATION;WITH OUTER JACKET;LISTED OR LABELED FOR THE LOCATION USED,UNLESS OTHERWISE
<br /> I.E.E.E.-INSTITUTE OF ELECTRICAL AND ELECTRONIC ENGINEERS SPECIFIED.
<br /> N.E.C.-NATIONAL ELECTRIC CODE
<br /> N.E.MA.-NATIONAL ELECTRICAL MANUFACTURERS ASSOCIATION 14.ALL POWER AND GROUNDING CONNECTIONS SHALL BE CRIMP-STYLE,COMPRESSION WIRE LUGS AND WIRENUTS BU#:815285
<br /> N.F.PA.-NATIONAL FIRE PROTECTION ASSOCIATION BY THOMAS AND BETTS(OR EQUAL).LUGS AND WIRENUTS SHALL BE RATED FOR OPERATION AT NO LESS THAN 75°C
<br /> U.L.-UNDERWRITERS LABORATORIES,INC. (90°C IF AVAILABLE). LOWELL
<br /> 3.THE SUBCONTRACTOR SHALL BE UCENSED TO PERFORM WORK IN THE STATE,CITY OR COUNTY OF THE 15.RACEWAY AND CABLE TRAY SHALL BE LISTED OR LABELED FOR ELECTRICAL USE IN ACCORDANCE WITH NEMA,UL,
<br /> PROJECT SITE AS REQUIRED. ANSMEEE,AND NEC.
<br /> 2408 39TH ST
<br /> 4.UTILITY COMPANY COORDINATION 16.ELECTRICAL METALLIC TUBING(EMI)OR RIGID NONMETALLIC CONDUIT(I.E.,RIGID PVC SCHEDULE 40,OR RIGID PVC
<br /> ELECTRICAL CONTRACTOR SHALL COMPLETE ALL WORK IN ACCORDANCE WITH THE RULES OF THE LOCAL SCHEDULE 80 FOR LOCATIONS SUBJECT TO PHYSICAL DAMAGE)SHALL BE USED FOR EXPOSED INDOOR LOCATIONS. EVERETT,WA 98201
<br /> UTILITY COMPANY.BEFORE SUBMITTING HIS BID,THE SUBCONTRACTOR SHALL CHECK WITH THE UTILITY
<br /> COMPANIES SUPPLYING SERVICE TO THIS PROJECT AND SHALL DETERMINE FROM THEM ALL EQUIPMENT 17.ELECTRICAL METALLIC TUBING(EMT),ELECTRICAL NONMETALLIC TUBING(ENT),OR RIGID NONMETALLIC CONDUIT
<br /> AND CHARGES WHICH THEY WILL REQUIRE AND SHALL INCLUDE THE COST IN HIS BID WHENEVER (RIGID PVC,SCHEDULE 40)SHALL BE USED FOR CONCEALED INDOOR LOCATIONS.POSSIBLE. EXISTING 1301-011 MONOPOLE
<br /> 13.GALVANIZED STEEL INTERMEDIATE METALLIC CONDUIT BMC)SHALL BE USED FOR OUTDOOR LOCATIONS ABOVE
<br /> 5.UTILITIES: GRADE.
<br /> THE SUBCONTRACTOR SHALL BE RESPONSIBLE FOR THE EXCAVATION AND PROPER BACKFILLING OF 19.RIGID NOMAETALUC CONDUIT(I.E.,RIGID PVC SCHEDULE 4D OR RIGID PVC SCHEDULE 80)SHALL BE USED GPD JOB NUMBER:2021724.75.815285.01
<br /> TRENCHES AND SUPPLY CONDUIT REQUIRED FOR UNDERGROUND TELEPHONE&ELECTRICAL UTILITIES. UNDERGROUND;DIRECT BURIED,IN AREAS OF OCCASIONAL LIGHT VEHICLE TRAFFIC OR ENCASED IN REINFORCED
<br /> ALL TRENCHING SHALL BE COMPACTED TO 95%MAXIMUM DRY DENSITY IN ACCORDANCE W/ASTM D-1557 IN CONCRETE IN AREAS OF HEAVY VEHICLE TRAFFIC.
<br /> 6"LIFTS. ISSUED FOR
<br /> 20.LIQUID-TIGHT FLEXIBLE METALLIC CONDUIT(LIQUID-TITE FLEX)SHALL BE USED INDOORS AND OUTDOORS,WHERE
<br /> THE ELECTRICAL TRENCH SHALL START AT THE NEW PREFABRICATED RADIO EQUIPMENT BUILDING AND VIBRATION OCCURS OR FLEXIBILITY IS NEEDED. REV DATE DAWN DESCRIPTION DES./QA
<br /> END AT THE NEW METER BOARD STRUCTURE.THE SUBCONTRACTOR SHALL THEN STUB THE CONDUIT 5' 0 01/21/2021 AJM FINAL C)M
<br /> OUTSIDE THE FENCE.THE ELECTRIC PROVIDER SHALL PROVIDE SERVICE TO THE NEW METER BOARD 21.CONDUIT AND TUBING FITTINGS SHALL BE THREADED OR COMPRESSION-TYPE AND APPROVED FOR THE LOCATION
<br /> STRUCTURE.THE SUBCONTRACTOR SHALL PROPERLY BACKFILL THE TRENCHES AFTER SETTLEMENT AND USED.SETSCREW FITTINGS ARE NOT ACCEPTABLE.
<br /> RESTORE GRAVEL COMPOUND.CONTACT ELECTRIC PROVIDER SIX WEEKS PRIOR TO CONSTRUCTION FOR
<br /> SERVICE AND COORDINATION OF ACCESS TO SITE. 22.CABINETS,BOXES,AND WIREWAYS SHALL BE LISTED OR LABELED FOR ELECTRICAL USE IN ACCORDANCE WITH
<br /> NEMA,UL,ANSUIEEE,AND NEC.
<br /> THE SUBCONTRACTOR SHALL RUN THE TELEPHONE TRENCH AND CONDUIT FROM THE NEW
<br /> PREFABRICATED RADIO EQUIPMENT BUILDING TO THE NEW TELCO METER BOARD STRUCTURE.THE 23.WIREWAYS SHALL BE EPDXY-COATED(GRAY)AND INCLUDE A HINGED COVER,DESIGNED TO SWING OPEN
<br /> SUBCONTRACTOR SHALL THEN RUN CONDUIT W/PULL STRING OUTSIDE THE FENCE IN THE UTILITY DOWNWARD;SHALL BE PANDUIT TYPE E(OR EQUAL);AND RATED NEMA 1(OR BETTER)INDOORS,OR NEMA 3R(OR
<br /> EASEMENT TO THE R.O.W.THE SUBCONTRACTOR SHALL STAKE THE LOCATIONS OF THE PULL BOXES.THE BETTER)OUTDOORS.
<br /> TELCO PROVIDER SHALL PROVIDE SERVICE TO THE METER BOARD STRUCTURE.THE SUBCONTRACTOR
<br /> SHALL PROPERLY BACKFILL THE TRENCHES AFTER SETTLEMENT AND RESTORE THE GRAVEL COMPOUND. 24.EQUIPMENT CABINETS,TERMINAL BOXES,JUNCTION BOXES,AND PULL BOXES SHALL BE GALVANIZED OR
<br /> EPDXY-COATED SHEET STEEL,SHALL MEET OR EXCEED UL 50,AND RATED NEMA 1(OR BETTER)INDOORS,OR NEMA 3R
<br /> (OR BETTER)OUTDOORS.
<br /> 25.METAL RECEPTACLE,SWITCH,AND DEVICE BOXES SHALL BE GALVANIZED,EPDXY-COATED,OR NON-CORRODING;
<br /> SHALL MEET OR EXCEED UL 514A AND NEMA OS 1;AND RATED NEMA 1(OR BETTER)INDOORS,OR WEATHER
<br /> PROTECTED(WP OR BETTER)OUTDOORS.
<br /> 26.NONMETALLIC RECEPTACLE,SWITCH,AND DEVICE BOXES SHALL MEET OR EXCEED NEMA OS 2;AND RATED NEMA 1
<br /> (OR BETTER)INDOORS,OR WEATHER PROTECTED(WP OR BETTER)OUTDOORS.
<br /> EN P.S1H
<br /> 27.THE SUBCONTRACTOR SHALL NOTIFY AND OBTAIN NECESSARY AUTHORIZATION FROM THE CONTRACTOR BEFORE ,ASH,9
<br /> COMMENCING WORK ON THE AC POWER DISTRIBUTION PANELS. y'�.cE Q., <9
<br /> AC G
<br /> 28.THE SUBCONTRACTOR SHALL PROVIDE NECESSARY TAGGING ON THE BREAKERS,CABLES AND DISTRIBUTION 4 3.'
<br /> PANELS IN ACCORDANCE WITH THE APPLICABLE CODES AND STANDARDS TO SAFEGUARD AGAINST LIFE AND
<br /> PROPERTY.
<br /> `s0aw
<br /> �0.4 RFtas10-7
<br /> �40NALF•
<br /> 02/03/2022
<br /> 01/22/2021
<br /> ELECTRICAL SEAL
<br /> IT IS A VIOLATION OF LAW FOR ANY PERSON,
<br /> UNLESS THEY ARE ACTING UNDER THE DIRECTION
<br /> OF A LICENSED PROFESSIONAL ENGINEER,
<br /> TO ALTER THIS DOCUMENT.
<br /> 2 2 SHEET NUMBER: REVISION: