BUILDING CODE REINFORCING STEEL 4. NO STRUCTURAL MEMBER SHALL BE CUT OR NOTCHED UNLESS ' \ <br /> 2015 INTERNATIONAL BUILDING CODE 1. ALL REINFORCING STEEL SHALL CONFORM TO ASTM A615 GRADE SPECIFICALLY DETAILED OR APPROVED IN WRITING BY THE STRUCTURAL <br /> 60 (fy = 60 KSI) FOR BAR SIZES NO. 5 & LARGER, GRADE 40 (fy ENGINEER. m 5 <br /> FLOOR LOAD = 40 KSI) FOR NO. 3 AND NO. 4 BARS. c N g$r <br /> DEAD LOAD : 12 psf 5. USE DOUBLE JOISTS UNDER WALLS OR PARTITIONS PARALLEL TO JOISTS <br /> LIVE LOAD: 40 psf 2. ALL REINFORCING STEEL SHALL BE LAPPED AS NOTED ON THE UNLESS SPECIFICALLY NOTED OTHERWISE. USE SOLID BLOCKING UNDER <br /> PLANS. WHERE LAP OR SPLICE LOCATIONS ARE NOT SPECIFICALLY PARTITIONS PERPENDICULAR TO JOISTS. <br /> ROOF LOAD INDICATED ON THE CONSTRUCTION DOCUMENTS, LAPS AND/OR tn <br /> 6. RIM JOIST ARE 11#4" LSL OR 2x SOLID SAWN LUMBER AS MINIMUM. C9 <br /> DEAD LOAD: 15 psf SPLICES SHALL BE 42 BAR DIA AND BE WELL STAGGERED. - <br /> FLAT ROOF SNOW LOAD: 25 psf O <br /> SNOW EXPOSURE FACTOR (Ce): 1.1 3. COMPLETE REINFORCING PLACEMENT DRAWINGS PREPARED IN 7. MAXIMUM MOISTURE CONTENT SHALL NOT EXCEED 16% FOR ALL CZ O <br /> STRUCTURAL MEMBERS. <br /> SNOW LOAD IMPORTANCE FACTOR (Is): 1.0 ACCORDANCE WITH ACI 315 SHALL BE REVIEWED BY THE ENGINEER U N <br /> in <br /> THERMAL FACTOR (Ct): 1.1 ANDDCAVAI AVAILABLE ON THE JOB SITE PRIOR TO THE PLACING OF 8. PROVIDE 2X2 WASHERS UNDER HEADS AND NUTS OF ALL BOLTS AND 0 N <br /> CONLAG SCREWS BEARING ON WOOD. N w - N E <br /> WIND DESIGN DATA 4. WELDED WIRE FABRIC SHALL CONFORM TO ASTM A82 AND A185 Q > 0 'I' 0 <br /> 1. BASIC WIND SPEED: 110 MPH 9. BOLT HOLES SHALL BE NOMINAL DIAMETER OF BOLT PLUS 1/16" > N v <br /> 2. WIND IMPORTANCE FACTOR (Iw): 1.0 AND SHALL BE 6x6 W2.1/W2.1 UNLESS OTHERWISE NOTED. LAP UNLESS OTHERWISE NOTED. LAG BOLT PILOT HOLES SHALL BE c- cZ c0 <br /> BUILDING CATEGORY: II REINFORCEMENT 6" MINIMUM. PRE-DRILLED TO 60% OF THE NOMINAL DIAMETER OF THE LAG BOLT z < t <br /> 3. WIND EXPOSURE: C UNLESS OTHERWISE NOTED. � U Q > <br /> 4. Kzt = 1.00 5. ANCHOR BOLTS, DOWELS AND OTHER EMBEDDED ITEMS SHALL BE N n a) 0 <br /> SECURELY TIED IN PLACE BEFORE CONCRETE IS POURED. SLAB ON I -.cV q <br /> 5. INTERNAL PRESSURE COEFFICIENT: NA 10. ALL SILL PLATES SHALL BE BOLTED TO THE FOUNDATION WITH 5/8" - .) O �� O <br /> GRADE REINFORCEMENT SHALL BE PLACED AT MID-DEPTH OF SLAB O <br /> 6. APPLICABLE WIND PRESSURE FOR AND SHALL BE HELD SECURELY IN PLACE WITH MECHANICAL DEVICES MINIMUM DIAMETER BOLTS SPACED AT 48" O.C. MAXIMUM SPACING (EMBED 0 O '- aj <br /> COMPONENTS AND CLADDING: NA 7" MINIMUM INTO CONCRETE OR MASONRY). SEE PLANS AND DETAILS FOR 0 > m 3 <br /> DURING PLACING OF THE CONCRETE. - Co uw m <br /> SPECIFIC REQUIREMENTS WHERE OCCUR. (6 <br /> SESIMIC DESIGN DATA L Lc; <br /> 6. REINFORCEMENT SHALL PLACED CONTINUOUS AROUND CORNERS N <br /> 1. SEISMIC IMPORTANCE FACTOR: 1.0 AND INTERSECTIONS UNLESS SPECIFIED OTHERWISE. 11. ALL FRAMING LUMBER IN CONTACT WITH MASONRY OR CONCRETE <br /> SEISMIC USE GROUP: I SHALL BE PRESSURE TREATED. (SEE NOTE 1 FOR MINIMUM GRADE <br /> 2. SPECTRAL RESPONSE ACCELERATION (Ss): 143.9% G 7. WELDED REINFORCING STEEL SHALL CONFORM TO ASTM A706 INFORMATION). ALL FOUNDATION BOLTS AND CONNECTORS MUST BE HEAVY D z <br /> 3. SITE CLASS: D (ASSUMED) GRADE 600 WITH A CARBON EQUIVALENT NOT EXCEEDING 0.55%. THE GALVANIZEDED, OR Z-MAX COATING TO PROTECT FROM OXIDATION. L 0 <br /> 4. SPECTRAL RESPONSE COEFFICIENTS (SDS): 95.9%G BAR SHALL DEMARCATED AS 'WELDABLE' (W). ALL WELDS SHALL -N <br /> 5. SEISMIC DESIGN CATEGORY: D FULLY DEVELOP THE REINFORCING STEEL YIELD STRENGTH UNLESS 12. FIELD-CUT ENDS, NOTCHES, AND DRILLED HOLES OF PRESSURE (') <br /> 6. BASIC SEISMIC-FORCE-RESISTING SYSTEM: SHEARWALLS NOTED OTHERWISE. ALL REINFORCING STEEL WELDING SHALL BE PRESERVATIVELY TREATED WOOD SHALL BE RETREATED IN THE FIELD IN <br /> 7. DESIGN BASE SHEAR: SEE CALCULATIONS CONDUCTED PER AWS D1.4 BY A WABO CERTIFIED WELDER. WELDED ACCORDANCE WITH AWPA M4. IRC 320.3.1 <br /> 8. SEISMIC RESPONSE COEFFICIENT (Cs): 0.103 PERPENDICULAR REINFORCING STEEL SHALL CONFORM TO ASTM A184. <br /> 9. RESPONSE MODIFICATION FACTOR (R): 6.5 ALL FIELD WELDING REQUIRES SPECIAL INSPECTION. 13. 2X4 RAFTERS EXCEPT WHERE SPECIFICALLY DETAILED SHALL NOT <br /> 10. ANALYSIS PROCEDURE USED: EQUIVALENT LATERAL SUPPORT SUSPENDED CEILINGS, SPRINKLERS, DROP SOFFITS, OR ANY n <br /> FORCE PROCEDURE GLUED-LAMINATED TIMBER OTHER ELEMENTS. LI 0 i"'( n^ <br /> FOUNDATIONS 1. ADHESIVE SHALL BE FOR WET USE. () N 1-3v� <br /> 1. THE FOUNDATION DESIGN IS BASED ON THE 14. WIRE STAPLES MAY BE SUBSTITUTED FOR DIAPHRAGM AND SHEARWALL Z � CO 0‹ <br /> RECOMMENDATION IN THE INTERNATIONAL BUILDING CODE 2. LAMINATIONS SHALL BE OF DOUGLAS FIR/WESTER LARCH, NAILING WHEN APPROVED BY THE STRUCTURAL ENGINEER. UJ .....1 -� � n^ <br /> TABLE 1804.2. FOUNDATION WORK SHALL BE PERFORMED COMBINATION 24F-V4 FOR SIMPLE SPAN BEAMS AND 24F-V8 FOR 0 IL Q a 7:3 t(v//� <br /> CONTINUOUS MULTIPLE SPAN AND CANTILEVERED BEAMS, FABRICATED 15. EXTERIOR STUD WALLS SHALL BE 2X6 ® 16" O.C.. UNLESS NOTED <br /> IN ACCORDANCE WITH CHAPTER 18 OF THIS CODE. (n w <br /> IN ACCORDANCE WITH AITC A190.1 AND ASTM D 3737. OTHERWISE. INTERIOR STUD BEARING WALLS SHALL BE CONSTRUCTED IL! CD CDtsj Co <br /> 2. THE FOUNDATION DESIGN IS BASED ON THE FOLLOWING USING 2X4 © 16" O.C. AT UPPER TWO FLOORS AND EITHER 2X6 0 16" DC I` as ., <br /> 3. FABRICATION SHALL BE BY A LICENSED FABRICATOR; SHOP <br /> VALUES: Iffil <br /> ALLOW. SOIL BEARING = 1500 PSF PRIORRING <br /> DRAWINTO FABRICATIONGS SHALL BE . AITCCERTIFICATES MITTED TO THE OFENSPECTION ARER FOR <br /> WALLS SHALL BE CONSTRUCTED USING 2ELOW TOP 0X4 ©024" 0 C..RS. UNLESS ANO ED < 0 � 0 N <br /> SOIL FRICTION = .25 REQUIRED FOR ALL MEMBERS. OTHERWISE. SEE NOTE FOR LUMBER GRADES OF STUDS AND PLATES. N CV 0 <br /> OZ EQUIV. FLUID PRESSURES: Ili <br /> *ACTIVE PRESSURE = 35 PCF 4. GLULAM BEAMS EXPOSED TO WEATHER SHALL BE WOLMANIZED OR 16. FRAMING ANCHORS FOR JOISTS, PURLINS AND POSTS SHALL BE < > <br /> PASSIVE PRESSURE = 150 PCF PRESSURE TREATED. SIMPSON, OR APPROVED EQUAL. APPROVAL MUST BE OBTAINED IN WRITING �"� �� <br /> *(WALLS RESTRAINED AGAINST ROTATION SHALL BE PRIOR TO INSTALLATION. FILL ALL FASTENER HOLES WITH FASTENER <br /> DESIGNED FOR AN EQUIV. FLUID PRESSURE OF 55 FRAMING LUMBER TYPES (NAILS, BOLTS, ETC.), SIZES, AND QUANTITIES AS SPECIFIE1 BY <br /> PCF). 1. FRAMING LUMBER SHALL BE DOUGLAS FIR/LARCH NO.1 FOR POSTS, THE MANUFACTURER. <br /> BEAMS, AND HEADERS; HEM-FIR NO.2 FOR 2X AND 3X JOISTS, AND COV11y <br /> 3. ALL FOOTINGS SHALL BE FOUNDED AT LEAST 18" STUDS; AND HEM-FIR NO.2 FOR ALL TOP AND BOTTOM PLATES 17. ALL HEADERS SHALL BE 4X8 DF#2 UNLESS OTHERWISE NOTED ON THE 4y�oFw�s C'� <br /> BELOW THE UNDISTURBED GROUND SURFACE OR TO FROST (GRADES ARE TYPICAL UNLESS OTHERWISE NOTED ON PLANS). DRAWINGS t4 ` 1,,�` 1- <br /> DEPTH. ALL FOOTINGS SHALL BE FOUNDED ON COMPACTED LUMBER TO BE GRADE MARKED PER WCLIB SPECIFICATIONS. <br /> FILL OR UNDISTURBED NATURAL GRADE UNLESS OTHERWISE 18. OSB OF EQUAL OR GREATER THICKNESS MAY BE SUBSTITUTED FOR M <br /> NOTED. 2. STRUCTURAL SHEATHING SHALL BE APA RATED PLYWOOD, PLYWOOD USED IN SHEAR PANELS. t, .?4,3 ",0 <br /> r- ry <br /> EXPOSURE 1 SHEATHING CONFORMING TO EITHER COMMERCIAL 19. CONTACT THIS OFFICE PRIOR TO MAKING ANY CHANGES TO THESE A'IONA W W <br /> 4. COMPACTION: MATERIAL FOR FILLING AND BACKFILLING STANDARDS DOC PS 1 OR PS 2. PROVIDE MINIMUM OF 3/8" EDGE LU LU <br /> SHALL CONSIST OF THE EXCAVATED MATERIAL AND/OR DISTANCE ON ALL NAILS AND A 1/8" EXPANSION JOINT BETWEEN ALL DETAILS AND NOTES. - <br /> JAN 3 Y W <br /> IMPORTED BORROW AND SHALL BE FREE OF ORGANIC PANEL EDGES. MINIMUM SHEATHING REQUIREMENTS ARE AS FOLLOWS: <br /> Ce <br /> MATTER, TRASH, LUMBER, OR OTHER DEBRIS. ALL WALLS Permit It: BW2007-004 > 0 <br /> SHALL BE ADEQUATELY BRACED PRIOR TO BACKFILLING. ROOF SHEATHING TO BE 15/32" C-D INT-APA RATED PLYWOOD <br /> FILL AND BACKFILL SHALL BE DEPOSITED IN LAYERS NOT Site Address: 82088THPLSW Drawn By: VKY <br /> TO EXCEED 8 INCHES THICK, PROPERLY MOISTENED TO WITH EXTERIOR GLUE, P.I. 24/16 (USE 5-PLY FOR PANELIZED Owner: ARIASSALVADOR/CAROTHERSIESSICA Checked By:CHRIS w <br /> APPROXIMATE OPTIMUM REQUIREMENTS AND THOROUGHLY ROOFS). NAIL WITH 8d NAILS AT 6" ON CENTER AT PANEL W <br /> EDGES AND 12" ON CENTER AT INTERMEDIATE SUPPORTS <br /> Tenant: [TenNarf� ., , , Date:O I -03-20 <br /> ROLLED OR COMPACTED WITH APPROVED EQUIPMENT IN � W <br /> UNLESS NOTED OTHERWISE. App.Date: 7�14( 2 .�'"+r i" <br /> SUCH A MANNER AND EXTENT AS TO PRODUCE A � k � ': sFR op §i-witv ibp,,, SDA JOB NO. <br /> DENSTYRELATIVEASODETE MANED BYMPACTION OF O ASTM D1557.% OF A HAND SUB <br /> SUB FLOORING TO BE 3/4" T&G C-D INT-APA RATED PLYWOOD Proposed <br /> Description: BUS I[' � O PATIO 88�jq- U <br /> LLI <br /> TAMPERS SHALL WEIGH AT LEAST 50 POUNDS EACH AND WITH EXTERIOR GLUE, P.I. 48/24. GLUE AND NAIL WITH 10d .1 < ,4,41; Tit CC <br /> SHALL HAVE A FACE AREA NOT IN EXCESS OF 64 SQUARE NAILS AT 6" ON CENTER AT PANEL EDGES AND 12" ON CENTER STRUCTURAL <br /> INCHES. HAND TAMPERS MAY BE OPERATED EITHER AT INTERMEDIATE SUPPORTS UNLESS NOTED OTHERWISE. ' / <br /> MANUALLY OR MECHANICALLY AND SHALL BE USED WHERE Reviewed BloS \ Date: ,/ !' NOTES <br /> 4 LARGER POWER DRIVEN COMPACTION EQUIPMENT CANNOT 3. NAILING SHALL CONFORM TO TABLE 2304.9.1 OF THE _�cv' •�w`" ///��� \ i <br /> BE USED. FILL OVER 12" DEEP SHALL COMPLY WITH A INTERNATIONAL BUILDING CODE UNLESS NOTED OTHERWISE. USE )ffice Set iob Site Set Fire/Planning Set 5- I ,O 3 <br /> GEOTECHNICAL REPORT. COMMON NAILS THROUGHOUT UNLESS NOTED OTHERWISE. - <br />