11/1/2021 Page <br /> • <br /> City of Everett <br /> 6418:34AM <br /> INSPECTION ACTIVITY REPORT <br /> Permit No. E2109-114 Site Address 1326 E MARINE VIEW DR <br /> Applied 9/16/2021 Applicant BEACON PLUMBING&MECHANICAL INC(ELEC Lot <br /> Approved 9/16/2021 Owner RITTER JUSTIN KEITH/DUNN MEGAN E Block <br /> Issued 9/16/2021 Contractor BEACON PLUMBING&MECHANICAL INC(ELEC Tract <br /> Parent Permit No. Description Install new 200 amp panel <br /> Notes Like for like <br /> Scheduled Completed Tyne Inspector Result ' Remarks Inspector's Comments <br /> 10/11/2021 10/11/2021 ELEC 09-FINAL SKB CORRECTION eTRAKiT Inspection 10/8/2021 9:04 AM BEACON <br /> Request PLUMBING&MECHANICAL INC <br /> (ELEC) <br /> PM please-call denis 206-488-4149 <br /> Contact Name:BEACON PLUMBING& <br /> MECHANICAL INC(ELEC) <br /> Site Address: 1326 E MARINE VIEW DR <br /> Phone:2067202040 <br /> e-Mail: <br /> accounting@BEACONPLUMBING.NET <br /> (10/11/2021 4:15 PM SKB) <br /> Provide access to the inside of the meter for <br /> visual inspection.Raise the junction and <br /> device boxes above the insulation line in <br /> the attic.Add at least 1 more receptacles in <br /> the front bedroom as the PMC code <br /> requires at least 2 receptacles per room. <br /> Remove abandoned knob and tube wiring <br /> in attic. <br /> 10/21/2021 Any 10/21/2021 ELEC 09-FINAL SKB CORRECTION eTRAKiT Inspection 10/20/2021 11:00 AM BEACON <br /> Request PLUMBING&MECHANICAL INC <br /> (ELEC) <br /> AM inspection requested. <br /> Please call in route-253-653-5991 <br /> Contact Name:BEACON PLUMBING& <br /> MECHANICAL INC(ELEC) <br /> Site Address: 1326 E MARINE VIEW DR <br /> Phone:2067202040 <br /> e-Mail: <br /> accounting@BEACONPLUMBING.NET <br /> 10/12/2021 12:18 PM BEACON <br /> PLUMBING&MECHANICAL INC <br /> (ELEC) <br /> Please call in route for access <br /> Denis V-206-488-4149 <br /> Contact Name:BEACON PLUMBING& <br /> MECHANICAL INC(ELEC) <br /> Site Address: 1326 E MARINE VIEW DR <br /> Phone:2067202040 <br /> e-Mail: <br /> accounting@BEACONPLUMBING.NET <br /> (10/21/2021 9:57 AM SKB) <br /> Provide access into the meter portion of the <br /> service for visual inspection,coordinate <br /> with PUD if necessary.Install covers on the <br /> junction boxes in the attic <br /> INSP12 CISYSTE S <br />