<br />NOTES-
<br />o FOR CONCRETE BLOCK WALL APPLICATIONS
<br />CENTER WRAP STRIP WITHIN WALL AND SEAL
<br />1.
<br />2-HOURRATED WALL, 2 LAYERS OF 5/8"
<br />WITH CAULK CP-25 OR POTTY 303 ON BOTH]
<br />THICK GYPSUM BOARD OR CONCRETE
<br />SIDES OF WALL.
<br />BLOCK WALL, (SEE NOTE 4).
<br />2.
<br />STEEL STUD.
<br />IT IS NOT NECESSARY TO REMOVE INSULATION
<br />3.
<br />1 WRAP OF 2" WIDE FS-195 WRAP/STRIP
<br />AS IT PENETRATES THE WALL OR FLOOR
<br />FLUSH TO EXTERIOR GYPSUM PANEL. (SEE
<br />WHEN USING 2M 'FIRE BARRIER.
<br />NOTE 1).
<br />4.
<br />METAL PIPE.
<br />MINIMUM NUMBER OF FS-195 WRAPS DEPENDS
<br />5,
<br />SEAL ENTIRE EDGE AND SEAMS WITH 1/4'
<br />ON INSULATION THICKNESS:
<br />LAYER OF CAULK CP-25.
<br />1"" OF INSULATION - 1 WRAP
<br />6.
<br />CLOSE FITTING METAL ESCUTCHEONS ON
<br />2" OF INSULATION - 2 WRAPS
<br />EACH SIDE OF WALL OR FLOOR
<br />3" OF INSULATION - 3 WRAPS
<br />7.
<br />COVER SURFACE AND SEAMS WITH CAULK
<br />CP-25 OR PUTTY 303.
<br />® RECOMMENDATIONS BASED ON PRODUCT
<br />8.
<br />WRAP INSULATION PIPE WITH FS-195
<br />PERFORMANCE ASTM E-814 (UL 1479) TIME
<br />WRAP/STRIP TO FILL GAP. FRICTION FIT
<br />TEMPERATURE CURVE FIRE EXPOSURE
<br />WRAP INTO OPENING (SEE NOTE 1) OR
<br />® A 28 AWG METAL COVER PLATE IS REQUIRED
<br />SECURE WRAPS TO PIPE WITH 18 GAUGE
<br />WHEN ANNULAR SPACE EXCEEDS 2 7/8"
<br />STEEL TIE WIRE, THEN SLIDE INTO OPENING
<br />FOR CONCRETE BLOCK WALL APPLICATIONS,
<br />FLUSH WITH TOP OF FLOOR SLAB.
<br />IT IS OPTIONAL TO INSTALL THE FS-195 ON
<br />9.
<br />PIPE INSULATION.
<br />BOTH SIDES OF THE WALL. IT IS
<br />10.
<br />2-HOUR FIRE RATED CONCRETE FLOOR
<br />RECOMMENDED THAT THE FS-195 BE
<br />SLAB.
<br />CENTERED IN THE WALL.
<br />11.
<br />TIE WIRE.
<br />f3/4"= 1 "-0'"
<br />,
<br />S ? 9 F
<br />F RATING = 1-HR
<br />T RATING = 1-HR
<br />NUiL6:
<br />1. FLOOR -CEILING ASSEMBLY.
<br />A. WOOD FLOORING SYSTEM 1 B. WOOD JOIST 1 C. 5/8" TYPE 'X'
<br />GYPSUM WALLBOARD.
<br />2. CHASE WALL
<br />A. STUDS
<br />B. SOLE PLATES
<br />C. TOP PLATE
<br />D. GYPSUM WALLBOARD
<br />3. THROUGH PENETRANTS
<br />4: FIRESTOP SYSTEM - RECTORSEAL FIRESEAL BIOSTOP BF150+
<br />DETAILBA� CORED WOOD FLOOR
<br />1 3"=V 0„
<br />I
<br />3
<br />„«, v.:°tY<, . ..e•3`.,.. 4"-,�`� .. P....:� .. "'i.. .;,:�. ,ems, �:i...
<br />i�..,-,
<br />Y .,, P.x., „S ,..... 7� b r fe,.. "',` 'S5. ,_< ,.�,:
<br />F RATING = 1-HR
<br />T RATING = 1-HR
<br />�A
<br />I:Q•:
<br />A
<br />NOTES SECTION
<br />I. FLOOR -CEILING ASSEMBLY.
<br />I.A. FLOORING SYSTEM
<br />1:B. WOOD JOIST
<br />I.C. GYPSUM WALLBOARD
<br />2. THROUGH PENETRANTS
<br />3. TUBE INSTALATION-PLASTICS
<br />4. FIRESTOP SYSTEM - RECTORSEAL FIRESEAL 'BIOSTOP BF150+
<br />i,
<br />6'
<br />N U �9 1
<br />(
<br />F RATING = 2-HR
<br />T RATING = 0-FIR
<br />NOT
<br />1. FLOOR OR WALL ASSEMBLY MINI 4-1/2 IN. THICK REINFORCED LIGHTWEIGHT OR NORMAL
<br />WEIGHT (100-150 PCF) CONCRETE. WALL MAY ALSO BE CONSTRUCTED OF ANY UL CLASSIFIED
<br />CONCRETE BLOCKS'. MAX AREA OF OPENING 224 SQ IN. WITH MAX DIMENSION OF 32 IN.
<br />2. SEE CONCRETE BLOCKS (CAZT) IN THE FIRE RESISTANCE DIRECTORY FOR NAMES OF
<br />MANUFACTURERS. CONDUIT ONE OR MORE NOM 4 IN DIAM (OR SMALLER) STEEL ELECTRICAL
<br />METALLIC TUBING OR STEEL CONDUIT TO BE INSTALLED EITHER CONCENTRICALLY OR
<br />ECCENTRICALLY WITHIN THE FIRESTOP SYSTEM. THE SPACE BETWEEN CONDUITS OR TUBES
<br />SHALL BE MIN 0 IN. (POINT CONTACT) TO MAX 1/2 IN. THE ANNULAR SPACE BETWEEN THE
<br />CONDUIT OR TUBE AND PERIPHERY OF OPENING SHALL BE MIN 0 IN. (POINT CONTACT) TO MAX
<br />2-3/4 IN. CONDUIT OR TUBE TO BE RIGIDLY SUPPORTED ON BOTH SIDES OF FLOOR OR WALL
<br />ASSEMBLY.
<br />3. CONDUIT - NOM 4 IN. DIAM (OR SMALLER) STEEL ELECTRICAL METALLIC CONDUIT OR STEEL
<br />CONDUIT. FILL, VOID OR CAVITY MATERIAL*- FOAM MIN 5 IN. THICKNESS OF FILL MATERIAL
<br />APPLIED WITHIN THE ANNULUS, EXTENDING 1./2 IN. ABOVE THE TOP SURFACE OF THE FLOOR
<br />OR BOTH SURFACES OF WALL AND OVERLAPPING THE CONCRETE 1/2 IN. ON ALL SIDES OF THE
<br />OPENING. HILTI CONSTRUCTION CHEMICALS, DIV OF HILT INC -- CP 620 FIRE FOAM *BEARING
<br />THE UL CLASSIFICATION MARK
<br />K IL
<br />3" = 1 °-0"
<br />5/$iDEPTH HILTI CP 606
<br />FLEXIBLE FIIRESTOP
<br />SEALANT OR HILTI F5 -
<br />ONE INTUMESCENT FIRE
<br />STOP SEALANT
<br />EXISTING 3/,
<br />PLYWOOD
<br />SUBFLOOR
<br />EXISTING
<br />FLOOR JOTS
<br />/ 3°"=V-0"
<br />New villimt all
<br />0
<br />�Sol nlull.1M-
<br />MINI 10 MIL VAPOR
<br />BARRIER TO MATCH
<br />EXISTING, IF EXISTING
<br />OS DAMAGED
<br />1Y i
<br />IN
<br />r
<br />It
<br />EXISTING CONCRETE
<br />SLAB ON GRADE -�
<br />COMPACTED FILL AS
<br />REQUIRED. PROVIDE
<br />COMPACTION TO 95%
<br />MODIFIED PROCTOR
<br />s'
<br />c x"
<br />w c
<br />4 1'
<br />3 Fx ;FA`
<br />i
<br />t
<br />AN&IUL1479 (ASTM E814)
<br />ANSWL1479 (ASTM E814)
<br />F RATING - 3 HR
<br />F RATING - 3 FIR
<br />T RATING - 0 HR
<br />FT RATING - 0 FIR
<br />L RATING AT AMBIENT - LESS
<br />FH RATING - 3 FIR
<br />THAN 1 CFM/SQ FT
<br />L RATING AT 400 F - 4 CFM/SQ FT
<br />FTH RATING - 0 FIR
<br />L RATING AT AMBIENT - LESS
<br />THAN 1 CFM/SQ FT
<br />L RATING AT 400 F - 4 CFM/SQ FT
<br />NOTE
<br />1. FLOOD OR WALL ASSEMBLY - MIN 4-1/2 IN. (114 MM) THICK REINFORCED LIGHTWEIGHT OR
<br />NORMAL WEIGHT (100-150 PCF OR 1600-2400 KG/M3) CONCRETE. WALL MAY ALSO BE
<br />CONSTRUCTED OF ANY UL CLASSIFIED CONCRETE BLOCKS*. MAX DIAM OF OPENING IS 32 IN.
<br />(813 MM).
<br />2. METALLIC SLEEVE (OPTIONAL) NOM 32 IN. (813 MM) DIAM (OR SMALLER) SCHEDULE 40 (OR
<br />HEAVIER) STEEL SLEEVE CAST OR GROUTED INTO FLOOR OR WALL ASSEMBLY, FLUSH WITH
<br />FLOOR OR WALL SURFACES OR EXTENDING A MAX OF 3 IN. (76 MM) .ABOVE FLOOR OR BEYOND
<br />BOTH SURFACES OF WALL.
<br />2.A. SHEET METAL SLEEVE -- (OPTIONAL) MAX 6 IN. (152 MM) DIAM, MIN 26 GA. GALV STEEL
<br />PROVIDED WITH A 26 GA GALV STEEL SQUARE FLANGE SPOT WELDED TO THE SLEEVE AT
<br />APPROX MID -HEIGHT, OR FLUSH WITH BOTTOM OF SLEEVE IN FLOORS, AND SIZED TO BE A
<br />MIN OF 2 IN. (51 MM) LARGER THAN THE SLEEVE DIAM. THE SLEEVE IS TO BE CAST IN
<br />PLACE AND MAY EXTEND A MAX OF 4 IN. (102 MM) BELCH/ THE BOTTOM OF THE DECK AND
<br />A MAX OF 1 IN. (25 MM) ABOVE THE TOP SURFACE OF THE CONCRETE FLOOR.
<br />2.1. SHEET METAL SLEEVE •- (OPTIONAL) - MAX 12 IN. (305 MM) DIAM, MIN 24 GA GALV STEEL
<br />PROVIDED W71-1 A 24 GA GALV STEEL_ SQUARE FLANGE SPOT WELDED TO THE SLEEVE AT
<br />APPROX MID -HEIGHT, OR FLUSH WITH BOTTOM OF SLEEVE IN FLOORS, AND SIZED TO BE A
<br />MINI OF 2 IN. (51 NAM) LARGER THAN THE SLEEVE DIAM. THE SLEEVE IS TO BE CAST IN
<br />PLACE AND MAY EXTEND A MAX OF 4 IN. (102 MM) BELOW THE BOTTOM OF THE DECK AND
<br />A MAX OF 1 IN. (25 MNA) ABOVE THE TOP SURFACE OF THE CONCRETE FLOOR.
<br />3. THROUGH -PENETRANT - ONE METALLIC PIPE, TUBE OR CONDUIT TO BE INSTALLED EITHER
<br />CONCENTRICALLY OR ECCENTRICALLY WITHIN THE FIRESTOP SYSTEM. THE ANNULAR SPACE
<br />BETWEEN PENETRANT AND PERIPHERY OF OPENING SHALL BE MIN 0 IN. (POINT CONTACT) TO
<br />MAX 1-7/8 IN. (48 MM). PENETRANT MAY BE INSTALLED WITH CONTINUOUS POINT CONTACT.
<br />PENETRANT TO BE RIGIDLY SUPPORTED ON BOTH SIDES OF FLOOR OR WALL ASSEMBLY. THE
<br />FOLLOWING TYPES AND SIZES OF METALLIC PENETRANTS MAY BE USED:
<br />A. STEEL PIPE - NOM 30 IN. (762 MM) DIAM (OR SMALLER) SCHEDULE 10 (OR HEAVIER) STEEL
<br />PIPE.
<br />B. IRON PIPE - NOM 30 IN. (762 MtlM) DIA (OR SMALLER) CAST OR DUCTILE IRONS PIPE.
<br />C. 'COPPER PIPE - NOM 6 IN. (152 MM) DIA (OR SMALLER) REGULAR (OR HEAVIER) COPPER
<br />PIPE.
<br />D. COPPER TUBING - NOM 5 IN. (152 Mull) DIA (OR SMALLER) TYPE L (OR HEAVIER) COPPER
<br />TUBING.
<br />E. CONDUIT - NOM 6 IN. (152 MM) DIA (OR SMALLER) STEEL CONDUIT:
<br />F. CONDUIT - NOM 4 IN. (102 MM) DIA (OR SMALLER) STEEL ELECTRICAL METALLIC TUBING
<br />(EMT).
<br />4. FIRESTOP SYSTEM -THE FIRESTOP SYSTEM SHALL CONSIST OF THE FOLLOWING:
<br />A. PACKING MATERIAL - MIN 4 IN. (102 MM) THICKNESS OF MIN 4 PCF (64 KG/M3) MINERAL
<br />WOOL BATT INSULATION FIRMLY PACKED INTO OPENING AS A PERMANENT FORM. PACKING
<br />MATERIAL TO BE RECESSED FROM TOP SURFACE OF FLOOR OR SLEEVE OR FROM BOTH
<br />SURFACES OF WALL OR SLEEVE AS REQUIRED TO ACCOMMODATE THE REQUIRED
<br />THICKNESS OF FILL MATERIAL.
<br />B. FILL, VOID OR CAVITY MATERIAL* - SEALANT - MIN 1/4 IN. (6 MIND THICKNESS OF FILL
<br />MATERIAL APPLIED WITHIN THE ANNULUS, FLUSH WITH TOP SURFACE OF FLOOR OR
<br />SLEEVE OR WITH BOTH SURFACES OF WALL OR SLEEVE, AT THE POINT OR CONTINUOUS
<br />CONTACT LOCATIONS BETWEEN PENETRANT AND CONCRETE OR SLEEVE, A MIN 1/4 IN. (6
<br />MM) DIAM BEAD OF FILL MATERIAL SHALL BE APPLIED AT THE CONCRETE OR SLEEVE/ PIPE
<br />PENETRANT INTERFACE ON THE TOP SURFACE OF FLOOR AND ON BOTH SURFACES OF
<br />WALL.
<br />HILTI CONSTRUCTION CHEMICALS, DIV OF HILTI INC - FS-ONE SEALANT OR FS-ONE MAX
<br />INTUMESCENT SEALANT
<br />* INDICATES SUCH PRODUCTS SHALL BEAR THE UL OR CUL CERTIFICATION MARK FOR
<br />JURISDICTIONS EMPLOYING THE UL OR CUL CERTIFICATION (SUCH AS CANADA), RESPECTIVELY.
<br />\� L
<br />EXISTING
<br />CONCRETE SLAB
<br />ON GRADE
<br />1•:e.
<br />1
<br />:4 G �a a. ®:
<br />..., .. . ,.,, •
<br />I
<br />�, c
<br />o _ c P:. c:'>
<br />o�,.c� �.7a c
<br />c�c �""V c c i�`l-U" c��C
<br />6X6 MiESH
<br />COMPACTED FILL AS REQUIRED. PROVIDE
<br />PROVIDE CONTINUOUS
<br />COMPACTION TO 95% MODIFIED PROCTOR
<br />SEPARATED CHEMICAL
<br />PEST BARRIER AT ALL
<br />DISTURBED AND
<br />MIN 10 MIL VAPOR BARRIER TO MATCH
<br />EXPOSED SOIL PRIOR TO
<br />EXISTING, IF EXISTING IS DAMAGED
<br />COVERING WITH
<br />r r Mr Pr=Tl= 8Mn Asa' �oA
<br />m V i m t f ? t � Y }
<br />v u TES €� x,
<br />� f
<br />`
<br />Rfi Yh;f,3.T ,++. slr,:.; :x F-.9,. ... ,....f .�' Y
<br />� A. ,. ...,.t ,EEx, S s. er , .,. e., + ,. ,v...a ... n.i• ., K'
<br />ANSVUL1479 (AASTM E814)
<br />ANSVUL1 479 (ASTM E814)
<br />FRATING -2HR
<br />FRATING -2HR
<br />T RATING - 2 FIR
<br />FT RATING - 2 FIR
<br />L RATING AT AMBIENT - LESS
<br />FH RATING - 2 FIR
<br />THAN 1 CFM/SQ FT
<br />L RATING AT 400 F - 4 CFM/SQ FT
<br />FTH RATING - 2 FIR
<br />L RATING AT AMBIENT - LESS
<br />W RATING - CLASS 1 (SEE ITEM 3B)
<br />THAN 1 CFM/SQ FT
<br />L RATING AT 400 F - 4 CFM/SQ FT
<br />TES.
<br />1. FLOOR ASSEMBLY - MIN 4-1/2 IN. (114 MM) THICK REINFORCED LIGHTWEIGHT OR NORMAL
<br />WEIGHT'(100-150 PCF OR 1600-2400 KG/M3) CONCRETE. AS AN ALTERNATE, ANY MIN 2 HR FIRE
<br />RATED D700, D800 OR D900 SERIES FLOOR -CEILING DESIGN IN THE UL FIRE RESISTANCE
<br />DIRECTORY HAVING A MINI 2-1/2 IN. (64 MM) THICKNESS OF LIGHTWEIGHT OR NORMAL WEIGHT
<br />(100-150 PCF OR 1600-2400 KG/M') CONCRETE TOPPING OVER THE STEEL DECK MAY BE USED.
<br />MAX DIAM OF OPENING IS 12-3/4 IN. (324 MM).
<br />2. THROUGH -PENETRANT - ONE METALLIC PIPE INSTALLED CONCENTRICALLY OR
<br />ECCENTRICALLY WITHIN OPENING. ANNULAR SPACE BETWEEN PENETRANT AND PERIPHERY
<br />OF OPENING SHALL BE MIN OF 0 IN. (POINT CONTACT) TO MAX 2 IN. (51 NAM). PENETRANT TO BE
<br />RIGIDLY SUPPORTED ON BOTH SIDES OF FLOOR ASSEMBLY. THE FOLLOWING TYPES AND
<br />SIZES OF PENETRANTS MAY BE USED:
<br />A. STEEL PIPE- NOM 10 IN. (254 MM) DIAM (OR SMALLER) SCHEDULE 40 (OR HEAVIER)
<br />STEEL PIPE.
<br />B. IRON PIPE - NON A 10 IN. (254 MM) DIAM (OR SMALLER) CAST OR DUCTILE IRON PIPE.
<br />C. CONDUIT - NOM 4 IN. (102 MM) DIAM (OR SMALLER) STEEL ELECTRICAL METALLIC TUBING
<br />OR NOM 6 IN. (152 MM) DIAM (OR SMALLER) RIGID STEEL CONDUIT.
<br />3. FIRESTOP SYSTEM -THE FIRESTOP SYSTEM SHALL CONSIST OF THE FOLLOWING:
<br />A. PACKING MATERIAL - MIN 2 IN. (51 MM) THICKNESS OF MIN 4 PCF (64 KG/M3) MINERAL
<br />WOOL BATT INSULATION FIRMLY PACKED INTO OPENING AS A PERMANENT FORM. WHEN
<br />CP 604, CFS-S SIL GG OR CFS-S SIL SL SEALANT IS USED (SEE ITEM 3B), MIN THICKNESS
<br />OF PACKING MATERIAL 1S 4 IN. (102 MM) AND MIN THICKNESS OF FLOOR IS 4-1/2 IN. (114
<br />MM). PACKING MATERIAL TO BE RECESSED FROM TOP SURFACE OF FLOOR TO
<br />ACCOMMODATE THE REQUIRED THICKNESS OF FILL MATERIAL.
<br />B. FILL, VOID OR CAVITY MATERIALS* - SEALANT - MIN 1/2 IN. (13 MM) THICKNESS OF
<br />SEALANT APPLIED WITHIN THE ANNULUS, FLUSH WITH TOP SURFACE OF FLOOR. HILTI
<br />CONSTRUCTION CHEMICALS, DIV OF HILTI INC - FS-ONE SEALANT, FS-ONE MAX
<br />INTUMESCENT SEALANT OR CP 604 SELF -LEVELING FIRESTOP SEALANT, CFS-S SIL GG OR
<br />CFS-S SIL SL SEALANT. W RATING APPLIES ONLY WHEN CP 604, CFS-S SIL GG OR CFS-S
<br />SIL SL SEALANT IS USED.
<br />C. DUCT WRAP MATERIAL* - ENCAPSULATED DUCT WRAP TIGHTLY \A/RAPPED AROUND
<br />PENETRANT TO EXTEND 24 IN. (610 MM) ABOVE THE FLOOR FOR PENETRANTS OF NOM 4
<br />IN. (102 NAM) DIAM OR SMALLER, AND 36 IN. (914 MM) ABOVE FLOOR FOR PENETRANTS
<br />GREATER THAN A NOM 4 IN. (102 MM) DIAM. AN ADDITIONAL LAYER OF ENCAPSULATED
<br />DUCT WRAP TIGHTLY WRAPPED AROUND THE FIRST LAYER OF DUCT WRAP TO EXTEND
<br />12 IN. (305 MM) (914 MM) ABOVE FLOOR. ALL LONGITUDINAL SEAMS OF BOTH LAYERS OF
<br />DUCT WRAP AND JOINTS BETWEEN LAYERS OF DUCT WRAP ARE SEALED WITH FOIL
<br />TAPE. ONE OF THE FOLLOWING TYPES AND THICKNESSES OF DUCT WRAP MAY BE USED:
<br />CA. NOM 1-1/2 IN. (38 MM) OR 2 IN. (51 MM) THICK ENCAPSULATED DUCT WRAP. UNIFRAX I
<br />LLC - FYREWRAP DUCT INSULATION OR FIREWRAP DUCT 1.5 INSULATION
<br />C.2. NOM 1-1/2 IN. (38 MM) THICK ENCAPSULATED DUCT WRAP. THERMAL CERAMICS INC
<br />- FIREMASTER FASTWRAP XL DUCT INSULATION
<br />* INDICATES SUCH PRODUCTS SHALL BEAR THE UL OR CUL CERTIFICATION MARK FOR
<br />JURISDICTIONS EMPLOYING THE UL OR CUL CERTIFICATION (SUCH AS CANADA),
<br />RESPECTIVELY.
<br />I / 3"=1'-0"
<br />3 REBAR CONT. (TYP) AT ALL INTERSECTIONS SAW CUT AND REMOVE EXISTING
<br />AND LAPS REBAR SHALL BE TIED WITH 16 GA. SLAB FOR TRENCH AS REQUIRED
<br />REBAR TIE WIRE. TAPE IS NOT ACCEPTABLE.
<br />#3 REBAR (TYP) EPDXY
<br />NEW 3,500 PSI CONCRETE SLABS ON
<br />COATED WITH HILTS
<br />GRADE TO MATCH 'DEPTH OF EXIST.,
<br />HIT-HY 200. INSTALL PER
<br />WITH #3 BARS AT 16" O.C. EACH WAY
<br />ICC-ES-3187 ----g
<br />AT MIDDLE DEPTH OF SLAB. DRILL AND
<br />I
<br />EPDXY 6° INTO EXIST. SLAB.
<br />EXISTING SLAB
<br />ON GRADE AS
<br />OCCURS-------� CONDUITLOCATE ABOVE 'VAPOR BARRIER
<br />PROVIDE CONTINUOUS
<br />SEPARATED CHEMICAL
<br />PEST BARRIER @ ALL
<br />DISTURBED AND
<br />EXPOSED SOIL PRIOR
<br />TO COVERING WITH
<br />CONCRETE AND ABC
<br />FILL
<br />VAPOR BARRIER TO ® COMPACTED FILL
<br />MATCH EXISTING AS REQUIRED
<br />12920 SE 38th STREET
<br />BELLEVUE, VVA 98006
<br />www.T-Mobile.com
<br />COPYRIGHT NOTICE:
<br />THESE DRAWINGS AND SPECIFICATIONS ARE COPYRIGHTED AND SUBJECT TO
<br />COPYRIGHT PROTECTION AS AN "ARCHITECTURAL WORK" UNDER SEC. 102 OF
<br />THE COPYRIGHT ACT, 17 U.S.C. AS AMENDED JANUARY 2003. THE PROTECTION
<br />INCLUDES, WITHOUT LIMITATION, THE OVERALL. FORM, ARRANGEMENT AND
<br />COMPOSITION OF SPACES AND ELEMENTS OF THE DESIGN. UNDER SUCH
<br />PROTECTION, UNAUTHORIZED USE OF THESE DRAWINGS AND SPECIFICATIONS
<br />MAY RESULT IN CESSATION OF CONSTRUCTION, BUILDING SEIZURE, AND/OR
<br />MONETARY LIABILITY.
<br />ARCHITECT:
<br />,( r'
<br />056 BVemoac1
<br />n ar x rr g Miaradeilur4 Ohio A 342
<br />s ..1+r1 844.50,4.7100:
<br />8007
<br />REGISTERED
<br />1, DONALD J, RETHMAN'
<br />STATE OF WASHINGTON
<br />07/06/
<br />CONSULTING ENGINEER:
<br />Lu
<br />uj
<br />op
<br />Lu
<br />UJ
<br />Lu
<br />DATE: July 02, 2021
<br />SCALE: AS NOTED
<br />DRAWN BY: PT
<br />SAP NUMBER:
<br />CORPORATE REBULD CD
<br />G.C. SHALL KEEP TRNCHING TO LDC
<br />,, ° ��n
<br />A I\/VINIMUM TO PROVIDE STUB -UPS Ce II Y OF EN � R, I FI
<br />FOR ALL FIXTURES. 36" MAXIMUM R'r'd ')'��" M I
<br />�V 1II F `a H SHEET TITLE:
<br />SLAB DETAILS
<br />SHEET NUMBER:
<br />SLAB ILL AT SUPPLYMASTE
<br />l 3 l'-0"
<br />INFILL ATLEAVE OUT
<br />3. 1'-0"
<br />4 3 2
<br />z
<br />UNG AT TRENCH
<br />1
<br />DATE: July 02, 2021
<br />SCALE: AS NOTED
<br />DRAWN BY: PT
<br />SAP NUMBER:
<br />CORPORATE REBULD CD
<br />G.C. SHALL KEEP TRNCHING TO LDC
<br />,, ° ��n
<br />A I\/VINIMUM TO PROVIDE STUB -UPS Ce II Y OF EN � R, I FI
<br />FOR ALL FIXTURES. 36" MAXIMUM R'r'd ')'��" M I
<br />�V 1II F `a H SHEET TITLE:
<br />SLAB DETAILS
<br />SHEET NUMBER:
<br />SLAB ILL AT SUPPLYMASTE
<br />l 3 l'-0"
<br />INFILL ATLEAVE OUT
<br />3. 1'-0"
<br />4 3 2
<br />z
<br />UNG AT TRENCH