<br />1 A SCOPE
<br />1.1 THE COMPLETE INSTALLATION SHALL BE MADE IN STRICT ACCORDANCE WITH THE LANDLORD'S REQUIREMENTS.
<br />CONSULT LANDLORD'S DESIGN CRITERIA.
<br />1.2 THE DRAWINGS AND THE SPECIFICATIONS SHALL BE CONSIDERED ADDITIONAL_ TO ARCHITECT AND MECHANICAL
<br />ENGINEER'S SPECIFICATIONS. ANY DISCREPANCY OR CONTRADICTION SHALL BE BROUGHT
<br />TO THE ATTENTION OF THE ENGINEER.
<br />1.3 ARCHITECT'S GENERAL REQUIREMENTS ARE PART OF THIS CONTRACT. AND THEY SHALL BE APPLIED BY
<br />THE GENERAL CONTRACTOR AND SUBCONTRACTORS (ELECTRICAL,ETC..).
<br />1.4 ONCE ONSITE GENERAL CONTRACTOR SHALL FAMILIARIZE HIMSELF WITH ANY CONDITIONS THAT MAY AFFECT HIS
<br />WORK IN ANY MANNER PRIOR TO START OF CONSTRUCTION. (MEASUREMENTS - PARTICULAR CONDITIONS, ETC...)
<br />GENERAL CONTRACTOR SHALL NOTIFY TENANT REPRESENTATIVE AND ARCHITECT OF ANY SUCH CONDITIONS PRIOR TO
<br />COMMENCEMENT OF WORK.
<br />1.5 GENERAL CONTRACTOR SHALL MAKE ALL NECESSARY CHECKING AND ADJUSTMENTS TO COMPLY WITH THE INTENT
<br />OF SPECIFICATIONS.
<br />1.6 THE DRAWINGS SHOW THE APPROXIMATE LOCATION OF THE EQUIPMENT. EACH SUBCONTRACTOR SHALL VERIFY
<br />THESE LOCATIONS BEFORE INSTALLATION.
<br />1.7 GENERAL CONTRACTOR'S TENDER SHALL INCLUDE THE COST OF ALL NECESSARY PERMITS AND CERTIFICATES, ALL
<br />DRAWINGS APPROVAL COSTS AND ALL INSPECTION COSTS REQUIRED BY ALL AUTHORITIES HAVING JURISDICTION.
<br />1.8 EACH SUBCONTRACTOR SHALL COMPLETE THE WORK IN EVERY DETAIL. EVEN THOUGH NOT SHOWN ON DRAWINGS
<br />OR CALLED FOR IN THIS SPECIFICATION.
<br />1.9 THE ELECTRICAL TRADE SHALL PROVIDE ALL LABOR AND MATERIALS NECESSARY FOR A COMPLETE AND OPERATING
<br />ELECTRICAL SYSTEM AS INDICATED ON THE DRAWINGS. THE TRADE SHALL ALSO PROVIDE ANY ITEMS AND/OR LABOR
<br />THAT ARE OBVIOUSLY NECESSARY OR REASONABLY IMPLIED TO COMPLETE ALL WORK.
<br />1.10 ALL ELECTRICAL WORK TO BE DONE IN ACCORDANCE WITH APPLICABLE EDITIONS AND AMENDMENTS OF THE
<br />NATIONAL ELECTRICAL CODE (NEC), NFPA AND ALL LOCAL CODES ADOPTED BY THE LOCAL JURISDICTION HAVING
<br />AUTHORITY.
<br />l A l ALL RUBBISH'S AND GARBAGE SHALL BE REMOVED FROM THE JOB SITE AT THE END OF EVERY WORKDAY. AT THE
<br />CONTRACT COMPLETION, ALL TOOLS AND EQUIPMENT SHALL BE REMOVED AND
<br />THE JOB SITE SHALL BE LEFT IN A CLEAN CONDITION..
<br />2.0 GUARANTEE
<br />2.1 EACH SUBCONTRACTOR SHALL GUARANTEE HIS WORK AND INSTALLATION REGARDING HIS CONTRACT. THE
<br />ELECTRICAL CONTRACTOR SHALL REPAIR OR REPLACE, AT HIS OWN EXPENSE, ALL DEFECTS AND THIS DURING A TWELVE
<br />MONTHS PERIOD, STARTING AT THE PROVISIONAL ACCEPTANCE BY THE TENANT. AS LONG AS THE DEFECTS IS NOT DUE
<br />TO A BAD USE OR NORMAL WEAR.
<br />3.0 TAXES
<br />3.1 EACH SUBCONTRACTOR SHALL PAY ALL APPLICABLE TAXES, FOR LABOR AND MATERIAL INCLUDED IN HIS TENDER
<br />4.0 TEMPORARY SERVICES
<br />4.1 ALL TEMPORARY LIGHTING (MIN. 20OLUX WITH MH HALIDE FIXTURE) AND POWER DURING CONSTRUCTION SHALL BE
<br />BY GENERAL CONTRACTOR AFTER AGREEMENT WITH ELECTRICAL CONTRACTOR AND SHALL BE TAKEN FROM EXISTING
<br />PANEL SERVING THE SPACE, SUPPLY VOLTAGE AND AMPS AS REQUIRED.
<br />5.0 SHOP DRAWINGS
<br />5.1 PRIOR TO ORDERING OR INSTALLING ANY EQUIPMENT SUBMIT TO ENGINEER FOR APPROVAL A MINIMUM OF TWO (2)
<br />COPIES OF SHOP DRAWINGS FOR EACH ITEM OF EQUIPMENT
<br />6.0 ALTERNATE EQUIPMENT
<br />6.1 PROPOSAL SHALL BE BASED ON SPECIFIED EQUIPMENT AND MATERIAL.
<br />6.2 PROPOSAL FOR ALTERNATE TO SPECIFICATION SHALL INCLUDE MANUFACTURER NAME, MODEL AND COST
<br />MODIFICATION,
<br />6.3 COST OF ANY CHANGE REQUIRED TO OTHER TRADES WORK. DUE TO SUBSTITUTION OF ALTERNATE EQUIPMENT,
<br />SHALL BE INCLUDED IN THE SUBCONTRACTOR'S PROPOSAL CALLING FOR THIS SUBSTITUTION. EVEN IF THESE CHANGES
<br />APPEAR AFTER THE DEMAND FOR SUBSTITUTION.
<br />6.4 ALTERNATE PROPOSALS WILL BE ACCEPTED OR REJECTED BEFORE CONTRACTS ARE AWARDED. NO CHANGES WILL
<br />BE ALLOWED AFTER THE CONTRACT IS SIGNED.
<br />7.0 IDENTIFICATION
<br />7.1 ALL ELECTRICAL EQUIPMENT (SWITCHES, PANELS, CIRCUITS ETC..) MUST BE PROPERLY IDENTIFIED WITH LAMICOID
<br />NAME PLATES SCREWED ON PANELS AND HAVE A TYPED DIRECTORY AND INDICATE LOAD ON
<br />EACH CIRCUIT.
<br />8.0 GROUND
<br />8.1 THE GROUND SHALL BE CONTINUOUS AND SHALL BE CONFORM TO THE APPLICABLE EDITION OF THE NATIONAL
<br />ELECTRICAL CODE.
<br />9.0 PULLING AND JUNCTION BOXES
<br />9.1 TRADE WILL PROVIDE PULLING AND JUNCTION BOXES WITH SCREWED PLATED COLOR MATCHED FOR WALL AND
<br />CEILING FINISHES.
<br />9.2 ALL BOXES SHALL BE ACCESSIBLE.
<br />9.3 BACK TO BACK BOXES WILL NOT BE ACCEPTED.
<br />9.4 PULL BOXES SHALL BE LOCATED EVERY 100 FEET (30m) AND EVERY TWO 90 DEG, ELBOW,
<br />9.5 ALL SURFACE MOUNTED BOXES FOR JUNCTION, SOCKETS, SWITCHES, FIXTURES ETC .... SHALL BE F.S. TYPE.
<br />10.0 DRILLING
<br />10.1 ELECTRICAL CONTRACTOR SHALL DRILL OR SAW CUT THE FLOOR WHERE REQUIRED. ELECTRICAL CONTRACTOR
<br />SHALL PROVIDE AND INSTALL SLEEVES IN CONCRETE SLAB, WHERE REQUIRED.
<br />10.2 NO ELECTRICAL OR PNEUMATIC HAMMER SHOULD BE USED.
<br />10.3 EXISTING CONCRETE COLUMNS ARE NOT TO BE CHANNELED OR NOTCHED.
<br />11.0 WIRING AND CONDUIT
<br />11.1 ALL WIRING, WILL BE COPPER TYPE, No.12 AWG MINIMUM, UNLESS OTHERWISE NOTED.
<br />11.2 ALL SURFACE WIRING, SHALL BE THWN TYPE IN E.M.T. CONDUIT. ALL COUPLINGS TO BE RAIN TIGHT OR GALVANIZED
<br />SET CREW TYPE.
<br />11.3 ALL WIRING AND CONDUIT, WILL BE RECESSED IN WALL OR CEILING (INCLUDING EXISTING ARCHITECTURAL
<br />ELEMENTS) UNLESS APPROVED BY LOCAL INSPECTOR AND AHJ. ELECTRICAL CONTRACTOR TO VERIFY.
<br />11.4 ALL CONDUIT SHALL BE PARALLEL WITH ARCHITECTURAL LINES AND DESIGN.
<br />11.5 FOR SUSPENDED CEILING, MC CABLE FOR 15 FEET (4.5m) IS ACCEPTED. MAIN WIRING TO BE THWN IN E.M.T. CONDUIT.
<br />11.6 ALL EMPTY CONDUIT SHALL INCLUDE A PULLING WIRE No.12 AWG. -MAX. 6'-0" FLEXIBLE CONDUIT MAYBE USED FOR
<br />FIXTURE AND EQUIPMENT CONNECTIONS ONLY. PLASTIC CONDUIT IS NOT ACCEPTED.
<br />12.0 FIRE BARRIER:
<br />12.1 IN CASE OF CROSSING A FIRE BARRIER (FLOOR, WALL, OR CEILING) FILL GAP WITH APPROPRIATE MATERIAL. THIS
<br />MATERIAL SHALL BE EFFICIENT BARRIER FOR FLAME, FUME AND GAS. SEAL AT SMOKE WALL.
<br />I
<br />13.0 EXPANSION JOINT
<br />13.1 EACH TIME ELECTRICAL CONDUIT PASS THROUGH AN EXPANSION JOINT OF THE BUILDING USE GALVANIZED STEEL
<br />SLIDING TYPE EXPANSION JOINT WITH CONTINUOUS COPPER GROUNDING. FLEXIBLE AT THESE LOCATIONS.
<br />14.0 FIXTURES AND LAMPS
<br />14.1 COMPLETE LIGHTING PACKAGE IS OWNER (OR LANDLORD) FURNISHED (REFER TO LEASE AGREEMENT), GC
<br />INSTALLED. ELECTRICAL CONTRACTOR SHALL INSTALL ALL FIXTURES, LAMPS AND CONTROLS PER MANUFACTURER
<br />SPECS AND RDSS (ENERGY DESIGN SERVICE SYSTEMS) INSTALLATION INSTRUCTIONS.
<br />15.0 FIELD CONDITIONS
<br />15.1 ENGINEER CAN RELOCATE ALL EQUIPMENT (FIXTURES, OUTLETS, ETC...), AT NO COST, IF DISPLACEMENT IS LESS
<br />THAN 10 FEET (3m), AND WRITTEN NOTICE IS SENT TO CONTRACTOR PRIOR TO INSTALLATION,
<br />15.2 CONFER WITH ALL OTHER TRADES AND ARRANGE EQUIPMENT IN PROPER RELATION WITH OTHER APPARATUS,
<br />DUCTS, PIPES, ETC. AND WITH BUILDING CONSTRUCTION AND ARCHITECTURAL FINISHES.
<br />16.0 EXISTING CONDITIONS
<br />16.1 ELECTRICAL CONTRACTOR WORK AFFECTING OTHER TENANT SHALL BE DONE OFF BUSINESS HOURS (NIGHT OR
<br />WEEK -END). COORDINATE WITH THE LANDLORD,
<br />16.2 ELECTRICAL CONTRACTOR SHALL REMOVE AND LEGALLY DISPOSE ANY UNUSED MATERIAL.
<br />16.3 ANY NON REUSED MATERIAL SHALL BE GIVEN BACK IN GOOD CONDITION TO LANDLORD
<br />16.4 ANY DAMAGED WALL, FLOOR, CEILING, FINISHES SHALL BE REPAIRED BY GENERAL CONTRACTOR THOSE REPAIRS
<br />SHALL MATCH EXISTING FINISHES.
<br />17.0 COMMUNICATIONS
<br />17.1 TENANT IS IN CHARGE FOR ANY COMMUNICATIONS SYSTEMS.
<br />17.2 ELECTRICAL CONTRACTOR SHALL PROVIDE AND INSTALL, IF REQUIRED, TELEPHONE TERMINAL BOARD, 24"x24"
<br />PLYWOOD 3/4" THICK (OR AS DETAILED IN PLANS), AND CONDUIT AS INDICATED ON DRAWINGS.
<br />17.3 ALL WIRING, INCLUDING INSTALLATION AND CONNECTION TO EQUIPMENT SHALL BE PERFORMED BY A SPECIALIZED
<br />CONTRACTOR, IN CHARGE OF THE TENANT.
<br />18.0 FIRE ALARMS
<br />18A EXISTING FIRE ALARM TO BE KEPT TENANT'S FIRE ALARM CONTRACTOR TO RELOCATE IF REQUIRED ANY
<br />EQUIPMENT AT NO COST.
<br />18.2 ALL REQUIRED WORK RELATED TO LIFE SAFETY SYSTEMS SHALL BE DONE AT NO EXTRA COST. RETAIN THE SYSTEM
<br />MANUFACTURER'S FORCES TO PERFORM FINAL CONNECTIONS, MODIFICATIONS AND PROVISION OF NEW INTERFACING
<br />DEVICES IN THE SYSTEM PANELS, ETC.
<br />18.3 ENSURE FULL COMPATIBILITY OF ALL NEW DEVICES WITH EXISTING LIFE SAFETY SYSTEMS.
<br />18.4 TENANT'S FIRE ALARIA CONTRACTOR SHALL HAVE SYSTEM MANUFACTURER TEST AND CERTIFY LIFE SAFETY
<br />SYSTEMS FOR PROPER OPERATION AT COMPLETION OF WORK.
<br />19.0 COLOR CODE
<br />120/203V
<br />120/240V HIGH LEG 3P AN 277/430V
<br />PHASE A
<br />BLACK
<br />BLACK BROWN
<br />PHASE B
<br />RED
<br />ORANGE ORANGE Y
<br />PHASE C
<br />BLUE
<br />BLUE W YELLOW
<br />NEUTRAL
<br />WHITE
<br />WHITE GREY
<br />GROUND
<br />GREEN~
<br />GREEN GREEN
<br />20.0 SPECIAL_ NOTES
<br />20.1 ELECTRICAL CONTRACTOR TO PROVIDE UNDERGROUND CONDUIT TO EC PROVIDED SURFACE MOUNTED J-BOXES,
<br />OWNER FURNISHED RECESSED FLOOR BOXES AND OWNER FURNISHED POKE-THRU BOXES AS INDICATED AND PROVIDE
<br />APPROVED FLEX CONNECTION ASSEMBLY. LEAVE FLEX CONNECTION ASSEMBLY COILED AND TAPED AS REQ'D UNTIL
<br />FIXTURE INSTALLATION. AFTER FIXTURE INSTALLATION EC TO INSTALL POWER RECEPTACLES IN PRE -INSTALLED BLANK
<br />BOXES INSIDE FIXTURE, PROVIDE POWER CIRCUIT FROM PANEL TO RECEPTACLES AND CONNECTION POWER SOURCE. EC
<br />TO PROVIDE PULL STRING FROM TELEPHONE BOARD TO ALL FIXTURE DESIGNATIONS FOR CAT5E DATA CABLING AND RJ45
<br />JACKS BY OWNER'S VENDOR. SEE WIRING DETAILS ON SHEETS E501 AND E511 FOR ADDITIONAL INFORMATION.
<br />20.2 ON ALL OUTLETS LOCATED IN POS COUNTERS, ETC..., ELECTRICAL TRADE SHALL ATTACH ALL CONDUITS TO THE
<br />FLOOR WITH APPROPRIATE CONNECTORS. GC MUST OBTAIN WRITTEN APPROVAL FROM THE LANDLORD PRIOR TO ANY
<br />TRENCHING OR CORE DRILLING.
<br />20.3 RECEPTACLES, OUTLETS, ETC..., LOCATED AT THE CASH COUNTERS SHALL BE INSTALLED IN COMMON BOXES, USE 1
<br />GANG, 2 GANG, 3 GANG OR 4 GANG, ETC..., BOXES C[W SEPARATIONS AS PER CODE, AS REQUIRED. BOXES SUPPLIED,
<br />INSTALLED AND CONNECTED BY THE ELECTRICAL CONTRACTOR.
<br />21.0 DEMOLITION
<br />21.1 REMOVE AND TRANSPORT OUT OF THE CONSTRUCTION SITE ALL EQUIPMENT MADE OBSOLETE CONSECUTIVE TO
<br />THE WORK, INCLUDING WIRING, CONDUITS, BOXES, OUTLETS, SWITCHES, LIGHTING FIXTURES, DISTRIBUTION EQUIPMENT,
<br />SUPERVISORY AND COMMUNICATION EQUIPMENT. ALL ACCESSORIES BEING PART OF THE ELECTRICAL INSTALLATION.
<br />21.2 REMOVE THE WIRING AND THE CONDUIT UP TO THE LAST PANEL OR BOX KEPT IN THE NETWORK.
<br />21.3 PUT BACK IN SERVICE ALL FEEDERS, CONTROL OR COMMUNICATION CABLES WHEN THE CONTINUITY OF THOSE
<br />SERVICES IS INTERRUPTED BY THE WORK.
<br />22.0 SPECIFICATIONS
<br />22.1 DISCONNECT AS PER CUTLER -HAMMER
<br />22.2 FUSES AS PER GOULD
<br />MODEL
<br />FUSE
<br />INSTALLATION
<br />HD
<br />WITH
<br />INTERIOR
<br />LID m
<br />WITHOUT
<br />INTERIOR
<br />RD
<br />UVITH
<br />EXTERIOR
<br />R® _-
<br />--WITHOUT
<br />EXTERIOR
<br />GAGE
<br />MODEL
<br />SPARE CITY.
<br />0 500A
<br />AJT
<br />M% MINIMUM 6
<br />22.3 SPUTTER BOXES AND TROUGHS, AS PER BEL, 14 GA STEEL WITH HINGED COVER CLOSED WITH SCREWS, TINNED
<br />COPPER BUS BARS, COMPLETE WITH SOLDERLESS TERMINALS. BARS SUPPORTED BY ISOLATORS.
<br />22.4 TRANSFORMERS AS PER DELTA, DT (TRIPLE PHASE).
<br />22.5 PANELS CAA/ DOORS AND LOCKS, AS PER CUTLER -HAMMER
<br />USAGE
<br />VOLTAGE
<br />MODEL
<br />LIGHTING
<br />120/20 3P3PH
<br />PRL 1
<br />BREAKERS WITH 10,000 A SYMMETRICAL INTERRUPTING
<br />CAPACITY, UNLESS OTHERWISE NOTED
<br />22.6 OUTLETS AS PER LEVI I ON, MODEL NO, 5262, WHITE.
<br />22.7 SWITCH
<br />TYPE _
<br />-
<br />UNIPOLAR
<br />_MODEL
<br />5401/001
<br />BIPOLAR
<br />54502/001
<br />THREE WAY
<br />54503/001
<br />FOUR WAY
<br />54504/001
<br />2
<br />1
<br />SYMBOLSLEGEND
<br />NOTE: NOT ALL SYMBOLS LISTED BELOW ARE SHOWN ON PLANS
<br />SWITCHING
<br />POWER
<br />DISTRIBUTION DEVICES
<br />GENERA. WIRING
<br />SWITCH BANK
<br />PANELBOARD SURFACE MOUNTED MAXIMUM
<br />HOMERUN - CONDUIT SYSTEM TO
<br />72" TO TOP OF OVERCURRENT PROTECTION
<br />PANEL AS NOTED ON DRAWINGS
<br />SWITCH _
<br />ET
<br />TRANSFORMER a
<br />CONDUIT SYSTEM UNDER FLOOR
<br />DIMMER SWITCH
<br />DISCONNECT SWITCH
<br />CONDUIT UP
<br />OS
<br />OCCUPANCY SENSOR - CEILING MOUNTED
<br />'M `)
<br />METER
<br />TELEPHONE TERMINAL BOARD
<br />ti
<br />SEE DETAIL AIL ON SHEET E4
<br />®
<br />OCCUPANCY SENSOR - WALL MOUNTED
<br />DUPLEX RECEPTACLE - 20A
<br />JUNCTION BOX
<br />18" AFF UNO
<br />PC
<br />PHOTOCELL - CEILING MOUNTED
<br />QUADPLEX RECEPTACLE - 20A
<br />RECESSED FLOOR BOX
<br />18" AFF UNO
<br />LCP
<br />LCP - LIGHTING CONTROL PANEL
<br />GFI
<br />RECEPTACLE
<br />ABBREVIATIONS
<br />WITH GROUND FAULT INTERRUPTER
<br />INVER
<br />MINI -INVERTER
<br />WP
<br />WEATHERPROOF RECEPTACLE
<br />BOH
<br />BACK OF HOUSE
<br />1$ AFF UNO
<br />CB
<br />CIRCUIT BREAKER
<br />Tvss
<br />TRANSIENT VOL RAGE SURGE SUPPRESSOR
<br />SHOW WINDOW RECEPTACLE
<br />DL
<br />DAYLIGHT 4
<br />EC
<br />ELECTRICAL CONTRACTOR
<br />iAGS
<br />JUNCTION BOX
<br />EM
<br />EMERGENCY
<br />GC
<br />GENERAL CONTRACTOR
<br />�A
<br />DETAIL DESIGNATION:
<br />� f COMMUNICATION
<br />1G -
<br />ISOLATED GROUND
<br />AA - DETAIL NUMBER
<br />JB
<br />JUNCTION BOX (J-BOX)
<br />BB
<br />BB - SHEET NUMBER
<br />TELEPHONE / DATA - RJ45 JACK W/ CAT5e
<br />JHA
<br />JURISDICTION HAVING AUTHORITY
<br />SHEET NOTE
<br />XX
<br />WIRES. CONDUIT WITH PULLWIRE TO ABOVE
<br />LL
<br />LANDLORD
<br />X
<br />ACCESSIBLE CEILING, CABLE IS BY OWNER.
<br />MLO
<br />MAIN LUG ONLY
<br />SECTION DESIGNATION:
<br />xx
<br />OVERHEAD AP CABLING
<br />MCB
<br />MAIN CIRCUIT BREAKER
<br />AA - DETAIL NUMBER
<br />OR
<br />ORANGE
<br />BB
<br />BB -SHEET NUMBER
<br />SW
<br />SHOW WINDOW
<br />SECURITY / COMMUNICATION
<br />TGC
<br />TENANT GENERAL CONTRACTOR
<br />KP
<br />ROUGH -IN FOR ADT KEY PAD @ 48"A.F.F.
<br />WH
<br />WHITE
<br />NEC
<br />NATIONAL ELECTRIC CODE
<br />T
<br />THERMOSTAT
<br />A. FIELD VERIFY ALL CONDITIONS.
<br />B. DESIGN DRAWINGS ARE SCHEMATIC. ONCE ONSITE GENERAL CONTRACTOR IS TO INSPECT EXISTING FIELD CONDITIONS. RFI SHALL BE SUBMITTED FOR ALL LABOR AND
<br />MATERIALS NECESSARY FOR FIELD MODIFICATIONS DUE TO EXISTING CONDITIONS.
<br />C. THE CONTRACTOR SHALL CONTACT THE ARCHITECT, ENGINEER OR OWNER ONCE ONSITE FOR INTERPRETATIONS AND CLARIFICATIONS OF THE DESIGN INTENT PRIOR TO
<br />COMMENCEMENT OF WORK.
<br />D. BIDDING CONTRACTORS SHALL HAVE A WORKING KNOWLEDGE OF LOCAL CODES AND ORDINANCES AND SHALL INCLUDE IN THEIR BIDS THE COSTS FOR ALL WORK INSTALLED
<br />IN STRICT ACCORDANCE WITH GOVERNING CODES, THE PLANS AND SPECIFICATIONS NOT WITHSTANDING. THE CONTRACTOR SHALL ALERT ARCHITECT, ENGINEER OR OWNER
<br />OF ANY APPARENT DISCREPANCIES BETWEEN GOVERNING CODES AND DESIGN INTENT.
<br />E, RFI SHALL BE SUBMITTED FOR ANY UNFORESEEN CONDITIONS THAT MAY EFFECT THE CONTRACTOR'S SCOPE OF WORK. MINOR VARIATIONS REQUIRED FOR ACCOMPLISHING
<br />THE INTENT OF THIS DESIGN SHALL BE INCLUDED IN THE RFI.
<br />F. PROVIDE ALL REQUIRED PERMITS AND INSPECTIONS. CONTRACTOR'S INSTALLATION SHALL CONFORM TO ALL LOCAL CODE REQUIREMENTS.
<br />G. VERIFY EXACT PLACEMENT OF ALL DEVICES SHOWN ON THE DOCUMENTS WITH ARCHITECTURAL, MECHANICAL AND PLUMBING DRAWINGS PRIOR TO FINAL PLACEMENT,
<br />H. BECOME FAMILIAR WITH REQUIRED DEMOLITION WORK PRIOR TO BIDDING AND START OF WORK. CONTRACTOR SHALL BE RESPONSIBLE TO PROVIDE ALL DEMOLITION AS
<br />REQUIRED FOR INSTALLATION OF NEW WORK.
<br />1. COORDINATE INSTALLATION OF ELECTRICAL WORK ABOVE THE CEILING TO PROVIDE THE GREATEST POSSIBLE CLEARANCE FOR INSTALLATION OF PLUMBING AND
<br />MECHANICAL, CONDUIT RUNS SHALL BE RUN THROUGH TRUSSES WHERE POSSIBLE.
<br />J. COORDINATE EXACT LOCATION OF DEVICES SERVING CASEWORK WITH FIXTURE CONTRACTOR.
<br />K. COORDINATE ALL LOW VOLTAGE CONDUIT AND ROUGH -IN REQUIREMENTS WITH LOW VOLTAGE CONTRACTORS.
<br />L. SWITCHBOARDS, PANELBOARDS, DISCONNECT SWITCHES, TRANSFORMERS AND CONTACTORS SHALL BE "LISTED" AND "IDENTIFIED" AS RATED FOR A MINIMUM OF 75°C
<br />CONDUCTOR TERMINATION.
<br />M. INCLUDE A COPPER EQUIPMENT GROUND CONDUCTOR IN ALL RACEWAYS. SIZE RACEWAYS AS NECESSARY TO COMPLY WITH NEC.
<br />N. ALL EMPTY CONDUITS SHALL BE PROVIDED WITH A PULL WIRE.
<br />O. ALL 20A BRANCH CIRCUITS BETWEEN 100' AND 150' IN LENGTH, #10 AWG COPPER WIRE SHALL BE USED. FOR ALL 20A BRANCH CIRCUITS OVER 150' IN LENGTH, #8 AWG COPPER
<br />WIRE SHALL BE USED.
<br />P. ALL 20A BRANCH CIRCUITS LESS THAN 100' iN LENGTH, SHALL BE #12 COPPER CONDUCTORS, #12 GND., 3/4" UNLESS NOTED OTHERWISE. TYPE MC CABLE MAY BE USED FOR
<br />BRANCH CIRCUITS ABOVE CEILINGS AND FOR FINAL FIXTURE CONNECTIONS. DO NOT USE TYPE MC EXPOSED UNLESS APPROVED BY LOCAL INSPECTOR AND JHA. ELECTRICAL
<br />CONTRACTOR TO VERIFY.
<br />Q. CIRCUITING INDICATED ON PLAN IS DIAGRAMMATIC FOR CLARITY. CIRCUITING SHALL BE "THRU-WIRING" WHERE/WHEN POSSIBLE. MULTI -CONNECTIONS TO A SINGLE LIGHT
<br />FIXTURE FOR FIELD CONDITIONS OR VOLTAGE DROP FACTORS MAY BE REQUIRED (FIXTURES SHALL BE MANUFACTURED TO ACCOMMODATE "THRU-WIRING"), AND RELATED
<br />COSTS SHALL BE INCLUDED IN BID.
<br />R. MAKE ALL FINAL ELECTRICAL CONNECTIONS AS REQUIRED FOR A COMPLETE AND OPERATING SYSTEM.
<br />S. WHERE DRYWALL CEILINGS ARE USED, CONTRACTOR SHALL ARRANGE CIRCUITING SO THAT JUNCTION/BOXES ACCESS PANELS ARE NOT INSTALLED IN THESE DRYWALL
<br />CEILING AREAS. (THE USE OF JUNCTION BOXES IN THESE DRYWALL CEILINGS IS NOT PERMITTED, ARRANGE CIRCUITS TO AVOID THIS SITUATION). FIELD COORDINATE WITH
<br />TENANT'S CONSTRUCTION MANAGER PRIOR TO ROUGH -IN TO AVOID CONFLICTS. JUNCTION BOXES MAY BE PLACED ABOVE LAY -IN CEILINGS.
<br />T. FIELD VERIFY EXACT LOCATION AND ELECTRICAL REQUIREMENTS OF ALL HVAC EQUIPMENT WITH MECHANICAL CONTRACTOR, PRIOR TO ORDERING RELATED ELECTRICAL
<br />EQUIPMENT.
<br />U. PLACEMENT OF ALL RECEPTACLES SHALL BE INTENTIONAL (I.E. CENTERED ON COLUMNS OR WALL FEATURES, OR TIGHT TO CORNER). IF RECEPTACLE IS NOT SHOWN IN A
<br />DESIRABLE LOCATION, FIELD VERIFY EXACT PLACEMENT OF RECEPTACLE WITH TENANT'S CONSTRUCTION MANAGER. PRIOR TO ROUGH -IN.
<br />V. PROVIDE ALL NECESSARY COMPONENTS TO MAKE A COMPLETE WORKING SYSTEM. VERIFY ROW LENGTHS, FEED POINT AND MOUNTING REQUIREMENTS S PRIOR TO ORDERING
<br />W. TAKE ADEQUATE CARE TO CORRECTLY LOCATE ALL ELECTRICAL S T UBOUTS, FLOOR BOXES, J-BOXES, TRACK, ETC. PRECISE LOCATIONS OF FLOOR OUTLETS AND J-BOXES IS
<br />VERY IMPORTANT.
<br />X. NO PIPING, DUCTS OR EQUIPMENT FOREIGN TO ELECTRICAL EQUIPMENT SHALL BE PERMITTED TO BE LOCATED WITHIN THE DEDICATED SPACE ABOVE THE ELECTRICAL
<br />EQUIPMENT. NEC 110.34(t).
<br />Y. FUSES SHALL BE PROVIDED WITH REJECTION TYPE FUSE HOLDERS. NEC 240.60B.
<br />Z. PROVIDE LOCK -ON DEVICE FOR CIRCUITS SUPPLYING EMERGENCY UNIT EQUIPMENT, NEC 700.18.
<br />AA. ATTAIN EXISTING BUILDING LOAD INFORMATION AND VERIFY AMPACITY AND DEMAND FOR BUILDING TO ENSURE THAT ALL LOADS (EXISTING AND NEW) DO NOT EXCEED THE
<br />AMPACITY OF THE SERVICE FEEDER(S) OR RATING OF THE SERVICE, PER NEC 220.40,
<br />AB. ALL DEDICATED RECEPTACLES SHALL BE RATED TO NOT LESS THAN THE RATING OF THE BRANCH CIRCUIT SERVING THE RECEPTACLE.
<br />AC, SUPPORT VERTICAL CABLE RUNS PER NEC 300.19.
<br />F
<br />I 12920 SE 38th STREET
<br />BELLEVUE, WA 98006
<br />vwvw.t-moblle.com
<br />i
<br />COPYRIGHT NOTICE:
<br />7 THESE DRAWINGS AND SPECIFICATIONS ARE COPYRIGHTED AND SUBJECT
<br />jj TO COPYRIGHT PROTECTION AS AN "ARCHITECTURAL WORK" UNDER SEC.
<br />102 OF THE COPYRIGHT ACT, 17 U.S.C. AS AMENDED JANUARY 2003, THE
<br />PROTECTION INCLUDES, WITHOUT LIMITATION, THE OVERALL FORM,
<br />ARRANGEMENT AND COMPOSITION OF SPACES AND ELEMENTS OF THE
<br />DESIGN, UNDER SUCH PROTECTION, UNAUTHORIZED USE OF THESE
<br />DRAWINGS AND SPECIFICATIONS MAY RESULT IN CESSATION OF
<br />CONSTRUCTION, BUILDING SEIZURE, AND/OR MONETARY LIABILITY.
<br />ARCHITECT:
<br />20:16 BjrpFL€ F:'1s"9CS
<br />kph ,""3+. x 3 [$#�
<br />Milancii'ufifburrg,,�411,004.5342
<br />5.. . vff'.: %"e U."�'sfFt R, c +`�:�
<br />��`i'C.6yli�..l 7L,�AF
<br />07/02/2021
<br />CONSULTING ENGINEER:
<br />DATE: 07/02/2021
<br />SCALE: AS NOTED
<br />DRAWN BY: JVH
<br />SAP NUMBER:
<br />CORPORATE REMODEL CD
<br />LDC
<br />SHEET TITLE:
<br />I
<br />SHEET NUMBER.
<br />E701