1. ALL DEMOLITION WORK SHALL BE 'PERFORMED WITH "DUE CARE AND <br />ENERGY CODE COMPLIANCE SHALL BE AS PER THE WASHINGTON STATE ENERGY <br />DILIGENCE" SO AS TO PREVENT THE ARBITRARY DESTRUCTION OF ADJACENT <br />CODE 2015. MINIMUM INSULATION (R) VALUES OR U-VALUES OF COMPONENTS SHALL <br />CONSTRUCTION DESIGNATED TO REMAIN. <br />BE AS FOLLOWS: <br />2. CARE SHALL ALSO BE TAKEN TO PREVENT THE INTERRUPTION OF <br />GLAZING, VERTICAL (U-VALUE) 0.22 MIN. <br />CONCEALED UTILITIES WHICH ARE TO REMAIN. <br />DOOR, ENTRANCE (U-VALUE) 0.22 MIN. <br />_ <br />CEILING INSULATION (ATTIC) R-49 MIN. <br />3. ANY UTILITIES DISCOVERED DURING THE DEMOLITION PROCESS WHICH <br />CEILING INSULATION (VAULTED) R-49 MIN. <br />- <br />WERE PREVIOUSLY UNIDENTIFIED SHALL BE REPORTED TO THE ARCHITECT <br />INSULATED WALLS R-21 MIN INT PLUS R-12 CI <br />BEFORE REMOVAL OR DISCONNECTION. <br />SLAB EDGE R-10 <br />n <br />FLOOR R-38 MIN. <br />C\ <br />4. REMOVE ALL EXISTING CONSTRUCTION AS DESIGNATED ON DEMOLITION <br />PLAN. <br />ENERGY CREDIT NOTES (3.5 CREDITS NEEDED): <br />1. OPTION 1c - EFFICIENT BUILDING ENVELOPE: PRESCRIPTIVE COMPLIANCE IS BASED <br />5. PATCH EXISTING CONSTRUCTION TO REMAIN TO MATCH EXISTING ADJACENT <br />ON TABLE R402.1.1 WITH THE FOLLOWING MODIFICATIONS: VERTICAL FENESTRATION <br />CONSTRUCTION AND FINISHES UNLESS NOTED OTHERWISE. <br />U =0.22, (2.0 CREDITS) <br />6. WHERE EXISTING DOORS AND WINDOWS ARE DESIGNATED TO BE REMOVED, <br />2. OPTION 3d- HIGH EFFICIENCY HVAC EQUIPMENT: DUCTLESS SPLIT SYSTEM HEAT <br />PATCH OPENING WITH CONSTRUCTION TO MATCH EXISTING ADJACENT <br />PUMPS, ZONAL CONTROL: IN HOMES WHERE THE PRIMARY SPACE HEATING SYSTEM IS <br />CONSTRUCTION UNLESS NOTED OTHERWISE. <br />ZONAL ELECTRIC HEATING, A DUCTLESS HEAT PUMP SYSTEM SHALL BE INSTALLED <br />r <br />AND PROVID HEATING TO THE LARGEST ZONE OF THE HOUSING UNIT (1.0 CREDITS) <br />7. ALL EQUIPMENT SUCH AS PLUMBING FIXTURES, ELECTRICAL FIXTURES AND <br />EQUIPMENT, MECHANICAL EQUIPMENT, AIR CONDITIONING UNITS, ETC., TO BE <br />3.OPTION 5a- EFFICIENT WATER HEATING: ALL SHOWERHEAD AND KITCHEN SINK <br />REMOVED SHALL BE TURNED OVER TO THE OWNER OR STORED AS DIRECTED <br />FAUCETS INSTALLED IN THE HOUSE SHALL BE RATED AT 1.75 GPM OR LESS. ALL <br />BY THE OWNER. <br />OTHER LAVATORY FAUCETS SHALL BE RATED AT 1.0 GPM OR LESS.(0.5 CREDITS) <br />FLOOR PLAN NOTES <br />FDN. VENT CALCS <br />VENTING REQ. = 1/150 SF <br />1. ALL DIMENSIONS ARE FROM FACE -OF -STUD TO FACE -OF -STUD, AND FACE -OF -BLOCK <br />TO FACE -OF -BLOCK (U.N.O.) <br />NEW CRAWL SPACE AREA 1 SF = 235 SF/150 SF <br />REQUIRED SF OF VENTING = 1.5 SF <br />2. ALL LUMBER TO BE DOUGLAS FIIR#2 OR BETTER (U.N.O.) <br />FOUNDATION VENTS - 2 MIN @ 1.00 =2 SF <br />TOTAL VENTING PROVIDED = 2 SF> 1.5 SF, OKAY <br />3. ALL FINISH MATER9ALS NOT SPECIFIED TO BE COORDINATED WITH OWNER AND/OR <br />ARCHITECT. <br />NEW CRAWL SPACE AREA 2 SF = 83 SF/150 SF <br />c <br />REQUIRED SF OF VENTING SF <br />es <br />4. PROVIDE SOLID BLOCKING BEHIND ALL FIXTURES AND WALL MOUNTED <br />FOUNDATION VENTTSS1 -1MIN. @ 1.00 = 1 SF <br />r <br />ACCESSORIES. <br />TOTAL VENTING PROVIDED = 1 SF> 0.5 SF, OKAY <br />5. ANY WALLS THAT ARE MODIFIED, REPLACE GYP.BD. W/ 5/8" TYPE 'X GYP.BD. <br />NOTE: <br />1. PROVIDE 6 MIL VAPOR RETARDER OVER ALL GROUND SURFACES IN UNDER <br />6. WHERE (E) STUD WIDTHS VARY FROM NEW WALL TYPE STUD WIDTH, MATCH (E) <br />2. PROVIDE 24" W ACCESS TO EXIST CRAWL SPACE FROM NEW <br />STUD WIDTH. <br />FLOOR AREA. <br />2. PLACE VENTS TO PROVIDE CROSS VENTILATION. <br />7. PROVIDE WALL &FLOOR STOPS AT DOORS AS REQUIRED. <br />3. PROVIDE 1$"x24" MIN. CRAWLSPACE ACCESS. <br />4. ADD ADDITIONAL VENTEPLACE ANYVENT COVERED BY ADDITION <br />8. (E) WALLS REQUIRING OPENINGS TO BE INFILLED SHALL MATCH (E) CONSTRUCTION <br />& FIRE PRATING. <br />9. OWNER MAY OPT TO PHASE UPPER LEVEL FINISHES SEPARATELY IN ORDER TO <br />WALL LEGE�.ND <br />OCCUPY THE LOWER LEVEL. iN THIS CASE, THE UPPER LEVEL WILL REMAIN <br />UNOCCUPIED AT THE COMPLETION OF PHASE 1 AND THE UPPER LEVEL FINISHES WILL <br />6" EXTERIOR STUDWALL - 2X6 <br />BE PHASE 2. <br />@16"OC W/SIDING 0/1-1/2" ZIP <br />SYSTEM R-SHEATHING (R-6.6) <br />O/ HOUSE WRAP O/ PLYW'D ON <br />EXT. FACE, 1/2" GYP. BD. 0/ <br />VAPOR BARRIER AT ONSIDE <br />FACE AND R-21 BATTS MIN. <br />DEMO WALL LEGEND <br />BTWN, U.N.O. <br />4" INTERIOR STUDWALL - 2X4@ <br />16"OC W/ 1/2" GYP. BD. EA. SIDE <br />- - - <br />AND SOUND BATT INSUL. BTWN. <br />- - - DEMOLISHED U.N.O. <br />USE 2X6 WHERE NEC. FOR <br />PLUMBING U.N.O. <br />EXISTING TO REMAIN U.N.O. <br />-----.--- EXISTING WALLS TO REMAIN <br />-A <br />U.N.O. <br />6" EXTERIOR STUDWALL - 2X6@ <br />16"OC - 1 HR. FIRE RATED (SEE <br />DETAIL 1 ON P. A9.2) <br />REMOVESHADED AREA. <br />AND REPLACE EXIST. <br />FOUNDATION <br />®®-EL_- _ <br />I- <br />I <br />I II <br />I <br />11' <br />(E) BATH <br />I I II <br />I� <br />II <br />() ED . 2 <br />; <br />I I I <br />L_u_jJI <br />(E) BEDRIM. 1 I I <br />II <br />II <br />I l f <br />I <br />e <br />II, <br />SI- <br />- <br />I <br />REMOVE EXIST. WALLS <br />-- <br />I I <br />PER. LEGEND <br />I�I <br />(E) DINING <br />II\ rd <br />(E) ENTRY <br />I' <br />III <br />(E) KITCHEN --� <br />(E) UVING RM. <br />1 II+ <br />11 <br />I�i vII <br />I' <br />-__--Fr---ii� I <br />1 j_ 1 I <br />3 <br />C�,7,,3sea 'r <br />1/4" = 1'-01° <br />.0 <br />Al <br />EO <br />cis <br />rm,\NEW UPPER LEVEL CLAN <br />1/4" = 11-01° <br />NEW ADDITION, TXE. <br />l 12'-6" <br />M 0-1 <br />Q <br />uO <br />o <br />(Ji gp <br />p <br />-� -�co <br />6' �_ 0°' z <br />DECK <br />LL <br />x <br />CD , `i _. <br />1/4" = 11-0" <br />6'-0" CL <br />If <br />(OPTI NAL) <br />(N)5°0" 4'0" SL <br />1 <br />10' - 6„ <br />on <br />6°-3" 4'-1" <br />0 <br />z � <br />z co <br />z <br />PANTRY CD <br />e\1 <br />(N)2'0" 4'0" SFI <br />iOf16' - 0" <br />10'-8" 2'-8" 5"-4" 2'-0" <br />9'-4" � r <br />4.1 � 9'-4" ot <br />5'-8" cE CL 5'-8" <br />- c <br />- 10'� El - 10" <br />)2,0„ 4'0" SH (N)4'0" 1 °6" FX (N)2'0'X4'0" H (N)4°0"X1'0" FX (N)4'0" 1 6' FX <br />( }2'®" 4'®" SH , (N)2'0' X4'0°' S <br />717 <br />5 <br />CD <br />EEDRM.2 ( a <br />(E) <br />(E BATH 1 (E) BED M. 1 - 0 <br />NEW 66" DIA PREMFD. bo <br />METAL IRC COMPLIANT X <br />STAIR; STAIR <br />MANUFACTURER TO <br />_ w <br />PROVIDE SHOP <br />DRAWINGSo"�'� <br />(N)2'6"X6'8 (E)2 6"X6 8 <br />5'0"X6'8" POCKET <br />vvv a"k-- <br />10iNI PA/ I N Y <br />vvv kn %% PANTRY <br />� SIT 1C � Cfl <br />\\ CCS <br />4L <br />6'-4" 6-4" 5'-8" <br />(E) KITCHEN <br />12°-7" 0 <br />17' - 1" <br />0 0 <br />01. <br />(N)4'0'fX4'0" SL <br />in ME <br />I, Ism <br />DUCTLESS <br />SPLIT HVAC <br />SYSTEM <br />(N)4" 41®II �I <br />20'-5" <br />m <br />(N)4,0"4'0" SL <br />4'-5" <br />w <br />OF <br />,ter <br />n <br />r <br />U <br />0 <br />m <br />'~ <br />r <br />w <br />H 0 <br />�. <br />A <br />Iu2� <br />m <br />Lu a W <br />®® <br />^ u pal 9 <br />CD <br />� <br />Iju� <br />A qn <br />Lu ° <br />H In <br />co <br />® <br />LU <br />{' <br />A <br />A <br />®co <br />�i <br />a� <br />m <br />® <br />� <br />Ld I <br />z Of <br />LLJ <br />L) <br />Xv-'� <br />:�E`2 <br />0ii� <br />Q <br />Lu <br />< <br />2 <br />u I� <br />C/� <br />M0 <br />�[if <br />I� <br />Lu <br />�® <br />v= <br />`A4.1 <br />00 <br />e <br />CL <br />® Sf <br />c <br />0 <br />a <br />, ,> <br />�CD <br />�cr� <br />0 <br />�U <br />LU LU <br />cra y <br />0 0 <br />z� <br />0 <br />c <br />® <br />r <br />�= <br />a�Lu <br />D <br />aLu0 <br />_U) <br />�ZD <br />Q® <br />= LL¢ <br />U) <br />0 <br />®< <br />c� D <br />®� <br />0-LL <br />a- <br />ca <br />Q <br />Z <br />0_® <br />0v <br />® w <br />0- <br />0ui <br />couj <br />I <br />D� <br />D� <br />W >- <br />Q <br /><x <br />Of <br />� 0 <br />0Q <br />®0 <br />v LLB <br />�of <br />k CONDENSER <br />SCREEN AS <br />NECESSARY <br />® <br />Lu <br />co <br />I� <br />® <br />u <br />00 <br />Ltd <br />. , pk 1 S ..P �� 4... 1"��'�.1 li <br />EE <br />l� <br />a� <br />� <br />z <br />CIO <br />