Laserfiche WebLink
Permit #: B2109-037 <br />Site Address: 2509 RAINIER AVE <br />Owner: REISENBICHLER MICHAELJACOB <br />u k­.� r <br />ENGI1" F� Er ICI N G <br />LC <br />Structural Calculations for: <br />Reisenbichler Residence Retrofit <br />2509 Rainier Ave <br />Everett, WA 98201-3125 <br />Client: A-FFIX, LLC <br />Code:2018 International Building Code <br />Note: This design is limited to seismic retrofit recommendations and meets <br />the intent of the project impact retrofit standards. <br />September 6, 2021 <br />Buker Engineering, Ilc <br />PO Box 28531 <br />Seattle, WA 98118-8531 <br />Ph: 206.310.3559 <br />Parcel Number 00562656900400 (R01) <br />Leggal: Ruckers 3rd Plat Blk 569 <br />D-00 - S1/2 of Lot 4 & all <br />of Lot 5 <br />OTC Hazards by Location <br />L1 Reisenbichler Residence Retrofit <br />ienanu <br />App.Date: 9/13/2021 <br />Proposed Use: COMMERCIAL ALTERATIONS <br />Description: VOLUNTARY SEISMIC RETROFIT - SINGLE <br />FAMILY RESIDENCE <br />Reviewed By: Date: I <br />�)ffice Set Job Site Set Fire/Pla ning et <br />Seismic Analysis (ASCE 7-16) <br />Search Information <br />Oak Harbor <br />Address: <br />2509 Rainier Ave, Everett, WA 98201, USA <br />SS = <br />1.224 <br />1 Fa = <br />1.20 <br />1 S,, = <br />11.4688 <br />1 <br />SD, = <br />10.98 <br />Coordinates: <br />47.9840814,-122.1981959 Sequi`n <br />$7 ft M ille <br />S: = <br />0.44 <br />F„ = <br />1.80 <br />Smt = <br />0.783 <br />Soy = <br />0.52 <br />Elevation: <br />87 ft <br />Whidbey Ev ett <br />� Island o <br />101 <br />Site Class = <br />D <br />L`rrJ <br />Use <br />Mean Roof Height = <br />20 <br />ft <br />Timestamp: <br />Hazard Type: <br />2021-08-24T22:07:24.118Z <br />Seismic <br />T = <br />0.19 <br />sec <br />SEP <br />R = <br />6.5 <br />02 <br />Redmond <br />I = <br />1.0 <br />C7, <br />Reference <br />ASCE7-16 <br />Go <br />gle Seattle ° Ma data o2021 Goo le <br />p g <br />rho = <br />1.0 <br />Document: <br />Cs = <br />0.151 <br />aTltl S4rV'C T <br />Risk Category: <br />11 <br />W = <br />132.73 <br />K <br />W=0 stories)(1309 <br />ft^2)(25 psf) <br />Site Class: <br />D-default <br />Ilowable Base Shear V = 3.45 1K <br />32.73 K <br />Basic Parameters <br />Wall V (K) Lw (ft) V (plf) <br />Nailing A.B./A35 ** <br />APPROVED <br />Uplift (#) <br />Holdown* <br />North <br />1.73 <br />20.0 <br />86 <br />0 <br />Not Reqd. <br />4 ox. <br />32/16 <br />Office of Community, Planning & Economic Di <br />Name <br />value <br />Description <br />South <br />1.73 <br />35.0 <br />49 <br />0 <br />Not Reqd. <br />4 o.c. <br />32/16 <br />PLANNING DEPARTMENT <br />SS <br />1.224 <br />MCER ground motion (period=0.2s) <br />East <br />1.73 <br />18.0 <br />96 <br />0 <br />Not Reqd. <br />4 o.c. <br />32/16 <br />West <br />1.73 <br />18.0 <br />96 <br />192 <br />Not Reqd. 1 <br />4 o.c. <br />32/1T71NAME:"✓ <br />DATE: , <br />SI <br />0.435 <br />MCER ground motion (period=1.0s) <br />* Holdown not required where wall <br />length >= 2*wall height <br />** At full height foundation walls, provide FRFP or URFP @ 4'-0" o.c. <br />SMS <br />1.469 <br />Site -modified spectral acceleration value <br />SMI <br />* null <br />Site -modified spectral acceleration value <br />CITY OF EVERETT <br />REVIEWED FOR PERMIT <br />SDS <br />0.979 <br />Numeric seismic design value at 0.2s SA <br />SDI <br />* null <br />Numeric seismic design value at 1.0s SA <br />* See Section <br />11.4.8 <br />THESE DOCUMENTS HAVE NOT BEEN <br />APPROVED FOR THE ISSUANCE OF <br />PUBLIC WORDS, MECHANICAL, FIRE <br />SUPPRESSION, ELECTRICAL 911 <br />PLUMBING 109RMITS, <br />bulcr <br />ENGINEERING", <br />The Following Apply Unless Noted Otherwise on the Drawings <br />Criteria Geotechnical Wood <br />1. ALL MATERIALS, WORKMANSHIP, DESIGN, AND CONSTRUCTION SHALL CONFORM TO THE DRAWINGS, 1. FOUNDATION NOTES: ALLOWABLE SOIL PRESSURE AND LATERAL EARTH PRESSURE ARE ASSUMED AND 1. FRAMING LUMBER SHALL BE KILN DRIED OR MC-19, AND GRADED AND MARKED IN CONFORMANCE <br />SPECIFICATIONS, AND THE 2018 INTERNATIONAL BUILDING CODE. THIS STRUCTURE DOES NOT THEREFORE MUST BE VERIFIED BY A QUALIFIED SOILS ENGINEER OR APPROVED BY THE BUILDING WITH W.C.L.B. STANDARD GRADING RULES FOR WEST COAST LUMBER NO.17. FURNISH TO THE <br />CONFORM TO PRESENT EARTHQUAKE CODE REQUIREMENTS. IT HAS BEEN ANALYZED AND OFFICIAL. IF SOILS ARE FOUND TO BE OTHER THAN ASSUMED, NOTIFY THE STRUCTURAL ENGINEER FOLLOWING MINIMUM STANDARDS: <br />REINFORCED FOR MINIMUM MAINTENANCE AND IS WITHIN THE CURRENT STANDARD OF PRACTICE FOR POSSIBLE FOUNDATION REDESIGN. JOISTS (2X & 3X MEMBERS) DOUGLAS FIR -LARCH NO. 2 <br />FOR THE RENOVATION OF EXISTING BUILDINGS OF THIS AGE AND TYPE OF CONSTRUCTION. NEW FOOTINGS SHALL BEAR ON FIRM, UNDISTURBED EARTH AT LEAST 18" BELOW ADJACENT AND BEAMS: MINIMUM BASE VALUE, Fb=1000 PSI <br />2. DESIGN LOAD CRITERIA FINISHED GRADE. UNLESS OTHERWISE NOTED, FOOTINGS SHALL BE CENTERED BELOW COLUMNS OR <br />ROOF SNOW LOAD 25 PSF WALLS ABOVE. POSTS: (4X MEMBERS) DOUGLAS FIR -LARCH NO. 2 <br />FLOOR LIVE LOAD (RESIDENTIAL) 40 PSF BACKFILL BEHIND ALL RETAINING WALLS WITH FREE DRAINING, GRANULAR FILL AND PROVIDE FOR MINIMUM BASE VALUE, Fc=1350 PSI <br />RISK CATEGORY 11 SUBSURFACE DRAINAGE. <br />ALLOWABLE SOIL PRESSURE 2000 PSF STUDS, PLATES & MISC. FRAMING: DOUGLAS-FIR-LARCH OR HEM -FIR NO. 2 <br />EARTHQUAKE LATERAL EARTH PRESSURE (RESTRAINED/UNRESTRAINED) 55 PCF/35 PCF 2. PLYWOOD SHEATHING SHALL BE GRADE C-D, EXTERIOR GLUE OR STRUCTURAL II, EXTERIOR GLUE IN <br />ANALYSIS PROCEDURE: EQUIVALENT LATERAL COEFICIENT OF FRICTION CONFORMANCE WITH DOC PS 1. ORIENTED STRAND BOARD OF EQUIVALENT THICKNESS, EXPOSURE <br />FORCE PROCEDURE (FACTOR OF SAFETY OF 1.5 INCLUDED) 0.3 RATING AND PANEL INDEX MAY BE USED IN LIEU OF PLYWOOD. <br />LATERAL SYSTEM: LIGHT FRAMED SHEAR WALLS <br />BASE SHEAR (ALLOWABLE) SEE CALCULATIONS <br />SITE CRITERIA SITE CLASS=D, Ss=1.224, Sds=0.98, <br />S1=0.435, SD1=0.52, Cs=0.151 <br />SDC D, le=1.0, R=6.5 <br />SEE PLANS FOR ADDITIONAL LOADING CRITERIA <br />3. CONTRACTOR SHALL VERIFY ALL EXISTING DIMENSIONS AND CONDITIONS FOR COMPATIBILITY AND <br />SHALL NOTIFY ENGINEER OF ANY DISCREPENCIES PRIOR TO CONSTRUCTION. <br />4. CONTRACTOR SHALL PROVIDE TEMPORARY BRACING FOR THE STRUCTURE AND STRUCTURAL <br />COMPONENTS UNTIL ALL FINAL CONNECTIONS HAVE BEEN COMPLETED IN ACCORDANCE WITH THE <br />PLANS. <br />5. CONTRACTOR SHALL BE RESPONSIBLE FOR ALL SAFETY PRECAUTIONS AND THE METHODS, <br />TECHNIQUES, SEQUENCES OR PROCEDURES, REQUIRED TO PERFORM THE CONTRACTORS WORK. THE <br />STRUCTURAL ENGINEER HAS NO OVERALL SUPERVISORY AUTHORITY OR ACTUAL AND/OR DIRECT <br />RESPONSIBILITY FOR THE SPECIFIC WORKING CONDITIONS AT THE SITE AND/OR FOR ANY HAZARDS <br />RESULTING FROM THE ACTIONS OF ANY TRADE CONTRACTOR. THE STRUCTURAL ENGINEER HAS NO <br />DUTY TO INSPECT, SUPERVISE, NOTE, CORRECT, OR REPORT ANY HEALTH OR SAFETY DEFICIENCIES TO <br />THE OWNER, CONTRACTORS, OR OTHER ENTITIES OR PERSONS AT THE PROJECT SITE. <br />6. CONTRACTOR -INITIATED CHANGES SHALL BE SUBMITTED IN WRITING TO THE STRUCTURAL ENGINEER <br />FOR APPROVAL PRIOR TO FABRICATION OR CONSTRUCTION. <br />7. DRAWINGS INDICATE GENERAL AND TYPICAL DETAILS OF CONSTRUCTION. WHERE CONDITIONS ARE <br />NOT SPECIFICALLY INDICATED BUT ARE OF SIMILAR CHARACTER TO DETAILS SHOWN, SIMILAR DETAILS <br />OF CONSTRUCTION SHALL BE USED, SUBJECT TO REVIEW AND APPROVAL BY THE STRUCTURAL <br />ENGINEER. <br />Renovation <br />1. DEMOLITION: CONTRACTOR SHALL VERIFY ALL EXISTING CONDITIONS BEFORE COMMENCING ANY <br />DEMOLITION. SHORING SHALL BE INSTALLED TO SUPPORT EXISTING CONSTRUCTION AS REQUIRED <br />AND IN A MANNER SUITABLE TO THE WORK SEQUENCES. DEMOLITION DEBRIS SHALL NOT BE <br />ALLOWED TO DAMAGE OR OVERLOAD THE EXISTING STRUCTURE, LIMIT CONSTRUCTION LOADING <br />(INCLUDING DEMOLITION DEBRIS) ON EXISTING FLOOR SYSTEMS TO 40 PSF. <br />Anchorage <br />1. EXPANSION BOLTS INTO CONCRETE AND CONCRETE MASONRY UNITS SHALL BE STRONG -BOLT 2 <br />ANCHORS AS MANUFACTURED BY THE SIMPSON STRONG TIE COMPANY AND INSTALLED IN STRICT <br />CONFORMANCE TO [CC -ES REPORT NUMBER ESR-3037, INCLUDING MINIMUM EMBEDMENT <br />REQUIREMENTS. BOLTS INTO CONCRETE MASONRY OR BRICK MASONRY UNITS SHALL BE INTO FULLY <br />GROUTED CELLS. SPECIAL INSPECTION IS REQUIRED FOR ALL EXPANSION BOLT INSTALLATION. <br />2. EPDXY -GROUTED ITEMS (THREADED RODS OR REINFORCING BAR) SPECIFIED ON THE DRAWINGS <br />SHALL BE INSTALLED USING "SET-3G" HIGH STRENGTH EPDXY AS MANUFACTURED BY THE SIMPSON <br />STRONG TIE COMPANY. INSTALL IN STRICT ACCORDANCE WITH ICC-ES REPORT NO. ESR-4057. SPECIAL <br />INSPECTION OF INSTALLATION IS REQUIRED. RODS SHALL BE ASTM A-36 UNLESS OTHERWISE NOTED. <br />A. WALL SHEATHING SHALL BE 1/2" (NOMINAL) WITH SPAN RATING 24/0. <br />B. REFER TO WOOD FRAMING NOTES BELOW FOR TYPICAL NAILING REQUIREMENTS. <br />3. ALL WOOD IN DIRECT CONTACT WITH CONCRETE OR MASONRY SHALL BE PRESSURE -TREATED WITH <br />AN APPROVED PRESERVATIVE OR (2) LAYERS OF ASPHALT IMPREGNATED BUILDING PAPER SHALL BE <br />PROVIDED BETWEEN UNTREATED WOOD AND CONCRETE OR MASONRY. <br />4. PRESSURE TREATED WOOD SHALL BE TREATED PER AWPA STANDARD. PRESSURE TREATED WOOD FOR <br />ABOVE GROUND USE SHALL BE TREATED TO A RENTION OF 0.25 PCF. WOOD IN CONTINUOUS <br />CONTACT WITH FRESH WATER OR SOIL SHALL BE TREATED TO A RETENTION OF 0.40 PCF. WOOD FOR <br />USE IN PERMANENT FOUNDATIONS SHALL BE TREATED TO A RETENTION OF 0.60 PCF. SODIUM BORATE <br />(SBX) TREATED WOOD SHALL NOT BE USED WHERE EXPOSED TO WEATHER. FASTENERS AND TIMBER <br />CONNECTORS IN DIRECT CONTACT WITH ACQ-A, CBA-A, CA-B, OR SBX TREATED WOOD SHALL BE G185 <br />OR A185 HOT DIPPED OR CONTINUOUS HOT -GALVANIZED PER ASTM A653. FASTENERS AND TIMBER <br />CONNECTORS IN DIRECT CONTACT WITH ACZA TREATED WOOD SHALL BE TYPE 304 OR 316 STAINLESS <br />STEEL. <br />5. TIMBER CONNECTORS CALLED OUT BY LETTERS AND NUMBERS SHALL BE "STRONG -TIE' BY SIMPSON <br />COMPANY, AS SPECIFIED IN THEIR CATALOG NUMBER C-C-2017. <br />ALL SHIMS SHALL BE SEASONED AND DRIED AND THE SAME GRADE (MINIMUM) AS MEMBERS <br />CONNECTED. <br />6. WOOD FASTENERS <br />A. NAIL SIZES SPECIFIED ON DRAWINGS ARE BASED ON THE FOLLOWING SPECIFICATIONS: <br />SIZE LENGTH DIAMETER <br />8d 2-1/2" 0.131" <br />10d 3" 0.148" <br />16d BOX 3-1/2" 0.135" <br />NAILS - PLYWOOD (APA RATED SHEATHING) FASTENERS TO FRAMING SHALL BE DRIVEN FLUSH TO <br />FACE OF SHEATHING WITH NO COUNTERSINKING PERMITTED. <br />B. ALL BOLTS IN WOOD MEMBERS SHALL CONFORM TO ASTM A307, PROVIDE WASHERS UNDER THE <br />HEADS AND NUTS OF ALL BOLTS AND LAG BOLTS BEARING ON WOOD. INSTALLATION OF LAG <br />BOLTS SHALL CONFORM TO THE NATIONAL DESIGN SPECIFICATION FOR WOOD CONSTRUCTION <br />(2005 EDITION) WITH A LEAD BORE HOLE OF 60 TO 70 PERCENT OF THE SHANK DIAMETER. LEAD <br />HOLES ARE NOT REQUIRED FOR 3/8" AND SMALLER LAG SCREWS. <br />7. WOOD FRAMING NOTES --THE FOLLOWING APPLY UNLESS OTHERWISE SHOWN ON THE PLANS: <br />A. ALL WOOD FRAMING DETAILS NOT SHOWN OTHERWISE SHALL BE CONSTRUCTED TO THE <br />MINIMUM STANDARDS OF THE INTERNATIONAL BUILDING CODE. MINIMUM NAILING, UNLESS <br />OTHERWISE NOTED, SHALL CONFORM TO TABLE 2304.9.1. COORDINATE THE SIZE AND LOCATION <br />OF ALL OPENINGS WITH MECHANICALAND ARCHITECTURAL DRAWINGS. <br />B. AT ANCHOR BOLTS CONNECTING WOOD SILL PLATES TO CONCRETE FOUNDATION WALLS, <br />PROVIDE 3" x 3" x y" PLATE WASHERS. <br />bu I c4m r <br />ENGINEERING <br />LLC <br />4303 Stone Way N <br />Seattle, WA 98103 <br />206.258.6333 <br />$ r RSH�UtI�, <br />A 61 44090 0$ <br />ONAL <br />O <br />L. <br />ent 4_i <br />W <br />C <br />OD <br />CnCV <br />LO <br />r <br />CO <br />>1 <br />o <br />Q T- <br />L <br />CZ <br />Q <br />N 0 <br />E M <br />O <br />CAI <br />W <br />U <br />(3) <br />No. Date Issue <br />2021 Permit <br />For DPD use <br />Sheet Contents <br />General Notes <br />and Calculations <br />Sheet No. <br />