fi <br /> * 1 I 2 I 3 I 4 I 5 <br /> M <br /> LOAD SCHEDULE: <br /> PANEL:"A" VOLTAGE:240/120V MAIN:200A,2P,CB WIRING: 1PH,3-WIRE <br /> TO UTILITY SERVICE ENCL:NEMA 1 MOUNTING:FLUSH Service Conductor:3-#2/0AWG,Type SE AIC:10,000 <br /> OVERHEAD CONNECTION <br /> D -'-----------PROVIDE <br /> LOAD <br /> �ROVIDE SERVICE SIZE DESCRIPTION (VA) AMPS WIRE SIZE NO.CKT A PHASE CKT LOAD <br /> B NO. WIRE SIZE AMPS (VA) DESCRIPTION BKRSIZE D <br /> ENTRANCE CAP <br /> 15A-1P Lighting,Living/Dining 978 8.15 3-#12-AWG 1 2418 2 3-#12-AWG 12.00 1440 Lighting,Kitchen/Family Room 15A-1P <br /> UTILITY KWHR-METER / / 3' 15A-1P Lighting,Basement 900 7.50 3-#12-AWG 3 2232 4 3-#12-AWG 11.10 1332 Lighting 2nd Flr,Master's 20A-1P <br /> (LOCATED AT THE NORTH-WEST �(SEA ELBOARD 15A-1P Cony.Outlet,Living Rm 1440 12.00 3-#12-AWG 5 2592 6 3-#12-AWG 9.60 1152 Lighting 2nd Flr,BR 1&2 15A-1P <br /> EXTERIOR CORNER OF / (SEE POWER PLAN 20A-1P Cony.Outlet,Master&BR1 1800 15.00 3-#12-AWG 7 3600 8 3-#12-AWG 15.00 1800 Cony.Outlet,Office/BR2 20A-1P <br /> THE BUILDING) FOR LOCATION) <br /> PROVIDE 2"0 RIGID GALVANIZE 0 20A-1P Cony.Outlet,Basement 2160 18.00 3-#12-AWG 9 3420 10 3-#12-AWG 10.50 1260 Cony.Outlet,Dining 20A-1P <br /> CODUIT AND FITTINGS 20A-1P Cony.Outlet,Kitchen 1500 12.50 3-#12-AWG 11 3000 12 3-#12-AWG 12.50 1500 Bathroom Circuit(Cony.Outlet) 20A-1P <br /> ROUTE CONDUIT BELO 15A-1P Waste Disposal 1000 8.33 3-#12-AWG 13 2200 14 3-#12-AWG 10.00 1200 Dishwasher 15A-1P <br /> THE FIRST FLOOR LEVEL. 15A-1P Microwave 1200 10.00 3-#12-AWG 15 2700 16 3-#12-AWG 12.50 1500 Refrigerator 15A-1P - <br /> PROVIDE #4AWG TW WIRE 15A-1P Gas Furnish 1000 8.33 3-#12-AWG 17 1000 18 Spare 15A-1P <br /> FOR GROUNDING ELECTRODE 15A-1P Spare 19 1500 20 3-#12-AWG 12.50 1500 Laundry(WM) 20A-1P <br /> CONDUCTOR IN 3/4"0 CONDUIT 21 8000 22 A/C Provision(Disconnect <br /> 40A-2P Cooking Range 6000 25.00 4-#8-AWG 3-#8-AWG 41.67 10000 50-2P <br /> VERIFY EXISTING GROUND ROD, 23 8000 24 Switch) <br /> OTHERWISE PROVIDE i/ 25 5000 26 <br /> 3/4"0x1O'GROUND ROD j 40A-2P Clothes Dryer 5000 20.83 4-#10 AWG 27 5000 28 3#10 AWG 20.83 5000 Water Heater 30-2P <br /> 20A-1P A/C Provision for Master's BR 1800 15.00 3-#12-AWG 29 1800 30 3-#12-AWG 1.25 150 Smoke Detectors 15A-1P <br /> C 15A-1P Spare 31 1440 32 3-#12-AWG 12.00 1440 Cony.Outlet,Family Room 15A-1P C <br /> Space 33 34 Space <br /> Connected kVA: 26.43 27.47 <br /> F,. Connected Amps: 220.25 228.93 <br /> Total Calculated Demand Load: 23.99 kVA <br /> Total Calculated Service: 99.97 Amps <br /> Note:Provide a 200Amp,2P,240V MCB -Use 3-#2/0 AWG Copper,Type SE Wires for Service Conductors <br /> -Use 1-#4 AWG Copper TW Wires for Grounding Electrode Conductor <br /> SERVICE CALCULATION: <br /> General Lighting Area 2660 SQ.FT. <br /> General Lighting Load 7980 VA <br /> Small Appliance Load 3000 VA <br /> B Laundry 1500 VA B <br /> 6000 VA <br /> SERVICE CONNECTION DETAIL Wa eerHeater 5000 VA <br /> SCALE NTS Dishwasher 1200 VA <br /> Clothes Dryer 5000 VA <br /> Microwave 1500 VA <br /> Waste Diposal 1000 VA <br /> NOTES: Gas Furnish 1000 VA <br /> A/C Units 11800 VA <br /> - 1. RELATED GENERAL NOTES ON SHEET E-001 APPLIES TO 44,980 VA - <br /> THIS SHEET. <br /> 2. DEMOLISH ALL EXISTING SERVICE ENTRANCE CONDUIT First 10K 10,000 VA <br /> INCLUDING THE EXISTING METER BASE. COORDINATE WITH <br /> THE UTILITY COMPANY AS TO METERING REQUIREMENT Remainder @ 40% 13,992 VA <br /> AND PERMANENT POWER CONNECTION. <br /> TOTAL DEMAND LOAD 23,992.00 VA <br /> Calculated Demand For Service 99.97 Amps <br /> A A <br /> PREPARED BY: B.SE(0 <br /> PROJECT TITLE : OWNER: REVISIONS DRAWING NO. <br /> ,. 4EP el*Ase, 9, STRUCTURAL&ELECTRICAL S.M DESCRIPTION DATE APPROVED <br /> TRIPLE V CONSULTANTS RENOVATION <br /> ." (Bremerton and Whidbey Island,WA) MR. SAI SHANKAR E-201 <br /> v Triplevconsultants@msn.com 1 SHEET TITLE : 2222 BAKER AVENUE <br /> �.,e st, EVERETT,WA 98201 SCALE: AS INDICATED <br /> ELECTRICAL- <br /> 360 632-2913 4ONAL SECTIONS I LOAD SCHEDULE - SHEE_L21 OF 21 <br /> I EXPIRES <br /> 1 I 2 I 3 I 4 I 5 ally' <br />
The URL can be used to link to this page
Your browser does not support the video tag.