• <br /> From: Steve Goforth <br /> To: Pete Helton <br /> Cc: Kurtis Brown;Tim Markham;Thad Newport <br /> Subject: 215 Dorn A,B,C,D <br /> Date: Tuesday,August 3,2021 2:58:05 PM <br /> Attachments: jmaae001.ong <br /> image002.onq <br /> Pete <br /> I am going to approve the permits for the system with the following corrections. <br /> 1. All systems will need a 1" meter as per City of Everett Construction Standard 524 <br /> 2. The system will be tied to the master toilet as a deterrent to shutting off the sprinkler system <br /> a. I will need as-builts showing this in the plans. <br /> 3. I will require an outside bell to activate on waterflow as per 2016 NFPA 13D 7.1.1 (3) <br /> This letter will affect the following permits <br /> K2107-005 Unit A <br /> K2107-006 Unit B <br /> K2107-007 Unit C <br /> K2107-008 Unit D <br /> Thank you <br /> Fire Department <br /> Steve Goforth <br /> Assistant Fire Marshal I Everett Fire Department <br /> 425-754-4576 12930 Wetmore,STE 7a, Everett,WA 98201 <br /> everettwa.gov/fire I Facebook I Twitter <br /> Note:Emails and attachments sent to and from the City of Everett are public records and may be subject to disclosure <br /> pursuant to the Public Records Act. <br />