FRONT ELEVATION PRIOR TO BRICK VENEER REMOVAL <br />DECAY At BLOCKING AND ENDS OF FLOOR JOISTS <br />DECAY AT SILL PLATE AND ENDS OF FLOOR JOISTS <br />EXIST. WALL SHEATHING <br />BRICK VENEER BY <br />OTHERS <br />SIMPSON LTP4 AT 2' O.G. <br />REMOVE 1 1/2" WIDE x <br />3 1/2" TALL SECTION OF <br />EXIST. FLOOR JOIST <br />WHERE DECAYED, <br />SHOWN SHADED, DO <br />NOT OVERCUT <br />SIMPSON LTP4 AT 2' O.C.) <br />AP945--srvc- <br />1/2"0 <br />ANCHORS AT 4' O.G. <br />(MIN. 2 PER SILL PLATE <br />SECTION), EMBED 4" MIN. <br />EXIST. CONC. BASEMENT <br />WALL <br />8/12/2021 <br />21087 WD 01.dwg <br />GENERAL NOTES: <br />GENERAL CONDITIONS: <br />1. DO NOT SCALE DRAWINGS. <br />2. REPETITIVE FEATURES MAY BE DRAWN OR CALLED OUT ONCE, BUT SHALL BE <br />COMPLETELY PROVIDED AS IF DRAWN IN FULL. <br />3. ALL WORKMANSHIP SHALL BE OF THE HIGHEST QUALITY AND SHALL BE IN <br />ACCORDANCE WITH ALL MANUFACTURERS' SPECIFICATIONS, DIRECTIONS AND <br />RECOMMENDATIONS. THE WORK SHALL ALSO BE IN STRICT CONFORMANCE WITH <br />INDUSTRY STANDARDS AND COMPLY WITH SOUND ENGINEERING AND CONSTRUCTION <br />PRACTICES. THE CONTRACTOR SHALL REPLACE PORTIONS OF THE INSTALLED WORK <br />THAT DOES NOT MEET THESE REQUIREMENTS AT THEIR EXPENSE. <br />4. ALL WORK SHALL BE PERFORMED IN ACCORDANCE WITH APPLICABLE FEDERAL, <br />STATE AND LOCAL LAWS, AND IN ACCORDANCE WITH CURRENT CODE REQUIREMENTS. <br />5. ALL NEW AND/OR REPLACEMENT MATERIALS SHALL BE EQUAL OR BETTER IN KIND AS <br />EXISTING MATERIALS. <br />6, CONTACT THIS OFFICE AT (206) 261-1500 IF ANY ADDITIONAL DAMAGE IS FOUND <br />OUTSIDE THIS SCOPE OF WORK DURING DEMOLITION OR ANY VARIATIONS TO THE SITE <br />OR EXISTING BUILDING ARE FOUND DURING THE CONSTRUCTION WORK. <br />,SITE CONDITIONS. SAFETY AND DEMOLITION: <br />1. THE CONTRACTOR SHALL PROVIDE ACCEPTABLE SAFETY AND SECURITY MEASURES <br />AND SHALL MAINTAIN SAFETY AND SECURITY AT THE JOB SITE DURING THE ENTIRE <br />COURSE OF THE PROJECT. <br />8. THE CONTRACTOR SHALL BE RESPONSIBLE FOR DEMOLITION, TEMPORARY BRACING, <br />METHODS, TECHNIQUES, SEQUENCES AND PROCEDURES IN CONNECTION WITH THE WORK. <br />9, THE CONTRACTOR SHALL PROVIDE TEMPORARY BRACING OR SUPPORT TO PREVENT <br />MOVEMENT OR SETTLEMENT OF STRUCTURE AS NEEDED IN AREAS BEING REPAIRED. <br />10, THE CONTRACTOR SHALL TRANSPORT AND DISCARD IN A LEGAL MANNER ALL <br />CONSTRICTION DEBRIS AND REMOVED ITEMS NOT INTENDED FOR REUSE, <br />11. INSPECT CONCEALED SPACES UNCOVERED DURING THE DEMOLITION PHASE FOR <br />ADDITIONAL DAMAGE. <br />12, REMOVE AND REPLACE ALL MOISTURE DAMAGED FINISHES INCLUDING: DAMAGED <br />THERMAL AND SOUND INSULATION. <br />13, THE CONTRACTOR IS TO LEAVE THE SITE BROOM CLEAN FROM CONSTRUCTION <br />RELATED DEBRIS AFTER DEMOLITION WORK IS COMPLETE, AT THE END OF EACH DAY <br />AND AT THE END OF THE PROJECT. <br />CONSTRUCTION. <br />14, ALL SUCH PRODUCTS AND MATERIALS SHALL BE INSTALLED IN ACCORDANCE WITH <br />THE MANUFACTURER'S RECOMMENDATIONS AND INSTALLATION INSTRUCTIONS, INDUSTRY <br />STANDARDS AND CODE REQUIREMENTS. THE CONTRACTOR SHALL SUBMIT TO PACIFIC <br />ENGINEERING TECHNOLOGIES, INC.. <br />15. PROVIDE WEATHER -RESISTIVE / AIR BARRIER BEHIND WALL CLADDING IN <br />ACCORDANCE WITH IRC R103 AND 2015 WASHINGTON STATE RESIDENTIAL ENERGY <br />CODE R402 AND TABLE R402.4.1.1. WEATHER -RESISTIVE / AIR BARRIER SHALL BE <br />CONTINUOUS AND ALL JOINTS SHALL BE TAPED OR SEALED IN ACCORDANCE WITH <br />THE MANUFACTURER'S RECOMMENDATIONS. <br />16. PROVIDE FLASHINGS FOR EXTERIOR BUILDING COMPONENTS IN ACCORDANCE WITH <br />IRC R103, <br />11. INSTALL ROOFING COMPONENTS IN ACCORDANCE WITH IRC CHAPTER S. <br />18, THE CONTRACTOR SHALL VERIFY THAT ALL WATERPROOFING COMPONENTS ARE <br />COMPATIBLE WITH EACH OTHER, I.E. SEALANTS AND BACKER ROD, SEALANTS, AND <br />SELF ADHESIVE (PEEL 'N' STICK) MEMBRANE, ETC. <br />IS. NEW THERMAL INSULATION MUST COMPLY WITH THE CURRENT EDITION OF THE <br />WASHINGTON STATE ENERGY CODE. PROVIDE MINIMUM R-3 PER INCH. <br />r1r-1,L iVr-trS fo 0(715^/' 106sJ'e <br />)of It <br />-TV re4A rY �� tecodrRs. <br />VtAlOFek � de 4WCN0460 Z�__AG G Z7034 B <br />10"t1Ge,�5 ,dCra4rtPot•®®�O��d�c�S� <br />9761 Z. <br />EXIST. 2x STUD WALL <br />EXIST. FLOOR SHEATHING <br />92EGdM.n ® u-900 sCf&js <br />_r"r 41tdwE�,o ay IsW . <br />70 e-44e& 60 a4&_ <br />EXIST. 2x FLOOR JOIST <br />2x BLOCKING, BOTTOM <br />PORTION OF BLOCKING TO <br />EXTEND UNDER CUT PORTION <br />OF FLOOR JOIST <br />MIN. 70EAIA t; e'3) 160t <br />REMOVE DECAYED 2x SILL <br />PLATE AND INSTALL P.T. 2x4 <br />SILL PLATE <br />NOTE: <br />1 <br />S CT I OI �t 7 SUR P RT OF FLOOR RJOISTS <br />SCALE: 1 1/2" = 1'-0" AS REQUIRED <br />EXIST. WALL SHEATHING F---� <br />BRICK VENEER BY <br />OTHERS <br />SIMPSON LTP4 AT 2' O.C. <br />AT REPLACED SECTIONS <br />OF RIM JOIST/SILL <br />PLATE <br />PROVIDE SIMPSON <br />MSTA24 STRAP AT RIM <br />JOIST SPLICE <br />SIMPSON LTP4 AT 2' O.C. <br />AT REPLACED SECTIONS <br />OF RIM JOIST/SILL <br />PLATE <br />ANCHORS At 4' O.G. <br />(MIN. 2 PER SILL PLATE <br />SECTION), EMBED 4" MIN. <br />EXIST. CONC. BASEMENT I �_ <br />WALL <br />EXIST. 2x STUD WALL <br />EXIST. FLOOR SHEATHING <br />L--I EXIST, 2x FLOOR JOIST <br />REMOVE AND REPLACE RIM <br />�U JOIST AND SILL PLATE AS <br />_ 1 REQ'D TO REMOVE DECAY <br />IN 4' LONG SECTIONS (MAX.) <br />SECTION <br />SCALE: 1 1/2" = 1'-0" <br />• /09-avelo 6 S eat <br />i <br />SITE AN <br />0 <br />SCALE. 1„20 0 <br />4 ® <br />®� <br />TRUE <br />PROJECT <br />NORTH <br />NORTH <br />©i <br />21'-1"} <br />THE INFORMATION ON THIS SITE <br />PLAN IS SCHEMATIC AND HAS <br />BEEN DERIVED FROM THE SITE <br />PLAN INFORMATION ON RECORD <br />WITH SNOHOMISH COUNTY, AERIAL <br />PHOTOGRAPHS AND SITE VISIT. <br />(PARTIAL 5ASE1~IENT WALLS SHOWN) <br />PARTIAL MAIN FLOOR <br />FRA1" rING PLAIN <br />SCALE: 1/4" = 1'-0" ® V <br />SCOPE OF UJORK SU1*"AR�' <br />TYPE: DECAY REPAIR <br />THE PURPOSE OF THESE DRAWINGS IS TO SHOW REPAIRS FOR DECAYED FLOOR FRAMING <br />THAT WAS UNCOVERED DURING REMOVAL OF BRICK VENEER WHICH WAS REPLACED AS A <br />RESULT OF A VEHICLE ''MPACT AT THE SUBJECT RESIDENCE IN EVERETT, WASHINGTON. <br />THERE IS NO INCREASE IN THE EXISTING BUILDING FOOTPRINT. <br />EXCLUSIONS: <br />NO REVIEW HAS BEEN MADE OF THE ADEQUACY OF THE EXISTING UNDAMAGED FRAMING <br />MEMBERS. <br />ARCHITECTURAL DETAILING SUCH AS, BUT NOT LIMITED TO: ROOFING, WEATHER -RESISTIVE <br />ASSEMBLIES, WATERPROOFING, EXTERIOR SIDING, FLASHING;, VENTILATION, WINDOWS, DOORS, <br />INSULATION, FIRE -RESISTIVE ASSEMBLIES, VAPOR RETARDERS, INTERIOR FINISHES, <br />MECHANICAL, ELECTRICAL, ETC. IS NOT INCLUDED IN THESE DRAWINGS, <br />3. ono <br />Ith Street Beat La <br />Dunlap ly dusirial <br />NORTHWEST <br />EVERETT <br />Everett <br />Community <br />College <br />19 <br />Whittler <br />Elmentary School <br />VICINITY MA fA Nh, APPROVED <br />SCALE: N.T.S. <br />Office of Community,PLANNING nDEPARTNiENTing & Economic �� <br />ASSESSOR'S No.: 00398100000100 <br />GOAL DESCRIPTION: <br />BAYVIEW ADD TO EV R=LT LT 15-IS BK 132 24,25 BK 133 1-1 BK 131 GRANDVIEW <br />ADD BLK 000 D-00 - LOT 1 LESS R/W ESE TO EVERETTTGW BEG At MOST SLY <br />COR LOT i REPLT GRANDVIEW ADD TH N34*52 26W ALG NE BDY THOF 15OFT TO <br />MOST NLY COR TH N55*06 34E25FT TH S34*53 26E PLT N BDY 149FT M/LTO NWLY <br />BDY ALVERSON BLVD TH SWLY ALG SDBDY 25FT M/L TO POB EXC NELY 5FT AS <br />MEASALG SELY LN THOF <br />.WILDING ATA: <br />JURISDICTION: CITY OF EVERETT <br />CODES: 2018 INTERNATIONAL RESIDENTIAL CODE (IRC) <br />2018 INTERNATIONAL EXISTING RESIDENTIAL CODE (IERC) <br />ZONING: R-1 - SINGLE FAMILY DETACHED LOW DENSITY <br />OCCUPANCY: R-3 (SINGLE FAMILY RESIDENCE) <br />LOT SIZE: 16,989 SQ. FT. OR .39 ACRES I I °� <br />BUILDING AREA: FIRST FLOOR: 1,699 $0. FT. <br />BASEMENT. 1012 $0. FT AUG 2 0 2021 <br />CITY OF <br />STRUCTURAL NOTES. �p <br />• Permit Services <br />CODE: <br />THE INTERNATIONAL RESIDENTIAL CODE (IRC) 2015 EDITION AND THE 2015 INTERNATIONAL <br />EXISTING BUILDING CODE (IERC), WITH THE STATE OF WASHINGTON AMENDMENTS. <br />STEEL BOLTS: <br />ALL BOLTS AND THREADED RODS SHALL BE ASTM A301 UNLESS NOTED OTHERWISE. <br />MECHANICAL ANCHORS: <br />MECHANICAL ANCHORS FOR ATTACHMENT TO CRACKED OR UNCRACKED CONCRETE <br />SHALL BE TITEN HD HEAVY DUTY SCREW ANCHORS BY SIMPSON STRONG -TIE, INC. (ICC-ES <br />REPORT 02113), UNLESS NOTED OTHERWISE ON THE PLANS. ANCHORS SHALL BE INSTALLED <br />AS RECOMMENDED BY THE MANUFACTURER <br />NAILS: <br />NAILING SHALL BE IN ACCORDANCE W/ FASTENING SCHEDULE TABLES 11-13 IN ICC-ES <br />EVALUATION REPORT ESR-1539 PREPARED FOR THE INTERNATIONAL STAPLE, NAIL AND <br />TOOL ASSOCIATION (ISANTA). ALL NAILS SHALL HAVE STANDARD SIZE ROUND HEADS <br />UNLESS NOTED OTHERWISE ON THE DRAWINGS. NAIL LENGTHS AND DIAMETERS SHALL BE <br />AS FOLLOWS: <br />10d 3" x 0.131" DIA. <br />10d COMMON 3" x 0.148" DIA. <br />ALL NAILS EXPOSED TO WEATHER OR IN CONTACT WITH PRESSURE TREATED WOOD <br />SHALL BE HOT -DIPPED GALVANIZED PER ASTM A153-GLASS D. <br />STRUCTURAL LUMBER GRADES AND SHEATHING RATINGS: <br />ALL LUMBER SHALL BE GRADED IN ACCORDANCE WITH CURRENT WWPA STANDARD <br />GRADING RILES FOR WESTERN LUMBER USE THE FOLLOWING SPECIES AND MINIMUM <br />GRADE: <br />BLOCKING 4 SILLS HEM -FIR 02 Fb = 850 PSI <br />WOOD PROTECTION / TREATMENT: <br />ALL LUMBER IN CONTACT WITH GROUND OR CONCRETE OR EXPOSED TO THE ELEMENTS <br />SHALL BE PRESSURE -TREATED (NOTED P.T.) IN ACCORDANCE WITH AWPA STANDARD Ul. <br />USE THE FOLLOWING MINIMUM AWPA USE CATEGORIES: <br />INTERIOR/DAMP (WOOD SILL PLATES): UC2 <br />PAINT ALL SCARS, CUTS AND DRILL HOLES WITH A WOOD PRESERVATIVE THAT IS <br />COMPATIBLE WITH THE CHEMICALS USED FOR THE PRESSURE TREATMENT OF THE WOOD, <br />PRESERVATIVES FOR FIELD TREATMENT SHALL MEET THE REQUIREMENTS OF AWPA <br />STANDARD M4. Subject To Field Inspection <br />Permit#: <br />B2108-034 <br />Site Address: <br />600 ALVERSON BLVD <br />Owner: <br />AYERS RANDY R <br />Tenant: <br />[TenName] <br />App. Date: <br />8/16/2021 <br />Proposed Use: <br />RESIDENTIAL ALTERATIONS <br />Description: <br />REPAIR DECAYED FLOOR FRAMING. <br />IT' OF EVERETT <br />REVIEWED FOR PERMIT <br />Reviewed By <br />Date:� <br />Office Set <br />Joky Site Set Fire/Planning Set <br />0 <br />6 <br />Z <br />Y <br />� <br />a <br />3z� <br />�Q <br />a <br />N Q> <br />rn <br />W9 <br />o <br />ad <br />N <br />to <br />'Q <br />(U <br />Q <br />U1 <br />W(Ld)no— <br />+� <br />a 0 <br />LU <br />LU <br />to <br />0 <br />as <br />1 <br />Ul <br />ul <br />Z <br />} <br />z <br />V <br />V luLU <br />V <br />0 <br />a> <br />LO <br />1 <br />Job No. 21081.00 <br />