Laserfiche WebLink
ORiverview J I WSEC Air Barrier Testing Report <br /> • B L D V IDA <br /> Individual Test Compliance Results <br /> The following tables list the separate pressurization and depressurization statistical parameters and compliance <br /> results with their confidence intervals used to compute values in Table 2. <br /> Table 3: Pressurization Test Compliance Results-Confidence Intervals <br /> Parameter Low Mid. High Limit Test <br /> Total Leakage @ 75 Pa 0.270 CFM/ft2 0.273 CFM/ft2 0.276 CFM/ft2 <0.25 CFM/ft2 10.3% <br /> above <br /> Pressure Exponent, n 0.638 0.658 0.678 0.45 < n<0.85 PASS <br /> Leakage Coefficient, Co 1,616 1,744 1,882 --- --- <br /> ELA @ 75 Pa 13.468 ft2 13.604 ft2 13.742 ft2 --- --- <br /> Correlation Coefficient,r2 ® >0.98 PASS <br /> Table 4: Depressurization Test Compliance Results - Confidence Intervals <br /> Parameter Low Mid. High Limit Test <br /> Total Leakage @ 75 Pa 0.216 CFM/ft2 0.217 CFM/ft2 0.218 CFM/ft2 <0.25 CFM/ft2 PASS <br /> Pressure Exponent, n 0.607 0.612 0.617 0.45< n<0.85 PASS <br /> Leakage Coefficient, Co 1,662 1,693 1,725 --- <br /> ELA @ 75 Pa 10.779 ft2 10.810 ft2 10.841 ft2 --- --- <br /> Correlation Coefficient,r2 >0.98 PASS <br /> Test Data <br /> The following sections list the model's corrected data inputs for pressurization and depressurization tests <br /> alongside figures plotting power-law model trendlines along with corrected data (see Test Procedure Section). <br /> 4 I 8 <br />