Laserfiche WebLink
Benyam Stephanos <br /> From: James Bronder <br /> Sent: Monday, September 24, 2018 3:17 PM <br /> To: Benyam Stephanos <br /> Subject: PWW1805-001 Permit Comments <br /> Hi Benyam, <br /> Please see below for comments: <br /> 1. Please provide a stamped set of drawings for the retaining wall design as it appears from Sheet C1.1,a stamp <br /> was not provided for the engineered design. <br /> 2. On the permit calculations, it appears that the addition of the block/concrete barrier is adding restoring moment <br /> to the retaining wall. The drawings do not appear to indicate that this barrier is provided on the drawings on <br /> Sheet C1.1. Please revise as required. <br /> 3. On the permit calculations, it appears that a set of increasingly taller retaining walls (3)total are shown in the <br /> cross section. However,the drawings on Sheet C1.1 do not appear to indicate this condition. Please clarify. <br /> Thank you, <br /> CELEBRATING4P—dikee" <br /> James Bronder, P.E.,S.E. <br /> 125 Associate Engineer—Plans Examiner I Permit Services <br /> YEARS Main:425.257.8810I Direct: 425.257.7287 13200 Cedar Street, Everett,WA 98201 <br /> A story worth telling everettwa.gov/permits I Facebook I Twitter <br /> Note:Emails and attachments sent to and from the City of Everett are public records and may be subject to disclosure pursuant to the Public <br /> Records Act. <br /> 1 <br />