CROWN CASTLE USA INC. SITE ACTIVITY REQUIREMENTS: <br />GENERAL NOTES: <br />ELECTRICAL INSTALLATION NOTES: <br />JURISDICTIONAL APPROVAL: 1 <br />1. NOTICE TO PROCEED- NO WORK SHALL COMMENCE PRIOR TO CROWN CASTLE USA INC. WRITTEN NOTICE <br />TO PROCEED (NIP) AND THE ISSUANCE OF A PURCHASE ORDER. PRIOR TO ACCESSING/ENTERING THE <br />SITE YOU MUST CONTACT THE CROWN CASTLE USA INC. NOC AT 800-788-7011 & THE CROWN CASTLE <br />USA INC. CONSTRUCTION MANAGER. <br />2. "LOOK UP" - CROWN CASTLE USA INC. SAFETY CLIMB REQUIREMENT: <br />THE INTEGRITY OF THE SAFETY CLIMB AND ALL COMPONENTS OF THE CLIMBING FACILITY SHALL BE <br />CONSIDERED DURING ALL STAGES OF DESIGN, INSTALLATION, AND INSPECTION. TOWER MODIFICATION, MOUNT <br />REINFORCEMENTS, AND/OR EQUIPMENT INSTALLATIONS SHALL NOT COMPROMISE THE INTEGRITY OR <br />FUNCTIONAL USE OF THE SAFETY CLIMB OR ANY COMPONENTS OF THE CLIMBING FACILITY ON THE <br />STRUCTURE. THIS SHALL INCLUDE, BUT NOT BE LIMITED TO: PINCHING OF THE WIRE ROPE, BENDING OF <br />THE WIRE ROPE FROM ITS SUPPORTS, DIRECT CONTACT OR CLOSE PROXIMITY TO THE WIRE ROPE WHICH <br />MAY CAUSE FRICTIONAL WEAR, IMPACT TO THE ANCHORAGE POINTS IN ANY WAY, OR TO IMPEDE/BLOCK ITS <br />INTENDED USE. ANY COMPROMISED SAFETY CLIMB, INCLUDING EXISTING CONDITIONS MUST BE TAGGED OUT <br />AND REPORTED TO YOUR CROWN CASTLE USA INC. POO OR CALL THE NOC TO GENERATE A SAFETY CLIMB <br />MAINTENANCE AND CONTRACTOR NOTICE TICKET. <br />3. PRIOR TO THE START OF CONSTRUCTION, ALL REQUIRED JURISDICTIONAL PERMITS SHALL BE OBTAINED. <br />THIS INCLUDES, BUT IS NOT LIMITED TO, BUILDING, ELECTRICAL, MECHANICAL, FIRE, FLOOD ZONE, <br />ENVIRONMENTAL, AND ZONING. AFTER ONSITE ACTIVITIES AND CONSTRUCTION ARE COMPLETED, ALL <br />REQUIRED PERMITS SHALL BE SATISFIED AND CLOSED OUT ACCORDING TO LOCAL JURISDICTIONAL <br />REQUIREMENTS. <br />4. ALL CONSTRUCTION MEANS AND METHODS; INCLUDING BUT NOT LIMITED TO. ERECTION PLANS, RIGGING <br />PLANS, CLIMBING PLANS, AND RESCUE PLANS SHALL BE THE RESPONSIBILITY OF THE GENERAL <br />CONTRACTOR RESPONSIBLE FOR THE EXECUTION OF THE WORK CONTAINED HEREIN, AND SHALL MEET <br />ANSI ASSE A10.48 LATEST EDITION); FEDERAL STATE, N LOCAL <br />/ ( ). A AND L C L REGULATIONS: AND ANY APPLICABLE <br />INDUSTRY CONSENSUS STANDARDS RELATED TO THE CONSTRUCTION ACTIVITIES BEING PERFORMED. ALL <br />RIGGING PLANS SHALL ADHERE TO ANSI ASSE A10. DITI N A 48 LATEST EDITION) AND CROWN CASTLE USA INC, <br />STANDARD CED-STD-10253, INCLUDING THE REQUIRED( INVOLVEMENT OF A QUALIFIED ENGINEER FOR <br />CLASS IV CONSTRUCTION, TO CERTIFY THE SUPPORTING STRUCTURE(S) IN ACCORDANCE WITH ANSI/TIA-322 <br />(LATEST EDITION). <br />5. ALL SITE WORK TO COMPLY WITH QAS-STD-10068 "INSTALLATION STANDARDS FOR CONSTRUCTION <br />ACTIVITIES ON CROWN CASTLE USA INC. TOWER SITE," CED-STD-10294 "STANDARD FOR INSTALLATION OF <br />MOUNTS AND APPURTENANCES," AND LATEST VERSION OF ANSI/TIA-1019-A-2012 "STANDARD FOR <br />INSTALLATION, ALTERATION, AND MAINTENANCEOF ANTE <br />NNA SUPPORTING STRUCTURES AND ANTENNAS. <br />6. IF THE SPECIFIED EQUIPMENT CAN NOT BE INSTALLED <br />LLED AS SHOWN ON THESE DRAWINGS THE CONTRACTOR <br />SHALL PROPOSE AN ALTERNATIVE INSTALLATION FOR APPROVAL BY CROWN CASTLE USA INC. PRIOR TO <br />PROCEEDING WITH ANY SUCH CHANGE OF INSTALLATION. <br />7. ALL MATERIALS FURNISHED AND INSTALLED SHALL BE IN STRICT ACCORDANCE WITH ALL APPLICABLE <br />CODES, REGULATIONS AND ORDINANCES. CONTRACTOR SHALL ISSUE ALL APPROPRIATE NOTICES AND <br />COMPLY WITH ALL LAWS, ORDINANCES, RULES, REGULATIONS AND LAWFUL ORDERS OF ANY PUBLIC <br />AUTHORITY REGARDING THE PERFORMANCE OF THE WORK. ALL WORK CARRIED OUT SHALL COMPLY WITH <br />ALL APPLICABLE MUNICIPAL AND UTILITY COMPANY SPECIFICATIONS AND LOCAL JURISDICTIONAL CODES, <br />ORDINANCES AND APPLICABLE REGULATIONS. <br />B. THE CONTRACTOR SHALL INSTALL ALL EQUIPMENT AND MATERIALS IN ACCORDANCE WITH MANUFACTURER'S <br />RECOMMENDATIONS UNLESS SPECIFICALLY STATED OTHERWISE. <br />9. THE CONTRACTOR SHALL CONTACT UTILITY LOCATING SERVICES PRIOR TO THE START OF CONSTRUCTION. <br />10. ALL EXISTING ACTIVE SEWER, WATER, GAS, ELECTRIC AND OTHER UTILITIES WHERE ENCOUNTERED IN THE <br />WORK, SHALL BE PROTECTED AT ALL TIMES AND WHERE REQUIRED FOR THE PROPER EXECUTION OF THE <br />WORK, SHALL BE RELOCATED AS DIRECTED BY CONTRACTOR. EXTREME CAUTION SHOULD BE USED BY THE <br />CONTRACTOR WHEN EXCAVATING OR DRILLING PIERS AROUND OR NEAR UTILITIES, CONTRACTOR SHALL <br />PROVIDE SAFETY TRAINING FOR THE WORKING CREW, THIS WILL INCLUDE BUT NOT BE LIMITED TO A) FALL <br />PROTECTION B) CONFINED SPACE C) ELECTRICAL SAFETY D) TRENCHING AND EXCAVATION E) <br />CONSTRUCTION SAFETY PROCEDURES. <br />11. ALL SITE WORK SHALL BE AS INDICATED ON THE STAMPED CONSTRUCTION DRAWINGS AND PROJECT <br />SPECIFICATIONS, LATEST APPROVED REVISION. <br />12, CONTRACTOR SHALL KEEP THE SITE FREE FROM ACCUMULATING WASTE MATERIAL, DEBRIS, AND TRASH AT <br />THE COMPLETION OF THE WORK. IF NECESSARY, RUBBISH, STUMPS, DEBRIS, STICKS, STONES AND OTHER <br />REFUSE SHALL BE REMOVED FROM THE SITE AND DISPOSED OF LEGALLY. <br />13. ALL EXISTING INACTIVE SEWER, WATER, GAS, ELECTRIC AND OTHER UTILITIES, WHICH INTERFERE WITH THE <br />EXECUTION OF THE WORK, SHALL BE REMOVED AND/OR CAPPED, PLUGGED OR OTHERWISE DISCONTINUED <br />AT POINTS WHICH WILL NOT INTERFERE WITH THE EXECUTION OF THE WORK, SUBJECT TO THE APPROVAL <br />OF CONTRACTOR, TOWER OWNER, CROWN CASTLE USA INC., AND/OR LOCAL UTILITIES. <br />14. THE CONTRACTOR SHALL PROVIDE SITE SIGNAGE IN ACCORDANCE WITH THE TECHNICAL SPECIFICATION FOR <br />SITE SIGNAGE REQUIRED BY LOCAL JURISDICTION AND SIGNAGE REQUIRED ON INDIVIDUAL PIECES OF <br />EQUIPMENT, ROOMS, AND SHELTERS. <br />15. THE SITE SHALL BE GRADED TO CAUSE SURFACE WATER TO FLOW AWAY FROM THE CARRIER'S EQUIPMENT <br />AND TOWER AREAS. <br />16. THE SUB GRADE SHALL BE COMPACTED AND BROUGHT TO A SMOOTH UNIFORM GRADE PRIOR TO FINISHED: <br />SURFACE APPLICATION. <br />17. THE AREAS OF THE OWNERS PROPERTY DISTURBED BY THE WORK AND NOT COVERED BY THE TOWER, <br />EQUIPMENT OR DRIVEWAY, SHALL BE GRADED TO A UNIFORM SLOPE, AND STABILIZED TO PREVENT <br />EROSION AS SPECIFIED ON THE CONSTRUCTION DRAWINGS AND/OR PROJECT SPECIFICATIONS. <br />18, CONTRACTOR SHALL MINIMIZE DISTURBANCE TO EXISTING SITE DURING CONSTRUCTION. EROSION CONTROL <br />MEASURES, IF REQUIRED DURING CONSTRUCTION, SHALL BE IN CONFORMANCE WITH THE LOCAL GUIDELINES <br />FOR EROSION AND SEDIMENT CONTROL. <br />19. THE CONTRACTOR SHALL PROTECT EXISTING IMPROVEMENTS, PAVEMENTS, CURBS, LANDSCAPING AND <br />STRUCTURES. ANY DAMAGED PART SHALL BE REPAIRED AT CONTRACTOR'S EXPENSE TO THE SATISFACTION <br />OF OWNER. <br />20. CONTRACTOR SHALL LEGALLY AND PROPERLY DISPOSE OF ALL SCRAP MATERIALS SUCH AS COAXIAL <br />CABLES AND OTHER ITEMS REMOVED FROM THE EXISTING FACILITY. ANTENNAS REMOVED SHALL BE <br />RETURNED TO THE OWNER'S DESIGNATED LOCATION. <br />21. CONTRACTOR SHALL LEAVE PREMISES IN CLEAN CONDITION. TRASH AND DEBRIS SHOULD BE REMOVED <br />FROM SITE ON A DAILY BASIS. <br />22. NO FILL OR EMBANKMENT MATERIAL SHALL BE PLACED ON FROZEN GROUND, FROZEN MATERIALS, SNOW <br />OR ICE SHALL NOT BE PLACED IN ANY FILL OR EMBANKMENT. <br />GREENFIELD GROUNDING NOTES: <br />1. FOR THE PURPOSE OF CONSTRUCTION DRAWING, THE FOLLOWING DEFINITIONS SHALL APPLY: <br />CONTRACTOR: GENERAL CONTRACTOR RESPONSIBLE FOR CONSTRUCTION <br />CARRIER: VERIZON <br />TOWER OWNER: CROWN CASTLE USA INC. <br />2. THESE DRAWINGS HAVE BEEN PREPARED USING STANDARDS OF PROFESSIONAL CARE AND COMPLETENESS NORMALLY <br />EXERCISED UNDER SIMILAR CIRCUMSTANCES BY REPUTABLE ENGINEERS IN THIS OR SIMILAR LOCALITIES. IT IS <br />ASSUMED THAT THE WORK DEPICTED WILL BE PERFORMED BY AN EXPERIENCED CONTRACTOR AND/OR WORKPEOPLE <br />WHO HAVE A WORKING KNOWLEDGE OF THE APPLICABLE CODE STANDARDS AND REQUIREMENTS AND OF INDUSTRY <br />ACCEPTED STANDARD GOOD PRACTICE. AS NOT EVERY CONDITION OR ELEMENT IS (OR CAN BE) EXPLICITLY SHOWN <br />ON THESE DRAWINGS, THE CONTRACTOR SHALL USE INDUSTRY ACCEPTED STANDARD GOOD PRACTICE FOR <br />MISCELLANEOUS WORK NOT EXPLICITLY SHOWN. <br />3. THESE DRAWINGS REPRESENT THE FINISHED STRUCTURE. THEY DO NOT INDICATE THE"IIMS OR METHODS OF <br />CONSTRUCTION. THE CONTRACTOR SHALL BE SOLELY RESPONSIBLE FOR THE CONSTRUCTION. MEANS, METHODS, <br />TECHNIQUES, SEQUENCES, AND PROCEDURES. THE CONTRACTOR SHALL PROVIDE ALL -MEASURES NECESSARY FOR <br />PROTECTION OF LIFE AND PROPERTY DURING CONSTRUCTION. SUCH MEASURES SHALL INCLUDE,.'13UT NOT BE LIMITED <br />TO, BRACING, FORMWORK, SHORING, ETC. SITE VISITS BY THE ENGINEER OR HIS "-kEPRESENTATIVE WILL NOT INCLUDE <br />INSPECTION OF THESE ITEMS AND IS FOR STRUCTURAL OBSERVATION OF THE FINISHED STRUCTURE ONLY. <br />4. NOTES AND DETAILS IN THE CONSTRUCTION DRAWINGS SHALL TAKE PRECEDENCE. OVER GENERAL NOTES AND TYPICAL <br />DETAILS. WHERE NO DETAILS ARE SHOWN, CONSTRUCTION SHALL CONFORM -TO SIMILAR WORK ON THE PROJECT, <br />AND/OR AS PROVIDED FOR IN THE CONTRACT DOCUMENTS. WHERE. DISCREPANCIES OCCUR BETWEEN:PLANS, DETAILS, <br />GENERAL NOTES, AND SPECIFICATIONS, THE GREATER, MORE STRICT REQUIREMENTS, SHALL GOVERN. 'IF FURTHER <br />CLARIFICATION IS REQUIRED CONTACT THE ENGINEER OF RECORD:. <br />5. SUBSTANTIAL EFFORT HAS BEEN MADE TO PROVIDE ACCURATE. DIMENSIONS AND MEASUREMENTS ON: THE. DRAWINGS TO <br />ASSIST IN THE FABRICATION AND/OR PLACEMENT OF CONSTRUCTIONELEMENTS BUT IT IS THE SOLE. RESPONSIBILITY <br />OF THE CONTRACTOR TO FIELD VERIFY THE DIMENSIONS, MEASUREMENTS, AND/OR CLEARANCES SHOWN IN THE <br />CONSTRUCTION DRAWINGS PRIOR TO FABRICATION OR C TTN I- Y U 1 G OF AN NEW OR EXISTING CONSTRUCTION ELEMENTS. <br />IF IT IS DETERMINED THAT THERE ARE DISCREPANCIES <br />SC EPANCIES AND/OR CONFLICTS WITH THE CONSTRUCTION DRAWINGS THE <br />ENGINEER OF RECORD IS TO BE NOTIFIED AS SOON' A I S POSSIBLE. <br />6. PRIOR TO THE SUBMISSION OF BIDS, THE BIDDING CONTRACTOR SHALL VISIT THE CELL SITE TO FAMILIARIZE WITH THE <br />EXISTING CONDITIONS AND TO CONFIRM THAT THE WOW CAN BE ACCOMPLISHED AS SHOWN ON THE CONSTRUCTION <br />DRAWINGS. ANY DISCREPANCY FOUND SHALL BE BROUGHT TO THE ATTENTION OF CROWN CASTLE. <br />7. ALL MATERIALS FURNISHED AND INSTALLED SHALL BE IN STRICT ACCORDANCE WITH ALL APPLICABLE CODES, <br />REGULATIONS AND ORDINANCES. CONTRACTOR SHALL ISSUE ALL APPROPRIATE NOTICES AND COMPLY WITH ALL LAWS, <br />ORDINANCES, RULES, REGULATIONS AND LAWFUL ORDERS OF ANY PUBLIC AUTHORITY REGARDING THE PERFORMANCE <br />OF THE WORK. ALL WORK CARRIED OUT COMPLY SHALL L C 0 WITH ALL APPLICABLE MUNICIPAL AND UTILITY COMPA <br />NY <br />SPECIFICATIONS AND LOCAL JURISDICTIONAL 'CODES ORDINANCES AND APPLICABLE REGULATIONS. <br />8. UNLESS NOTED OTHERWISE, THE WORK SHALL INCLUDE FURNISHING MATERIALS, EQUIPMENT, APPURTENANCES AND. <br />LABOR NECESSARY TO COMPLETE ALL INSTALLATIONS AS. INDICATED ON THE DRAWINGS. <br />9. THE CONTRACTOR SHALL INSTALL ALL EQUIPMENT AND MATERIALS IN ACCORDANCE WITH MANUFACTURER'S <br />RECOMMENDATIONS UNLESS SPECIFICALLY STATED OTHERWISE <br />10. IF THE SPECIFIED EQUIPMENT CANNOT. BE INSTALLED ;AS SHOWN ON THESE DRAWINGS, THE CONTRACTOR SHALL <br />PROPOSE AN ALTERNATIVE INSTALLATION FOR APPROVAL.BY THE CARRIER AND .CROWN CASTLE PRIOR TO PROCEEDING <br />WITH ANY SUCH CHANGE OF INSTALLATION. <br />11. CONTRACTOR IS TO PERFORM A SITE INVESTIGATION. AND IS TO DETERMINE THE BEST ROUTING OF ALL CONDUITS FOR <br />POWER, AND TELCO AND FOR GROUNDING CABLES. AS,SHOWN IN THE POWER, TELCO, AND GROUNDING PLAN <br />DRAWINGS. <br />12. THE CONTRACTOR SHALL PROTECT EXISTING IMPROVEMENTS, PAVEMENTS, CURBS, LANDSCAPING AND STRUCTURES. ANY <br />DAMAGED PART SHALL BE REPAIRED AT CONTRACTORS EXPENSE TO THE SATISFACTIONOF.CROWN CASTLE USA INC. <br />13. CONTRACTOR SHALL LEGALLY AND PROPERLY DISPOSE OF ALL SCRAP MATERIALS SUCH AS COAXIAL CABLES AND <br />OTHER ITEMS REMOVED FROM THE EXISTING FACILITY, ANTENNAS REMOVED SHALL BE .RETURNED TO THE OWNER'S <br />DESIGNATED LOCATION. <br />14. CONTRACTOR SHALL LEAVE PREMISES IN CLEAN. CONDITION. TRASH AND DEBRIS SHOULD BE REMOVED FROM SITE ON <br />A DAILY BASIS. <br />CONCRETE, FOUNDATIONS, AND REINFORCING STEEL' <br />1. ALL CONCRETE WORK SHALL BE:IN ACCORDANCE WITH THE ACI 301, ACI 318, ACI 336, ASTM A184, ASTM A185 AND <br />THE: DESIGN AND CONSTRUCTION SPECIFICATION FOR CASTrIN-PLACE CONCRETE. <br />2.UNLESS NOTED OTHERWISE,'SOIL BEARING PRESSURE USED FOR DESIGN OF SLABS AND FOUNDATIONS IS ASSUMED <br />TO' BE 1000 psf. <br />3..' ALL CONCRETE SHALL 'HAVE A MINIMUM COMPRESSIVE STRENGTH.(f'c). OF 3000 psi AT 28 DAYS, UNLESSNOTED <br />'OTHERWISE. NO MORE THAN S90 MINUTES SHALL ELAPSE#FROM BATCH TIME TO TIME OF. PLACEMENT UNLESS <br />APPROVED BY THE ENGINEER OF RECORD. TEMPERATURE OF CONCRETE SHALL NOT EXCEED SO'f AT-TIME'OF <br />PLACEMENT. <br />4. CONCRETE EXPOSED TO FREEZE -THAW : CYCLES SHALL CONTAIN:AIR ENTRAINING ADMIXTURES. AMOUNT OF AIR <br />ENTRAINMENT. TO BE BASED ON SIZE OF AGGREGATE AND F3 CLASS EXPOSURE (VERY SEVERE). CEMENT USED TO BE <br />TYPE I1 PORTLAND CEMENT WITH -A MAXIMUM WATER -TO -CEMENT RATIO (W/C). OF GAS. <br />5. ALL STEEL REINFORCING SHALL CONFORM TO ASTM A615. ALL WELDED WIRE FABRIC (WWF) SHALL CONFORM TO ASTM <br />A185. ALL SPLICES SHALL BE 'CLASS "B' TENSION SPLICES, UNLESS NOTED OTHERWISE. ALL HOOKS . SHALL:' BE <br />STANDARD 90 DEGREE HOOKS, UNLESS NOTED OTHERWISE. YIELD STRENGTH (Fy);: OF. STANDARD DEFORMED: BARS ARE <br />AS FOLLOWS: <br />#4 BARS AND SMALLER ...... .:5 ................ ..................................... 40 kel <br />#5 BARS AND LARGER. ........ ................. ....... ........,....... 60 ksi.: <br />6. THE FOLLOWING MINIMUM CONCRETE COVER SHALL BE PROVIDED FOR REINFORCING STEEL. UNLESS SHOWN OTHERWISE <br />ON DRAWINGS: <br />CONCRETE CAST AGAINST AND PERMANENTLY EXPOSED TO EARTH ....................... 3" <br />CONCRETE EXPOSED TO EARTH OR WEATHER:' <br />#6 BARS AND LARGER .:i....................... .....,.,2". <br />#5 BARS AND SMALLER.. ....................... ............................................ 1-1/2 <br />CONCRETE NOT EXPOSED TO .EARTH OR WEATHER <br />SLAB AND WALLS. ....: .....a.. ......3/4".: <br />BEAMS AND COLUMNS / <br />7. A TOOLED EDGE OR A.3/4"�ICHAMFER SHALL BE PROVIDED AT ALL EXPOSED EDGES OF CONCRETE, UNLESS NOTED <br />OTHERWISE, IN ACCORDANCE WITH ACI 301 SECTION 4.2.4. <br />1. ALL GROUND ELECTRODE SYSTEMS (INCLUDING TELECOMMUNICATION, RADIO, LIGHTNING PROTECTION AND AC POWER GES'S) SHALL BE BONDED TOGETHER AT OR BELOW GRADE, BY TWO OR MORE COPPER BONDING CONDUCTORS IN <br />ACCORDANCE WITH THE NEC. <br />2. THE CONTRACTOR SHALL PERFORM IEEE FALL-OF-POTENTAL RESISTANCE TO EARTH TESTING (PER IEEE 1100 AND 81) FOR GROUND ELECTRODE SYSTEMS, THE CONTRACTOR SHALL FURNISH AND INSTALL SUPPLEMENTAL GROUND <br />ELECTRODES AS NEEDED TO ACHIEVE A TEST RESULT OF 5 OHMS OR LESS. <br />3. THE CONTRACTOR IS RESPONSIBLE FOR PROPERLY SEQUENCING GROUNDING AND UNDERGROUND CONDUIT INSTALLATION AS TO PREVENT ANY LOSS OF CONTINUITY IN THE GRDUNDING' SYSTEM OR DAMAGE TO THE CONDUIT AND PROVIDE <br />TESTING RESULTS. <br />4. METAL CONDUIT AND TRAY SHALL BE GROUNDED AND MADE ELECTRICALLY CONTINUOUS WITH LISTED BONDING FITTINGS OR BY BONDING ACROSS THE DISCONTINUITY WITH #6 COPPER WIRE UL APPROVED GROUNDING TYPE CONDUIT <br />CLAMPS. <br />5. METAL RACEWAY SHALL NOT BE USED AS THE NEC REQUIRED EQUIPMENT GROUND CONDUCTOR. STRANDED COPPER CONDUCTORS WITH GREEN INSULATION, SIZED IN ACCORDANCEWITH THE NEC, SHALL BE FURNISHED AND INSTALLED <br />WITH THE POWER CIRCUITS TO BTS EQUIPMENT. <br />6. EACH CABINET FRAME SHALL BE DIRECTLY CONNECTED TO THE MASTER GROUND BAR WITH GREEN INSULATED SUPPLEMENTAL EQUIPMENT GROUND WIRES, #6 STRANDED COPPER OR LARGER FOR INDOOR BTS; #2 BARE SOLID TINNED <br />COPPER FOR OUTDOOR BTS. <br />7. CONNECTIONS TO THE GROUND BUS SHALL NOT BE DOUBLED UP OR STACKED BACK TO BACK CONNECTIONS ON OPPOSITE SIDE OF THE.. GROUND BUS ARE PERMITTED. <br />S. ALL EXTERIOR GROUND CONDUCTORS BETWEEN EQUIPMENT/GROUND BARS AND THE GROUND RING SHALL BE #2 SOLID TINNED COPPERUNLESSOTHERWISE INDICATED. _ <br />9. ALUMINUM CONDUCTOR OR COPPER CLAD STEEL CONDUCTOR SHALL NOT BE USED FOR GROUNDING CONNECTIONS. <br />10. USE OF 90' BENDS IN THE PROTECTION GROUNDING CONDUCTORS SHALL BE AVOIDED WHEN 45 BENDS CAN BE ADEQUATELY SUPPORTED. - <br />11. EXOTHERMIC WELDS SHALL BE USED FOR ALL GROUNDING CONNECTIONS BELOW GRADE. <br />12. ALL GROUND CONNECTIONS ABOVE GRADE (INTERIOR AND EXTERIOR) SHALL BE FORMED USING HIGH PRESS CRIMPS. <br />13. COMPRESSION GROUND CONNECTIONS MAY BE REPLACED BY EXOTHERMIC WELD CONNECTIONS. <br />14, ICE BRIDGE BONDING CONDUCTORS SHALL BE EXOTHERMICALLY BONDED OR BOLTED TO THE BRIDGE AND THE TOWER GROUND BAR. <br />15. APPROVED ANTIOXIDANT COATINGS (i.e. CONDUCTIVE GEL OR PASTE) SHALL BE USED ON ALL COMPRESSION AND BOLTED GROUND CONNECTIONS. <br />16. ALL EXTERIOR GROUND CONNECTIONS SHALL BE COATED WITH A CORROSION RESISTANT MATERIAL, <br />17. MISCELLANEOUS ELECTRICAL AND NON -ELECTRICAL METAL BOXES, FRAMES AND SUPPORTS SHALL BE BONDED TO THE GROUND RING, IN ACCORDANCE WITH THE NEC. <br />18. BOND ALL METALLIC OBJECTS WITHIN 6 ft OF MAIN GROUND RING WITH (1) #2 BARE SOLID TINNED COPPER GROUND CONDUCTOR. <br />19. GROUND CONDUCTORS USED FOR THE FACILITY GROUNDING AND LIGHTNING PROTECTION SYSTEMS SHALL NOT BE ROUTED THROUGH METALLIC OBJECTS THAT FORM A RING AROUND THE CONDUCTOR, SUCH AS METALLIC CONDUITS, <br />METAL SUPPORT CLIPS OR SLEEVES THROUGH WALLS OR FLOORS. WHEN IT IS REQUIRED TO BE HOUSED IN CONDUIT TO MEET CODE REQUIREMENTS OR LOCAL CONDITIONS, NON-METALLIC MATERIAL SUCH AS PVC CONDUIT SHALL BE <br />USED. WHERE USE OF METAL CONDUIT IS UNAVOIDABLE (i.e.. NONMETALLIC CONDUIT PROHIBITED BY LOCAL CODE) THE GROUND CONDUCTOR SHALL BE BONDED TO EACH END OF THE METAL CONDUIT. <br />20. ALL GROUNDS THAT TRANSITION FROM BELOW GRADE TO ABOVE GRADE MUST BE #2 BARE SOLID TINNED COPPER IN 3/4" NON-METALLIC, FLEXIBLE CONDUIT FROM 24" BELOW GRADE TO WITHIN 3" TO 6" OF CAD -WELD TERMINATION <br />POINT. THE EXPOSED END OF THE CONDUIT MUST BE SEALED WITH SILICONE CAULK. (ADD TRANSITIONING GROUND STANDARD DETAIL AS WELL). <br />21. BUILDINGS WHERE THE MAIN GROUNDING CONDUCTORS ARE REQUIRED TO BE ROUTED TO GRADE, THE CONTRACTOR SHALL ROUTE TWO GROUNDING CONDUCTORS FROM THE ROOFTOP, TOWERS, AND WATER TOWERS GROUNDING RING, TO <br />THE EXISTING GROUNDING SYSTEM, THE GROUNDING CONDUCTORS SHALL NOT BE SMALLER THAN 2/0 COPPER. ROOFTOP GROUNDING RING SHALL BE BONDED TO THE EXISTING GROUNDING SYSTEM, THE BUILDING STEEL COLUMNS, <br />LIGHTNING PROTECTION SYSTEM, AND BUILDING MAIN WATER UNE (FERROUS OR NONFERROUS METAL PIPING ONLY). <br />1. ALL ELECTRICAL WORK SHALL BE PERFORMED IN ACCORDANCE WITH THE PROJECT SPECIFICATIONS, NEC AND ALL APPLICABLE <br />FEDERAL, STATE, AND LOCAL CODES/ORDINANCES. <br />2. CONDUIT ROUTINGS ARE SCHEMATIC. CONTRACTOR SHALL INSTALL CONDUITS SO THAT ACCESS TO EQUIPMENT IS NOT BLOCKED <br />AND TRIP HAZARDS ARE ELIMINATED, <br />3. WIRING, RACEWAY AND SUPPORT METHODS AND MATERIALS SHALL COMPLY WITH THE REQUIREMENTS OF THE NEC. <br />4. ALL CIRCUITS SHALL BE SEGREGATED AND MAINTAIN MINIMUM CABLE SEPARATION AS REQUIRED BY THE NEC. <br />4.1. ALL EQUIPMENT SHALL BEAR THE UNDERWRITERS LABORATORIES LABEL OF APPROVAL, AND SHALL CONFORM TO <br />REQUIREMENT OF THE NATIONAL ELECTRICAL CODE. <br />4.2. ALL OVERCURRENT DEVICES SHALL HAVE AN INTERRUPTING CURRENT RATING THAT SHALL BE GREATER THAN THE SHORT <br />CIRCUIT CURRENT TO WHICH THEY ARE SUBJECTED, 22,000 AIC MINIMUM. VERYIFY AVAILABLE SHORT CIRCUIT CURRENT DOES <br />NOT EXCEED THE RATING OF ELECTRICAL EQUIPMENT IN ACCORDANCE WITH ARTICLE 110.24 NEC OR THE MOST CURRENT <br />ADOPTED CODE PRE THE GOVERNING JURISDICTION. <br />5. EACH END OF EVERY POWER PHASE CONDUCTOR, GROUNDING CONDUCTOR, AND TELCO CONDUCTOR OR CABLE SHALL BE <br />LABELED WITH COLOR -CODED INSULATION OR ELECTRICAL TAPE (3M BRAND, 1/2" PLASTIC ELECTRICAL TAPE WITH UV <br />PROTECTION, OR EQUAL). THE IDENTIFICATION METHOD SHALL CONFORM WITH NEC AND OSHA. <br />6. ALL ELECTRICAL COMPONENTS SHALL BE CLEARLY LABELED WITH LAMICOID TAGS SHOWING THEIR RATED VOLTAGE, PHASE <br />CONFIGURATION, WIRE CONFIGURATION, POWER OR AMPACITY RATING AND BRANCH CIRCUIT ID NUMBERS (i.e. PANEL BOARD AND <br />CIRCUIT ID'S). <br />7. PANEL BOARDS (ID NUMBERS) SHALL BE CLEARLY LABELED WITH PLASTIC LABELS, <br />8. ALL TIE WRAPS SHALL BE CUT FLUSH WITH APPROVED CUTTING TOOL TO REMOVE SHARP EDGES. <br />9. ALL POWER AND EQUIPMENT GROUND WIRING IN TUBING OR CONDUIT SHALL BE SINGLE COPPER CONDUCTOR (#14 OR LARGER) <br />WITH TYPE THHW, THWN, THWN-2, XHHW, XHHW-2, THW, THW-2, RHW, OR RHW-2 INSULATION UNLESS OTHERWISE SPECIFIED. <br />10. SUPPLEMENTAL EQUIPMENT GROUND WIRING LOCATED INDOORS SHALL BE SINGLE COPPER CONDUCTOR (#6 OR LARGER) WITH <br />TYPE THHW THWN THWN-2 XHHW XHHW- IN T - 2 THIN. THW-2, RHW OR RHW-2 INSULATION UNLESS OTHERWISE SPECIFIED. <br />11. POWER AND WIRING CONTROL FLEXIBLE <br />0 G IN LE BLE CORD SHALL BE MULTI -CONDUCTOR, TYPE SCOW CORD (#14 OR LARGER) UNLESS <br />OTHERWISE SPECIFIED. <br />12. POWER AND CONTROL WIRING FOR USE IN CABLE TRAY SHALL BE MULTI -CONDUCTOR, TYPE TO CABLE (#14 OR LARGER), WITH <br />TYPE THHW, THWN, THWN-2, XHHW, XHHW-2, THW, THW-2, RHW, OR RHW-2 INSULATION UNLESS OTHERWISE SPECIFIED. <br />13. ALL POWER AND GROUNDING CONNECTIONS SHALL BE CRIMP -STYLE, COMPRESSION WIRE LUGS AND WIRE NUTS BY THOMAS AND <br />BETTS (OR EQUAL). LUGS AND WIRE NUTS SHALL BE RATED FOR OPERATION NOT LESS THAN 75- C (90' C IF AVAILABLE). <br />14. RACEWAY AND CABLE TRAY SHALL BE LISTED OR LABELED FOR ELECTRICAL USE IN ACCORDANCE WITH NEMA, UL, ANSI/IEEE <br />AND NEC. <br />15. ELECTRICAL METALLIC TUBING(EMT), T M INTERMEDIATE METAL CONDUIT IMC OR RIGID ME <br />TAL ETAL CONDUIT RMC SHALL BE USED FO ( ) ( R <br />EXPOSED INDOOR LOCATIONS. <br />16. ELECTRICAL METALLIC TUBING (EMT) OR METAL -CLAD CABLE (MC) SHALL BE USED FOR CONCEALED INDOOR LOCATIONS, <br />17. SCHEDULE 40 PVC UNDERGROUND ON STRAIGHTS AND SCHEDULE 80 PVC FOR ALL ELBOWS/90s AND ALL APPROVED ABOVE <br />GRADE PVC CONDUIT. <br />18, LIQUID -TIGHT FLEXIBLE METALLIC CONDUIT (LIQUID-TITE FLEX) SHALL BE USED INDOORS AND OUTDOORS, WHERE VIBRATION <br />OCCURS OR FLEXIBILITY IS NEEDED. <br />19. CONDUIT AND TUBING FITTINGS SHALL BE THREADED OR COMPRESSION -TYPE AND APPROVED FOR THE LOCATION USED. SET <br />SCREW FITTINGS ARE NOT ACCEPTABLE. <br />20. CABINETS, BOXES AND WIRE WAYS SHALL BE LABELED FOR ELECTRICAL USE IN ACCORDANCE WITH NEMA, UL, ANSI/IEEE AND <br />THE NEC. <br />21. WIREWAYS SHALL BE METAL WITH AN ENAMEL FINISH AND INCLUDE A HINGED COVER, DESIGNED TO SWING OPEN DOWNWARDS <br />(WIREMOLD SPECMATE WIREWAY). <br />22. SLOTTED WIRING DUCT SHALL BE PVC AND INCLUDE COVER (PANDUIT TYPE E OR EQUAL), <br />23. CONDUITS SHALL BE FASTENED SECURELY IN PLACE WITH APPROVED NON -PERFORATED STRAPS AND HANGERS. EXPLOSIVE <br />DEVICES (i.e. POWDER ACTUATED) FOR ATTACHING HANGERS TO STRUCTURE WILL NOT BE PERMITTED. CLOSELY FOLLOW THE <br />LINES OF THE STRUCTURE, MAINTAIN CLOSE PROXIMITY TO THE STRUCTURE AND KEEP CONDUITS IN TIGHT ENVELOPES. CHANGES <br />IN DIRECTION TO ROUTE AROUND OBSTACLES SHALL BE MADE WITH CONDUIT OUTLET BODIES. CONDUIT SHALL BE INSTALLED IN <br />'A NEAT AND WORKMANLIKE MANNER. PARALLEL AND PERPENDICULAR TO STRUCTURE WALL AND CEILING LINES. ALL CONDUIT <br />..'SHALL BE FISHED TO CLEAR OBSTRUCTIONS, ENDS OF CONDUITS SHALL BE TEMPORARILY CAPPED FLUSH TO FINISH GRADE TO <br />PREVENT CONCRETE, PLASTER OR DIRT FROM ENTERING. CONDUITS SHALL BE RIGIDLY CLAMPED TO BOXES BY GALVANIZED <br />MALLEABLE IRON BUSHING ON INSIDE AND GALVANIZED MALLEABLE IRON LOCKNUT ON OUTSIDE AND INSIDE. <br />24.EQUIPMENT CABINETS, TERMINAL BOXES, JUNCTION BOXES AND PULL BOXES SHALL BE GALVANIZED OR EPDXY -COATED SHEET <br />'STEEL. SHALL MEET OR EXCEED UL 50 AND BE RATED NEMA 1 (OR BETTER) FOR INTERIOR LOCATIONS AND NEMA 3R (OR <br />BETTER) FOR EXTERIOR LOCATIONS. <br />25. METAL RECEPTACLE, SWITCH AND DEVICE BOXES SHALL BE GALVANIZED, EPDXY -COATED OR NON -CORRODING; SHALL MEET OR <br />EXCEED UL 514A AND NEMA OS 1 AND BE RATED NEMA 1 (OR BETTER) FOR INTERIOR LOCATIONS AND WEATHER PROTECTED <br />(WP OR BETTER) FOR EXTERIOR LOCATIONS. <br />26:-.NONMETALLIC RECEPTACLE, SWITCH AND DEVICE BOXES SHALL MEET OR EXCEED NEMA OS 2 (NEWEST REVISION) AND BE RATED <br />.NEMA 1 (OR BETTER) FOR INTERIOR LOCATIONS AND WEATHER PROTECTED (WP OR BETTER) FOR EXTERIOR LOCATIONS. <br />27. THE CONTRACTOR SHALL NOTIFY AND OBTAIN NECESSARY AUTHORIZATION FROM THE CARRIER AND/OR CROWN CASTLE USA INC. <br />BEFORE COMMENCING WORK ON THE AC POWER DISTRIBUTION PANELS. <br />28.;THE CONTRACTOR SHALL PROVIDE NECESSARY TAGGING ON THE BREAKERS, CABLES AND DISTRIBUTION PANELS IN ACCORDANCE <br />WITH THE APPLICABLE CODES AND STANDARDS TO SAFEGUARD LIFE AND PROPERTY. <br />29. INSTALL LAMICOID LABEL ON THE METER CENTER TO SHOW 'VERIZON". <br />30. ALL EMPTY/SPARE CONDUITS THAT ARE INSTALLED ARE TO HAVE A METERED MULE TAPE PULL CORD INSTALLED. <br />CONDUCTOR COLOR CODE <br />SYSTEM <br />CONDUCTOR <br />COLOR <br />120/24OV, 10 <br />A PHASE <br />BLACK <br />B PHASE <br />RED <br />NEUTRAL <br />WHITE <br />GROUND <br />GREEN <br />120/208V, 30 <br />A PHASE <br />BLACK <br />B PHASE <br />RED <br />C PHASE <br />BLUE <br />NEUTRAL <br />WHITE <br />GROUND <br />GREEN <br />277/48OV, 30 <br />A PHASE <br />BROWN <br />8 PHASE <br />ORANGE OR PURPLE <br />C PHASE <br />YELLOW <br />NEUTRAL <br />GREY <br />GROUND <br />GREEN <br />DC VOLTAGE <br />POS (+) <br />RED** <br />NEG (-) <br />BLACK*" <br />* SEE NEC 210.5(C)(1) AND (2) <br />** POLARITY MARKED AT TERMINATION <br />ABBREVIATIONS <br />APWA UNIFORM COLOR CODE: <br />WHITE PROPOSED EXCAVATION <br />TEMPORARY SURVEY MARKINGS <br />c ELECTRIC POWER LINES, CABLES, <br />CONDUIT, AND LIGHTING CABLES <br />YELLOW GAS, OIL, STEAM, PETROLEUM, OR <br />GASEOUS MATERIALS <br />COMMUNICATION, ALARM OR SIGNAL LINES, <br />CABLES, OR CONDUIT AND TRAFFIC LOOPS <br />® POTABLE WATER <br />RECLAIMED WATER <br />, IRRIGATION, AND <br />SLURRY LINES , <br />SEWERS AND DRAIN LINES <br />ANT <br />ANTENNA <br />(E) <br />EXISTING <br />FIF <br />FACILITY INTERFACE FRAME <br />GEN <br />GENERATOR <br />GPS <br />GLOBAL POSITIONING SYSTEM <br />GSM <br />GLOBAL SYSTEM FOR MOBILE <br />LTE <br />LONG TERM EVOLUTION <br />MOB <br />MASTER GROUND BAR <br />MW <br />MICROWAVE <br />(N) <br />NEW <br />NEC <br />NATIONAL ELECTRIC CODE <br />(P) <br />PROPOSED <br />- <br />PP <br />POWER PLANT <br />QTY <br />QUANTITY <br />RECT <br />RECTIFIER <br />RBS <br />RADIO BASE STATION <br />T T <br />RET <br />REMOTE ELECTRIC TILT <br />CITY OFEVERE <br />REDS <br />RADIO FREQUENCY DATA SHEET <br />- ryg <br />RRH <br />REMOTE RADIO HEAD <br />PER <br />RRU <br />REMOTE RADIO UNIT <br />E VIE ED <br />SIAD <br />SMART <br />TINTEGRATED DEVICE <br />• 'wA�� <br />R®, <br />TMA <br />TOWER MOUNTED AMPLIFIER <br />TYP <br />TYPICAL <br />UMTS <br />UNIVERSAL MOBILE TELECOMMUNICATIONS SYSTEM <br />W.P. <br />WORK POINT <br />v riz e on <br />3245 158-I I AVENUE NIS 231 <br />BELLEVUE WA 98008 <br />CCROWN <br />C CASTLE <br />1505 WESTLAKE. AVENUE NORTH, SUI"LE 800 <br />SEA iTLE,, WA 98109 <br />roup <br />Engineering * Ddsign * Cam mkv <br />Engineer utg wide Precision, Pace and Passion. <br />1675 Pmtum Avenue <br />Hoffman Estates, IL 60192 <br />T:224.293.6333 F:224293.64-44 <br />wtengmeering.com <br />©COPYRIGHT 2021 TIIE W-T GROUP. LLC <br />VERI'Z,ON SITE NUMBER: 471496 <br />BU #: 824022 <br />FEELY <br />8215 BROADWAY <br />EVERETT,WA 98203 <br />AMENDMENT 60'-0" MONOPOLE. <br />ISSUED FOR: <br />REV <br />Di:j-,', <br />DRAM <br />DESCRIPTION <br />DES./Q. <br />d <br />04/20/21 <br />JF..G <br />P1tE;LIDi1NAR}' <br />JKR <br />0 <br />OS/27/21 <br />Te", <br />FINALS <br />JKR <br />1 <br />BG/D3/_I <br />RS\l <br />RU.VISIONS <br />JKR <br />g. G% <br />o�ans�,¢s.�� <br />TQ <br />d! <br />4a <br />II' IS _1 VIOLATION OF FAw FOR.INY ­-Ni., <br />N UNLESS TFIE} ARL•.AGTL CUNDER'CI-IE DIRECTI <br />OF A LICENSED PROFESSIONAL ENGINEER, <br />TO :ALTER THIS DOCUMEN' <br />SHEET NUMBER: REVISION: <br />T-2 1 <br />