0 • <br /> Terri Jorgenson <br /> From: Terri Jorgenson <br /> Sent: Monday,January 24, 2022 8:44 AM <br /> To: brad@hightrekventures.com; CRISTIE@CROWNFP.COM <br /> Cc: Thad Newport;Tim Markham; Randy Allen <br /> Subject: K2201-001 1425 SE EVERETT MALL WAY <br /> Attachments: 515 - DCDA 2 inch and Larger Service.pdf <br /> Hello Cristie, <br /> I am doing the Public Works review for the fire sprinkler permit submitted for 1425 SE Everett Mall Way(Game On NW) <br /> and our records show the existing backflow device on the fire service is a single check valve in a vault. Anytime a <br /> building with an existing single check backflow device applies for a modification to their sprinkler system the backflow <br /> device must be brought up to the minimum double check detector check valve assembly. I have attached the section <br /> from our Design and Construction Standards and Specifications. Please apply for a Utility Permit and provide a plan <br /> showing the DCDA location and cut sheets for approval. Once we approve the Utility permit for the DCDA we can <br /> approve the corresponding Fire Sprinkler permit. If you have any questions on the backflow device requirements please <br /> contact Tim Markham who is also copied on this email. His direct phone number is 425-257-8833 as well. <br /> Terri Jorgenson <br /> iii <br /> IIIIDevelopment Technician I Permit Services <br /> 425.257.8810 13200 Cedar Street, 2nd Floor, Everett,WA 98201 <br /> EVERETT Phone Hours: M/W/Th: 8 a.m.—12 p.m & 1 p.m.—3 p.m. <br /> everettwa.gov/permits I Facebook I Twitter <br /> Note:Emails and attachments sent to and from the City of Everett are public records and may be subject to disclosure pursuant to the Public <br /> Records Act. <br /> 1 <br />