Laserfiche WebLink
1/28/2020 City of Everett Page 1 <br /> 9:05:29AM <br /> INSPECTION ACTIVITY REPORT <br /> Permit No. E2001-022 Site Address 302 BRIDGEWAY <br /> Applied 1/7/2020 Applicant Lot <br /> Approved 1/7/2020 Owner MCNIEL KAYLEIGH Block <br /> Issued 1/8/2020 Contractor IN-HOUSE ELECTRICAL SRVCS Tract <br /> Parent Permit No. Description 200 AMP PANEL CHANGE <br /> Notes <br /> Scheduled Completed Tune Inspector Result Remarks Inspector's Comments <br /> 1/15/2020 1/15/2020 ELEC 09-FINAL SKB NOT READY eTRAKiT Inspection 1/9/2020 3:34 PM IN-HOUSE <br /> Request ELECTRICAL SRVCS <br /> Description:(360)430-4742 <br /> Contact Name:IN-HOUSE ELECTRICAL <br /> SRVCS <br /> Site Address:302 BRIDGEWAY <br /> Phone:3604304742 <br /> e-Mail:ihepermits@gmail.com <br /> (1/15/2020 11:39 AM SKB) <br /> EMT is not allowed on the service entrance <br /> conductors entering inside the building.It's <br /> a grounding electrode conductor is ran <br /> through metal conduit it must be bonded to <br /> the conduit on both ends. <br /> 1/27/2020 1/27/2020 ADMIN USE HPC APPROVAL <br /> ONLY** <br /> 1/27/2020 1/27/2020 ELEC 09-FINAL SKB APPRVD-PERN eTRAKiT Inspection 1/26/2020 5:54 PM IN-HOUSE <br /> Request ELECTRICAL SRVCS <br /> Contact Name:IN-HOUSE ELECTRICAL <br /> SRVCS <br /> Site Address:302 BRIDGEWAY <br /> Phone:4253209149 <br /> e-Mail:ihepermits@gmail.com <br /> INSP12 CRWS i TEM <br />