NOTES: <br /> I 1. ALL NEW CONDUCTORS TO BE INSTALLED SHALL BE COPPER. <br /> ALL CONDUCTORS SHALL BE THHW, THWN, THWN-2, XHHW,OR XHHW- UNLESS NOTED OTHERWISE. Tii ■ 0 Mobile A . • <br /> 2. CONTRACTOR IS TO HELD VERIFY ALL EXISTING ITEMS SHOWN <br /> ON THE ELECTRICAL ONE-LINE DIAGRAM AND NOTIFY THE <br /> ENGINEER OF ANY DISCREPANCIES. <br /> 3. ALL GROUNDING AND BONDING PER THE NEC 250. 8960 ALDERWOOD ROAD <br /> PORTLAND,OR 9722Q <br /> 4. GENERAL CONTRACTOR SHALL PROVIDE LABELING ACCORDING <br /> TO NEC 110.21. <br /> CROWN <br /> CASTLE <br /> 1505 WESTLAKE AVENUE NORTH,SUITE 800 <br /> SEATTLE,WA 98109 <br /> 11 <br /> /— —1 (TE)RANS UTILITYFORMER COMPANY B+T G ER P <br /> 1717 L_ _J SUITE BOULDER <br /> SUITE 300 <br /> TULSA,OK 74119 <br /> (E) WIRE AND CONDUIT PH:(918)587-4630 <br /> PER UTILITY COMPANY REQUIREMENTS www.btgrp.com <br /> r — — (E) METER ENCLOSURE <br /> FINAL PANEL SCHEDULE <br /> LOAD POLES AMPS BUS AMPS POLES LOAD L - - T-MOBILE <br /> L1 L2 L3 A <br /> (E) WIRE AND CONDUIT SITE NUMBER: E01 A <br /> r - - BU#: 824022 <br /> I I FEELY <br /> o J o / a N DOLE, NEMA ESCON ECT. LOCATION OF 3MAIN <br /> I <br /> BorDINc JUMPER. <br /> 8215 BROADWAY <br /> L — _ _I BONDING <br /> WA 98203 <br /> EXISTING <br /> O (E) WIRE AND CONDUIT 60r-0°MONOPOLE <br /> RATED VOLTAGE:0120/240 0 . 3 PHASE, 4 WIRE BRANCH POLES:012 024 030 042 APPROVED MF'RS <br /> RATED AMPS: 0100 0225 0400 0 . CABINET: ❑SURFACE ❑FLUSH NEMA 01 03R 04X <br /> ❑MAIN LUGS ONLYIMAIN AMPS ❑BREAKER ❑FUSED SWITCH ❑HINGED DOOR ❑KEYED DOOR LATCH (E) 200A, 120/240V, 1463W, NEMA 3R, POWER PROTECTION <br /> ❑FUSED ❑CIRCUIT BREAKER BRANCH DEVICES ❑ TO BE GFCI BREAKERS FULL NEUTRAL BUS GROUND BAR - - ��CABINET (PPC) WITH INTEGRATED MANUAL TRANSFER SWITCH, <br /> ALL BREAKERS MUST BE RATED TO INTERRUPT A SHORT CIRCUIT ISC OF 10,000 AMPS SYMMETRICAL r ✓✓✓ LOAD CENTER, AND FACTORY WIRED GENERATOR INTERFACE FOR <br /> INSTALL A NEW 2P 200A BREAKER E, PORTABLE GENERATOR CONNECTION ISSUED FOR: <br /> • <br /> INSTALL A NEW 1P 20A BREAKER I REV DATE. DAWN DESCRIP IlON DES./QA <br /> INSTALL NEW WIRING FOR NEW HPL3 CABINET WITH (3) 3/0 AWG THWN (COPPER) AND (1) #2G AWG. MINIMUM CONDUIT SIZE TO BE 2". <br /> IF MAIN DISCONNECT CIRCUIT BREAKER IS LESS THAN 150A. REPLACE WITH 2P 200A BREAKER RATED FOR 120/240V. l 1 I A G/3/21 AN PRELIMINARY REVIEW ITS <br /> IF 200A BREAKER WILL NOT PROPERLY FIT IN EXISTING PANEL, REPLACE (E) PANEL WITH SQUARE D PANEL Q012040M20ORB (OR APPROVED EQUAL). 0 7/9/21 YXI CONSTRUCTION YXI <br /> UPGRADE FEEDER WIRES TO MEET AMPACITY IF NEW PANEL IS REQUIRED. . .. <br /> FINAL PANEL DESIGN AND CALCULATIONS FOR WIRE SIZE WERE BASED OFF OF EXISTING DOCUMENTS AND PHOTOS 1 8/11/21 LHT CONSTRUCTION YXI <br /> INSTALL NEW 20A, 1-POLE <br /> BREAKER IN PPC FOR GFCI <br /> INSTALL NEW 200A, 2-POLE <br /> 20/1 BREAKER IN PPC `-' <br /> INSTALL NEW (3) 3/0 CU <br /> -200/2 WITH #2 GROUND IN 2"PVC <br /> L J <br /> RGS FOR DC CABLES co WAS 47< <br /> — — 0.., �. <br /> 100 <br /> NEW HPL3 I I NEW LB3 <br /> 1i <br /> CABINET I CABINET F}T <br /> 3,1 <br /> . J — — — — J L — — — — J <br /> ' <br /> B&T ENGINEERING, INC. <br /> 3425 <br /> Expires 12/31/21 <br /> IT IS A VIOLATION OF LAW FOR ANY PERSON, <br /> UNLESS THEY ARE ACTING UNDER THE DIRECTION <br /> 1 OF A LICENSED PROFESSIONAL ENGINEER, <br /> TO ALTER THIS DOCUMENT. <br /> SHEET NUMBER: • REVISION: <br /> OAC PANEL DETAIL ONE LINE DIAGRAM ■ t <br /> SCALE: NOT TO SCALE }SCALE: NOT TO SCALE ,H1J 1 <br /> 1SI \a <br />