Laserfiche WebLink
GENERAL NOTES GENERAL NOTES INTERCONNECTION NOTES: RVR <br /> Q`'o R <br /> 1. MODULES ARE LISTED UNDER UL 1703 AND CONFORM TO THE STANDARDS. 26. LOAD-SIDE INTERCONNECTION SHALL BE IN ACCORDANCE WITH[NEC CODE] ENGINEERING <br /> 2. INVERTERS ARE LISTED UNDER UL 1741 AND CONFORM TO THE STANDARDS. 27. THE SUM OF THE UTILITY OCPD AND INVERTER CONTINUOUS INPUT MAY NOT EXCEED 120%OF BUSBAR <br /> 3. DRAWINGS ARE DIAGRAMMATIC,INDICATING GENERAL ARRANGEMENT OF THE PV SYSTEM AND THE ACTUAL RATING[NEC CODE]. SYSTEM INFORMATION <br /> S11 t CONDITION MIGHT VARY. 28. WHEN SUM OF THE PV SOURCES EQUALS>100%OF BUSBAR RATING,PV DEDICATED BACKFFED BREAKERS <br /> 4. WORKING CLEARANCES AROUND THE NEW PV ELECTRICAL EQUIPMENT WILL BE MAINTAINED IN MUST BE LOCATED OPPOSITE END OF THE BUS FROM THE UTILITY SOURCE OCPD[NEC CODE]. DC SYSTEM SIZE'3720W <br /> ACCORDANCE WITH NEC CODE. 29. AT MULTIPLE PV OUTPUT COMBINER PANEL,TOTAL RATING OF ALL OVER CURRENT DEVICES SHALL NOT AC SYSTEM SIZE:3800W <br /> 5. ALL GROUND WIRING CONNECTED TO THE MAIN SERVICE GROUNDING IN MAIN SERVICE PANEL/SERVICE EXCEED AMPACITY OF BUSBAR. HOWEVER,THE COMBINED OVER CURRENT DEVICE MAY BE EXCLUDED MODULES: <br /> EQUIPMENT. ACCORDING TO NEC CODE. (12)AXITEC AC-310MH/1205 <br /> 6. ALL CONDUCTORS SHALL BE 600V,75°C STANDARD COPPER UNLESS OTHERWISE NOTED. 30. FEEDER TAP INTER CONNECTION(LOAD SIDE)ACCORDING TO NEC CODE INVERTER: <br /> 7. WHEN REQUIRED, A LADDER SHALL BE IN PLACE FOR INSPECTION IN COMPLIANCE WITH OSHA 31. SUPPLY SIDE TAP INTERCONNECTION ACCORDING TO NEC CODE (A) WITH SERVICE ENTRANCE (1)SOLAREDGE TECHNOLOGIES <br /> REGULATIONS. CONDUCTORS IN ACCORDANCE WITH NEC CODE SE3800H-US(240V) <br /> 8. THE SYSTEM WILL NOT BE INTERCONNH ItD BY THE CONTRACTOR UNTIL APPROVAL FROM THE LOCAL 32. BACK FEEDING BREAKER FOR UTILITY-INTERACTIVE INVERTER OUTPUT IS EXEMPT FROM ADDITIONAL <br /> JURISDICTION AND/OR THE UTILITY. FASTENING[NEC CODE]. ENGINEER OF RECORD <br /> 9. ROOF AT T-FSS POINT SHAI I BE LOCATED IN AREAS THAT DO NOT REQUIRE THE PI a'FMENT OF GROUND <br /> LADDERS OVER OPENINGS SUCH AS WINDOWS OR DOORS,AND LOCATED AT STRONG POINTS OF BUILDING GROUNDING NOTES: <br /> CONSTRUCTION WHERE THE ACCESS POINT DOES NOT CONFLICT WITH OVERHEAD OBSTRUCTIONS SUCH AS <br /> TREES,WIRES OR SIGNS. 33. GROUNDING SYSTEM COMPONENTS SHALL BE US1tU FOR THEIR PURPOSE,AND GROUNDING DEVISES <br /> 10. PV ARRAY COMBINER/JUNCTION BOX PROVIDES TRANSITION FROM ARRAY WIRING TO CONDUIT WIRING EXPOSED TO THE ELEMENTS SHALL BE RATED FOR SUCH USE. <br /> 34. PV EQUIPMENT SHALL BE GROUNDED ACCORDING TO NEC CODE AND MINIMUM NEC TABLE. <br /> EQUIPMENT LOCATION: 35. METAL PARTS OF MODULE FRAMES, MODULE RACKING, AND ENCLOSURES CONSIDERED GROUNDED IN <br /> ACCORD. <br /> 11. ALL EQUIPMENT SHALL MEET MINIMUM SETBACKS AS REQUIRED BY NEC CODE 36. EQUIPMENT GROUNDING CONDUCTORS SHALL BE SIZED ACCORDING TO NEC CODE AND MICRO INVERTER <br /> 12. WIRING SYSTEMS INSTALLED IN DIRECT SUNLIGHT MUST BE RATED FOR EXPECTED OPERATING MANUFACTURER'S INSTRUCTIONS. <br /> TEMPERATURE AS SPECIFIED BY NEC CODE AND NEC TABLES. 37. EACH MODULE WILL BE GROUNDED USING WEEB GROUNDING CLIPS AS SHOWN IN MANUFACTURER <br /> 13. JUNCTION AND PULL BOXES PERMIT 1 tU INSTALLED UNDER PV MODULES ACCORDING TO NEC CODE. DOCUMENTATION AND APPROVED BY THE AHJ.IF WEEBS ARE NOT USED,MODULE GROUNDING LUGS MUST <br /> 14. ADDITIONAL AC DISCONNECT(S)SHALL BE PROVIDED WHERE THE INVERTER IS NOT WITHIN SIGHT OF THE BE INSTALLED AT THE SPECIFIED GROUNDING LUG HOLES PER THE MANUFACTURERS INSTALLATION <br /> AC SERVICING DISCONNECT. REQUIREMENTS. <br /> 15. ALL EQUIPMENT SHALL BE INSTALLED ACLESIBLE TO QUALIFIED PERSONNEL ACCORDING TO NEC 38. THE GROUNDING CONNECTION TO A MODULE SHALL BE ARRANGED SUCH THAT THE REMOVAL OF A MODULE <br /> APPLICABLE CODES. DOES NOT INTERRUPT A GROUNDING CONDUCTOR TO ANOTHER MODULE. <br /> 16. ALL COMPONENTS ARE LISTED FOR THEIR PURPOSE AND RATED FOR OUTDOOR USAGE WHEN APPROPRIATE 39. GROUNDING AND BONDING CONDUCTORS,IF INSULATED,SHALL BE COLORED GREEN OR MARKED GREEN IF <br /> #4 AWG OR LARGER[NEC CODE] <br /> STRUCTURAL NOTES: 40. THE GROUNDING ELECTRODE SYSTEM COMPLIES WITH NEC CODE.IF EXISTING SYSTEM IS INACCESSIBLE, <br /> OR INADEQUATE,A GROUNDING ELECTRODE SYSTEM PROVIDED ACCORDING TO NEC CODE AND AHJ. <br /> 17. RACKING SYSTEM & PV ARRAY WILL BE INSTALLED ACCORDING TO CODE-COMPLIANT INSTALLATION 41. GROUND-FAULT DETECTION SHALL COMPLY WITH NEC CODE IN GENERAL AND NEC CODE SPECIFICALLY. <br /> MANUAL TOP CLAMPS REQUIRE A DESIGNATED SPACE BETWEEN MODULES,AND RAILS MUST ALSO EXTEND 42. DISCONNECTION AND OVER-CURRENT PROTECTION NU I ES: A ale <br /> A MINIMUM DISTANCE BEYOND EITHER EDGE OF THE ARRAY/SUBARRAY, ACCORDING TO RAIL 43. DISCONNECTING SWITCHES SHALL BE WIRED SUCH THAT WHEN THE SWITCH IS OPENED THE CONDUCTORScor <br /> MANUFACTURER'S INSTRUCTIONS. REMAINING ENERGIZED ARE CONNECTED TO THE TERMINALS MARKED"LINE SIDE"(TYPICALLY THE UPPER energy today <br /> 18. JUNCTION BOX WILL BE INSTALLED PER MANUFACTURER'S SPECIFICATIONS.IF ROOF-PENETRATING TYPE,IT TERMINALS). __ ea, e0,0, ,,;:vrhiL° <br /> SHALL BE FLASHED&`'+FAT FD PER LOCAL REQUIREMENTS. 44. DISCONNECTS TO BE ACCESSIBLE TO QUALIFIED UTILITY PERSONNEL, BE LOCKABLE, AND BE A CUSTOMER INFORMATION <br /> 19. ROOFTOP PENETRATIONS FOR PV RACEWAY WILL BE COMPLETED AND SEALED WITH APPROVED CHEMICAL VISIBLE-BREAK SWITCH <br /> SEALANT PER CODE BY A LICENSED CONTRALI UR 45. RAPID SHUTDOWN OF ENERGIZED CONDUCTORS BEYOND 10 FT OF PV ARRAY OR 5 FT INSIDE A BUILDING <br /> 20. ALL PV RELATED ROOF ATTACHMENTS TO BE SPACED NO GREATER THAN THE SPAN DISTANCE SPECIFIED BY WITHIN 10 SECONDS.CONTROLLED CONDUCTORS 5.30V AND 5_240VA[NEC CODE].LOCATION OF LABEL NAME&ADDRESS: <br /> THE RACKING MANUFACTURER. ACCORDING TO AEU. RITA BLANKENSHIP <br /> 21. WHEN POSSIBLE,ALL PV RELATED RACKING ATTACHMENTS WILL BE STAGGERED AMONGST THE ROOF 46. ALL OCPD RATINGS AND TYPES SPECIFIED ACCORDING TO NEC CODE. 7611 EASY ST,EVERETT,WA 98203. <br /> FRAMING MEMBERS. 47. MICRO INVERTER BRANCHES CONNECTED TO A SINGLE BREAKER OR GROUPED FUSES IN ACCORDANCE WITH <br /> NEC CODE.2.6.7 IF REQUIRED BY AHJ,SYSTEM WILL INCLUDE ARC-FAULT CIRCUIT PROTECTION ACCORDING 47°5543.73"N 122°13'43.50"W <br /> IRING&CONDUIT NOTES: TO NEC CODE AND UL1699B. APN:003-927-000-002-00 <br /> 22. ALL CONDUIT AND WIRE WILL BE LISTED AND APPROVED FOR THEIR PURPOSE. CONDUIT AND WIRE AHJ:WA-CITY OF EVERETT <br /> SPECIFICATIONS ARE REED ON MINIMUM CODE REQUIREMENTS AND ARE NOT MEANT TO LIMIT UP-SIZING. <br /> 23. CONDUCTORS SIZED ACCORDING TO NEC CODE. <br /> 24. DC WIRING UNITED TO MODULE FOOTPRINT.MICRO INVERTER WIRING SYSTEMS SHALL BE LOCATED AND <br /> SECURED UNDER THE ARRAY WITH SUITABLE WIRING CLIPS. PROJECT NUMBER:SETI-000473 <br /> 25. AC CONDUCTORS COLORED OR MARKED AS FOLLOWS:PHASE A OR Ll-BLACK PHASE B OR L2-RED,OR <br /> OTHER CONVENTION IF THREE PHASE PHASE C OR L3-BLUE,YELLOW,ORANGE**,OR OTHER CONVENTION <br /> NEUTRAL-WHITE OR GREY IN 4-WIRE DELTA CONNECTED SYSTEMS THE PHASE WITH HIGHER VOLTAGE TO GENERAL NOTES <br /> BE MARKED ORANGE[NEC CODE]. <br /> DESIGNER/CHECKED BY: <br /> LS/RE <br /> SCALE:AS NOTED PAPER SIZE:17"x11" <br /> DATE:02/25/2020 REV:A PV-2.0 <br />