• • <br /> Ms. Finsch <br /> Tiscareno Associates <br /> Plan Check Number: B1801-032, First Review <br /> March 13, 2018 <br /> considering the actual weight of the planters with a superimposed live load of 20 psf. The <br /> loading criteria on Sheet S001 should be revised. See IBC Section 1607.12.3.1. <br /> 5. Note 10 on Sheets S211a through S211c state a shear load as"[2000LBS] The magnitude of <br /> the load and units (i.e., total load or load per-linear-foot) should be verified. A detail should be <br /> provided in the drawings showing the required connections between the trusses, roof <br /> diaphragm, and shear wall. See IBC Sections 1603.1.8. <br /> 6. Calculation page SC115 specifies 2x8 framing that is Grade DFL #1. The table of solid wood <br /> lumber in the "Wood Framing'section of the Structural General Notes on Sheet 5003 does not <br /> include this size and grade, and should be revised. See IBC Section 1072.1. <br /> 7. Sheet A208 and Sections 14/A412 and 15/A412 appear to show steel-framed canopies on at <br /> Grids S-A/S-7 — S-8 and S-C/S-7 — S-8. Documentation substantiating the design of the <br /> canopies should be submitted for review. Where the canopy relies on the main building <br /> structure for support, documentation substantiating the design of the supporting framing and <br /> connections should be submitted for review. See IBC Sections 107.2.1, 1603.1, 1604.1, <br /> 1604.4, 1609.1.1, and 1613.1, and ASCE 7-10 Sections 1.4 and 12.1.3. <br /> 8. Sheet S207a shows six architectural columns near Grid S-A that extend to and partially support <br /> steel-framed canopies at the fourth story. See Sheet A211a and the isometric views on Sheet <br /> A900. Documentation substantiating the design of the canopies should be submitted for <br /> review. Where the canopy relies on the main building structure for support, documentation <br /> substantiating the design of the supporting framing and connections should be submitted for <br /> review. See IBC Sections 107.2.1, 1603.1, 1604.1, 1604.4, 1609.1.1, and 1613.1, and ASCE 7- <br /> 10 Sections 1.4 and 12.1.3. <br /> 9. The project includes cantilever canopies in the parking area per Sheet A100b. The design for <br /> the canopies should be included in the structural drawings. Calculations substantiating the <br /> design should be submitted for review. See IBC Sections 1603.1 and 1604.1. <br /> 10.The vertical design of all gravity and lateral framing shall include the vertical earthquake <br /> component per ASCE 7-10 Sections 12.4.1, 12.4.2, and 12.4.2.2. See other comments below <br /> regarding the design of structural framing and systems throughout the structure. See IBC <br /> Section 1613.1. <br /> Foundation System: <br /> 11. Note 5 on Sheets S207a and S207b specifies the top of footings as X'-X". It appears an actual <br /> elevation is intended. The note should be revised as needed. See IBC Section 1603.1. <br /> 12.The"Soils and Foundations" section of the Structural General Notes on Sheet S001 indicates <br /> that the foundation system consists of shallow footings and slabs-on-grade. See also Note 6 <br /> on Sheets S207a and S207b. However, the foundation sections on Sheets S301 and S302 <br /> indicate that portions of the foundation system may be supported on piles. It is anticipated <br /> that rigid ground improvements may be intended. Foundations that do not effectively bear on <br /> the soil do not qualify as shallow foundations per IBC Section 1809.2. Foundations supported <br /> e3of11 <br /> CITY OF EVERETT • 3200 Cedar Street • Everett, WA 98201 • (425) 257-8810 • Fax(425) 257-8857 <br />