R301 CLIMATE ZONE
<br />THIS PLAN IS DESIGNED FOR CLIMATE ZONE 5 AND MARINE 4 PER TABLE R301.1, 2015 WASHINGTON STATE
<br />ENGERY CODE.
<br />R402.2 FENESTRATION PRESCRIPTIVE
<br />R402.3 Fenestration (Prescriptive). In addition to the requirements of Section R402, fenestration shall comply with Sections
<br />R402.3.1 through R402.3.6.
<br />R402.3.1 U-factor. An area -weighted average of fenestration products shall be permitted to satisfy the U-factor requirements.
<br />R402.3.2 Glazed fenestration SHGC. An area -weighted average of fenestration products more than 50 percent glazed shall be
<br />permitted to satisfy the SHGC requirements.
<br />R402.3.3 Glazed fenestration exemption. Up to 15 square feet (1.4 m2) of glazed fenestration per dwelling unit shall be
<br />permitted to be exempt from U-factor and SHGC requirements in Section R402.1.1. This exemption shall not apply to the U-
<br />factor alternative approach in Section R402.1.3 and the total UA alternative in Section R402.1.4.
<br />R402.3.4 Opaque door exemption. Oneside-hinged o a ue door assembly u to 24 square feet 2.22 m2 in area is exempted
<br />popaque Y p q ( ) p
<br />from the U-factor requirement in Section R402.1.1. This exemption shall not apply to the U-factor alternative approach in Section
<br />R402.1.3 and the total UA alternative in Section R402.1.4
<br />R404.1 LIGHTING EFFICACY
<br />MIN. OF 75%OF LAMPS IN PERMANENTLY INSTALLED FIXTURES SHALL BE HIGH EFFICACY LAMPS
<br />M 1507 MECHANICAL VENTILATION
<br />M1507.3.1 SYSTEM DESIGN.
<br />EACH DWELLING UNIT OR GUESTROOM SHALL BE EQUIPPED WITH A VENTILATION SYSTEM COMPLYING WITH
<br />SECTION M1507.3.4, M1507.3.5, M1507.3.6 OR M1507.3.7. COMPLIANCE IS ALSO PERMITTED TO BE DEMONSTRATED
<br />THROUGH COMPLIANCE WITH THE INTERNATIONAL MECHANICAL CODE.
<br />M1507.3.2 CONTROL AND OPERATION.
<br />1. LOCATION OF CONTROLS. CONTROLS FOR ALL VENTILATION SYSTEMS SHALL BE READILY ACCESSIBLE BY THE
<br />OCCUPANT.
<br />2. INSTRUCTIONS, OPERATING INSTRUCTIONS FOR WHOLE -HOUSE VENTILATION SYSTEMS SHALL BE PROVIDED TO
<br />THE OCCUPANT BY THE INSTALLER OF THE SYSTEM.
<br />3. LOCAL EXHAUST SYSTEMS. LOCAL EXHAUST SYSTEMS SHALL BE CONTROLLED BY MANUAL SWITCHES,
<br />DEHUMIDISTATS, TIMERS, OR OTHER APPROVED MEANS,
<br />4. CONTINUOUS WHOLE -HOUSE VENTILATION SYSTEMS. CONTINUOUS WHOLE -HOUSE VENTILATION SYSTEMS SHALL
<br />OPERATE CONTINUOUSLY. EXHAUST FANS, FORCED -AIR SYSTEM FANS, OR SUPPLY FANS SHALL BE EQUIPPED WITH
<br />"FAN ON" AS OVERRIDE CONTROLS. CONTROLS SHALL BE CAPABLE OF OPERATING THE VENTILATION SYSTEM
<br />WITHOUT ENERGIZING OTHER ENERGY -CONSUMING APPLIANCES, A LABEL SHALL BE AFFIXED TO THE CONTROLS
<br />THAT READS"WHOLE HOUSE VENTILATION (SEE OPERATING INSTRUCTIONS)."
<br />5. INTERMITTENT WHOLE -HOUSE VENTILATION SYSTEMS. INTERMITTENT WHOLE -HOUSE VENTILATION SYSTEMS
<br />SHALL COMPLY WITH THE FOLLOWING:
<br />5.1. THEY SHALL BE CAPABLE OF OPERATING INTERMITTENTLY AND CONTINUOUSLY.
<br />5.2. THEY SHALL HAVE CONTROLS CAPABLE OF OPERATING THE EXHAUST FANS, FORCED -AIR SYSTEM FANS, OR
<br />SUPPLY FANS WITHOUT ENERGIZING OTHER ENERGY -CONSUMING APPLIANCES.
<br />5.3. THE VENTILATION RATE SHALL BE ADJUSTED ACCORDING TO THE EXCEPTION IN SECTION 403.8.5.1.
<br />5.4. THE SYSTEM SHALL BE DESIGNED SO THAT IT CAN OPERATE AUTOMATICALLY BASED ON THE TYPE OF CONTROL
<br />TIMER INSTALLED.
<br />5.5. THE INTERMITTENT MECHANICAL VENTILATION SYSTEM SHALL OPERATE AT LEAST ONE HOUR OUT OF EVERY
<br />FOUR.
<br />5.6. THE SYSTEM SHALL HAVE A MANUAL CONTROL AND AUTOMATIC CONTROL, SUCH AS A 24-HOUR CLOCK TIMER.
<br />5.7. AT THE TIME OF FINAL INSPECTION, THE AUTOMATIC CONTROL SHALL BE SET TO OPERATE THE WHOLE -HOUSE
<br />FAN ACCORDING TO THE SCHEDULE USED TO CALCULATE THE WHOLE -HOUSE FAN SIZING.
<br />M1507.3.4 WHOLE -HOUSE VENTILATION USING EXHAUST FANS.
<br />THIS SECTION ESTABLISHES MINIMUM PRESCRIPTIVE REQUIREMENTS FOR WHOLE -HOUSE VENTILATION SYSTEMS
<br />USING EXHAUST FANS. A SYSTEM WHICH MEETS ALL THE REQUIREMENTS OF THIS SECTION SHALL BE DEEMED TO
<br />SATISFY THE REQUIREMENTS FOR A WHOLE -HOUSE VENTILATION SYSTEM.
<br />M1507.3.4.1 WHOLE -HOUSE VENTILATION FANS.
<br />EXHAUST FANS PROVIDING WHOLE -HOUSE VENTILATION SHALL HAVE A FLOW RATING AT 0.25 INCHES WATER GAUGE
<br />AS SPECIFIED IN TABLE M1507.3.3(1). MANUFACTURERS' FAN FLOW RATINGS SHALL BE DETERMINED ACCORDING TO
<br />HVI 916 OR AMCA 210.
<br />M1507.3.4.2 FAN NOISE.
<br />WHOLE -HOUSE FANS LOCATED 4 FEET OR LESS FROM THE INTERIOR GRILLE SHALL HAVE A SONE RATING OF 1.0 OR
<br />LESS MEASURED AT 0.1 INCHES WATER GAUGE. MANUFACTURER'S NOISE RATINGS SHALL BE DETERMINED AS PER
<br />HVI 915 (MARCH 2O09). REMOTELY MOUNTED FANS SHALL BE ACOUSTICALLY ISOLATED FROM THE STRUCTURAL
<br />ELEMENTS OF THE BUILDING AND FROM ATTACHED DUCT WORK USING INSULATED FLEXIBLE DUCT OR OTHER
<br />APPROVED MATERIAL.
<br />M1507.3.4.3 FAN CONTROLS.
<br />THE WHOLE -HOUSE VENTILATION FAN SHALL MEET THE REQUIREMENTS OF SECTION M1507.3.2 AND M1507.3.2.1
<br />M1507.3.4.4 OUTDOOR AIR INLETS.
<br />OUTDOOR AIR SHALL BE DISTRIBUTED TO EACH HABITABLE SPACE BY INDIVIDUAL OUTDOOR AIR INLETS. WHERE
<br />OUTDOOR AIR SUPPLIES ARE SEPARATED FROM EXHAUST POINTS P MADE T 0 US 0 S BY DOORS, PROVISIONS SHALL BE M D 0
<br />ENSURE AIR FLOW BY INSTALLATION OF DISTRIBUTION DUCTS, UNDERCUTTING DOORS, INSTALLATION OF GRILLES,
<br />TRANSOMS, OR SIMILAR MEANS. DOORS SHALL BE UNDERCUT TO A MINIMUM OF 1/21NCH ABOVE THE SURFACE OF
<br />THE FINISH FLOOR COVERING.
<br />INDIVIDUAL ROOM OUTDOOR AIR INLETS SHALL:
<br />1. HAVE CONTROLLABLE AND SECURE OPENINGS;
<br />2. BE SLEEVED OR OTHERWISE DESIGNED SO AS NOT TO COMPROMISE THE THERMAL PROPERTIES OF THE WALL OR
<br />WINDOW IN WHICH THEY ARE PLACED;
<br />3. PROVIDE NOT LESS THAN 4 SQUARE INCHES OF NET FREE AREA OF OPENING FOR EACH HABITABLE SPACE. ANY
<br />INLET OR COMBINATION OF INLETS WHICH PROVIDE 10 CFM AT 10 PASCALS ARE DEEMED EQUIVALENT TO 4 SQUARE
<br />INCHES NET FREE AREA.
<br />INLETS SHALL BE SCREENED OR OTHERWISE PROTECTED FROM ENTRY BY LEAVES OR OTHER MATERIAL. OUTDOOR
<br />AIR INLETS SHALL BE LOCATED SO AS NOT TO TAKE AIR FROM THE FOLLOWING AREAS:
<br />1. CLOSER THAN 10 FEET FROM AN APPLIANCE VENT OUTLET, UNLESS SUCH VENT OUTLET IS 3 FEET ABOVE THE
<br />OUTDOOR AIR INLET.
<br />2. WHERE IT WILL PICK UP OBJECTIONABLE ODORS, FUMES OR FLAMMABLE VAPORS.
<br />3. A HAZARDOUS OR UNSANITARY LOCATION.
<br />4. A ROOM OR SPACE HAVING ANY FUEL -BURNING APPLIANCES THEREIN.
<br />5. CLOSER THAN 10 FEET FROM A VENT OPENING OF A PLUMBING DRAINAGE SYSTEM UNLESS THE VENT OPENING IS
<br />AT LEAST 3 FEET ABOVE THE AIR INLET.
<br />6. ATTIC, CRAWL SPACES, OR GARAGES.
<br />TABLE 1507.3.3 (1) CONTINUOUS WHOLE HOUSE MECHANICAL VENTILATION SYSTEM AIRFLOW RATES
<br />FLOOR AREA
<br />BEDROOMS*
<br />(SQ. FT.)
<br />0-1
<br />2-3
<br />4-5
<br />6-7
<br />>7
<br />< 1500
<br />30
<br />45
<br />60
<br />75
<br />90 (IN
<br />1501-3000
<br />45
<br />60
<br />75
<br />90
<br />105
<br />3001-4500
<br />60
<br />75
<br />90
<br />105
<br />120
<br />4501-6000
<br />75
<br />90
<br />105
<br />120
<br />135
<br />6001-7500
<br />90
<br />105
<br />120
<br />135
<br />150
<br />>7500
<br />105
<br />120
<br />135
<br />150
<br />165
<br />TABLE 1507.3.3 (2) INTERMITTENT WHOLE HOUSE MECHANICAL VENTILATION RATE FACTORS
<br />RUN-TIME PERCENTAGE IN
<br />EACH
<br />25% 33% 50%
<br />66%
<br />75%
<br />100%
<br />FACTOR
<br />4 3 2
<br />1.5
<br />1.3
<br />1.0
<br />THIS PLAN USES AN INTERMITTENT WHOLE HOUSE VENTILATION SYSTEM WITH TIMER(s),
<br />TOTAL HEATED FLOOR AREA = 3026 SQ. FT. BEDROOMS = 5
<br />WHOLE HOUSE VENTILATION SIZE = 90 CFM X 3 (25% PER 4-HOUR) = 270 TOTAL CFM FAN(s) SIZE.
<br />INTEGRATED FURNACE OUTSIDE AIR INTAKE WITH EXHAUST FANS AS NOTED IN PLAN.
<br />MULTIPLE WHOLE HOUSE VENTILATION FANS TO BE INTERCONNECTED TO OPERATE SIMULTANEOUSLY
<br />2015 WASHINGTON STATE ENERGY CODE
<br />MISC. ENERGY CODE NOTES
<br />A permanent certificate shall be completed and posted on or within three feet of the electrical distribution panel by the
<br />builder or registered design professional. The certificate shall be completed by the builder or registered design
<br />professional and shall not cover or obstruct the visibility of the circuit directory label, service disconnect label or other
<br />required labels. The certificate shall list the predominant R-values of insulation installed in or on ceiling/roof, walls,
<br />foundation slab below -grade wall and/or floor and du iconditioned-
<br />( g ) cts outside spaces; U factors for fenestration and the
<br />solar heat gain coefficient (SHGC) of fenestration, and the results from any required duct system and building envelope
<br />air leakage testing done on the building. Where there is more than one value for each component, the certificate shall list
<br />the value covering the largest area. The certificate shall list the types and efficiencies of heating, cooling and service
<br />water heating equipment.
<br />The building or dwelling unit shall be tested and verified as having an air leakage rate of not exceeding 5 air changes
<br />per hour. Testing shall be conducted with a blower door at a pressure of 0.2 inches w.g. (50 Pascals).Where
<br />required by the code official, testing shall be conducted by an approved third party. A written report of the results of
<br />the test shall be signed by the party conducting the test and provided to the code official. Testing shall be performed
<br />at any time after creation of all penetrations of the building thermal envelope.
<br />Where the primary heating system is a forced -air furnace, at least one thermostat per dwelling unit shall be capable of
<br />controlling the heating and cooling system on a daily schedule to maintain different temperature set points at different
<br />times of the day. Specifics and Exceptions see SEC.
<br />ALL DUCTWORK SHALL BE SEALED AND TESTED PER R403.2.2.
<br />WINDOW AND DOOR HEADERS SHALL BE INSULATED WITH R-10 RIGID INSULATION EXCEPT IN SITUATIONS
<br />WHERE STRUCTURAL BEAM SIZE REQUIREMENTS OVERRIDE.
<br />ALL APPLIANCES SHALL BE U.L. LISTED.
<br />WHOLE HOUSE FANS
<br />Whole house ventilation fans shall be installed so as to run simultaniously.
<br />EXHAUSTFANS
<br />Exhaust fans to terminate at building exterior with clearances per SRC
<br />M1506.2 (min. 3 ft to openings) and for clothes dryer vent terminations to be per M1502.3 (3 ft to bldg. openings).
<br />ALL FENESTRATION SHALL BE NFRC CERTIFIED.
<br />?x6 TOP PLATES
<br />. W. B.
<br />;ID R-10 INSULATION
<br />1LED IN CAVITY BETWEEN
<br />ER AND INTERIOR G.W.B.
<br />ER PER PLAN
<br />VVII.UOW, FINISH &TRIMS
<br />PER MISC. DETAILS
<br />HEADER INSULATION
<br />1 1/2" = V-0"
<br />PRESCRIPTIVE ENERGY CODE COMPLIANCE
<br />Prescriptive Energy Code Compliance for All Climate i
<br />P 9y P
<br />a e Zones n Washington
<br />Project Information
<br />Contact information
<br />a1 tCfIAUUE
<br />This project will use the requirements of the Prescriptive Path below and incorporate the
<br />the minimum values listed. In addition, based on the size of the structure, the appropriate
<br />number of additional credits are checked as chosen by the permit applicant.
<br />All Climate Zones
<br />R-Valuea
<br />U-Factors
<br />Fenestration U-Factor
<br />n/a
<br />0.30
<br />Skylight LI-Factor
<br />n/a
<br />0.50
<br />Glazed Fenestration SHGCb'e'
<br />n/a
<br />n/a
<br />Ceilingk
<br />49'
<br />0.026
<br />Wood Frame Walll,m,n
<br />21 int
<br />0.056
<br />Mass Wall R-Value'
<br />21/21'
<br />0.056
<br />Floor
<br />309
<br />0.029
<br />Below Grade Wall° "
<br />10/15/21 1nt + TB
<br />0.042
<br />Slab° R-Value & Depth
<br />1 10, 2 ft I
<br />n/a
<br />I *Table R402.1.1 and Table R402.1.3 Footnotes included on Page 2.
<br />Table R406.2 Summary
<br />Option Description Credit(s)
<br />la
<br />JEfficient Building Envelope la
<br />0.5
<br />lb
<br />Efficient Building Envelope I
<br />1.0
<br />1c
<br />Efficient Building Envelope 1c
<br />2.0
<br />1d
<br />Efficient Building Envelope 1d
<br />0.5
<br />2a
<br />Air Leakage Control and Efficient Ventilation 2a
<br />0.5
<br />2b.'
<br />Air Leakage Control and Efficient Ventilation 2b
<br />1.0
<br />2c
<br />Air Leakage Control and Efficient Ventilation 2c
<br />1.5
<br />3a
<br />High Efficiency HVAC 3a
<br />1.0
<br />3b
<br />High Efficiency HVAC 3b
<br />1.0
<br />3c
<br />High Efficiency HVAC 3c
<br />1.5
<br />3d
<br />High Efficiency HVAC 3d
<br />1.0
<br />4
<br />High Efficiency HVAC Distribution System
<br />To
<br />5a
<br />Efficient Water Heating 5a
<br />0.5
<br />5b
<br />Efficient Water Heating 5b
<br />1.0
<br />5c
<br />Efficient Water Heating 5c
<br />1.5
<br />5d
<br />Efficient Water Heating 5d `
<br />0.5
<br />6
<br />lRenewable Electric Energy
<br />0.5
<br />11
<br />❑
<br />❑
<br />1.0
<br />P1 1.0
<br />11
<br />El
<br />0 1.5'
<br />*1200 kwh 0.0'
<br />Total Credits 3.50
<br />*Please refer to Table R406.2 for complete option descriptions
<br />FENESTRATION CALCULATIONS ENERGY CREDITS
<br />VERTICAL GLAZING 318 SF 3a HIGH EFFICIENCY HVAC EQUIPMENT 3a: 1.0
<br />LESS EXEMPT GLAZING -00 SF Gas, propane or oil -fired furnace with minimum AFUE of 9 %, or
<br />Gas, propane or oiled -fired boiler with minimum I F'UE of 92%'
<br />PLUS GLAZED DOORS 124 SF
<br />PLUS OTHER EXTERIOR DOORS 21 SF To qualify to claim this credit, the building permit €'a�yina shall specify the option
<br />being selected and shall specify the heating equipment type and the minimum
<br />TOTAL FENESTRATION: 463 SF I equipment efficienc
<br />NOTE:
<br />SEE SHEETS A7 FOR
<br />ADDITIONAL INSULATION
<br />LOCATIONS AND DETAILS,
<br />4 HIGH EFFICIENCY MAC DISTRIBUTION SYSTEM:
<br />All heating and cooling system components installed inside the conditioned space.
<br />This includes all equipment and distribution system components such as forced air
<br />ducts, hydronic piping, hydronic floor heating loop, convectors and radiators: All
<br />combustion equipment shall be direct vent or sealed combustion.
<br />For'- forced air ducts: A maximum of 10 linear feet ;of return ducts and 5 linear feet o
<br />supply ducts may be located outside the conditioned space. All metallic ducts located
<br />outside the conditioned space inust have both transverse and longitudinal joints sealed
<br />with mastic. If flex ducts are used. they cannot contain splices. flex duct connections
<br />must be made with nylon straps and installed using a plastic strapping tensioning tool.
<br />Ducts located outside the conditioned space must be insulated to a ininiinum ofR-8.
<br />Locating system components in conditioned crawl spaces is not permitted under this
<br />option.
<br />Electric resistance heat and ductless Beat pumps are not permitted under this option.
<br />Direct combustion heating equipmentwith AFUE less than 80% is not pemn tted
<br />under this option
<br />To qualify to claim this credit, the building permit drawings shall specify the option
<br />being selected and shall specify the heating equipment type and shall show the
<br />1.0
<br />5c
<br />EFFICIENT WATER HEATING 5c
<br />1.5
<br />Water heating system shall include one of the following:
<br />Gas, propane or oil water heater with a minimum EF of 0.91
<br />_
<br />or
<br />Solar water heating supplementing a minimum standard water Beater. Solar water
<br />heating will provide a rated minimum savings of 85 therms or 2000 k'%7h based on the
<br />Solar Rating and Certification Corporation (SRCC) Annual Performance ofOG-300
<br />Certified Solar Water Heating, Systems
<br />or
<br />Electric heat prune water treater with a minimum EF of 2..0 and iueetrrtg the standards
<br />of TEEA's Noithern Climate Specifications for Heat Pump Water Heaters
<br />To qualify to clam this credit, the building permit drawings shall specify the option
<br />being selected and shall specify the eater heater equipment type and the minimum
<br />equipment efficiency and. for solar water heating system, the calculation of the
<br />minimum energy savings
<br />For SI: 1 foot .= 304.8 mm, ci .= continuous insulation, int .= intermediate framing.
<br />a R-values are minimums. U-factors and SHGC are maximums. When insulation is installed in a cavity which is
<br />less than the label or design thickness of the insulation the compressed R-value of the insulation from
<br />a g p
<br />Appendix Table A101.4 shall not be less than the R-value specified in the table.
<br />b The fenestration U-factor column excludes skylights. The SHGC column applies to all glazed fenestration.
<br />"10/15/21.+TB" means R-10 continuous insulation on the exterior of the wall, or R-15 on the continuous
<br />insulation on the interior of the wall, or R-21 cavity insulation plus a thermal break between the slab and the
<br />basement wall at the interior of the basement wall. 10 15 21. TB shall be permitted to be met with R-13
<br />/ /
<br />cavity insulation on the interior of the basement wall plus R-5 continuous insulation on the interior or exterior
<br />of the wall. "10/13" means R-10 continuous insulation on the interior or exterior of the home or R-13 cavity
<br />insulation at the interior of the basement wall. "TB" means thermal break between floor slab and basement
<br />wall.
<br />d R-10 continuous insulation is required under heated slab on grade floors. See R402.2.9.1.
<br />e There are no SHGC requirements in the Marine Zone.
<br />f Reserved.
<br />' Reserved.
<br />h Reserved.
<br />The second R-value applies when more than half the insulation is on the interior of the mass wall.
<br />Reserved.
<br />k For single rafter- or joist -vaulted ceilings, the insulation may be reduced to R-38.
<br />IReserved.
<br />m Int. (intermediate framing) denotes standard framing 16 inches on center with headers insulated with a
<br />minimum of R-10 insulation.
<br />Table R402.1.3 Footnote
<br />a Nonfenestration U-factors shall be obtained from measurement, calculation or an approved source or as
<br />specified in Section R402.1.3.
<br />HEATING SYSTEM SIZE
<br />Hea in Simple S s p t a v t ern Size:
<br />e Washington State
<br />This heating system sizing calculator is based on the Prescriptive Requirements of the 2015 Washington State Energy Code (WSEC) and ACCA
<br />Manuals J and S. This calculator will calculate heatingloads only. ACCA procedures for sizing cooling systems should be used to determine cooling
<br />. P X
<br />loads.
<br />Please fill out all of the green ow g drop -downs ns and boxes that are applicable to your project. As you make selections in the drop downs for each section,
<br />some values will be calculated for you. If you do not see the selection you need in the drop -down options, please call the WSU Energy Extension
<br />Program at (360) 956-2042 for assistance.
<br />(07101113)
<br />r
<br />0
<br />z�
<br />00
<br />Z a
<br />Q U
<br />Y 2 p,
<br />CL
<br />W�-
<br />� 0�
<br />O _
<br />J
<br />` n 0)
<br />U rn
<br />M CO �
<br />Z 00 N
<br />LLi � '�
<br />ad o
<br />W m
<br />-J o
<br />LU a
<br />H
<br />_5
<br />to,r
<br />w a
<br />r�
<br />.f P Ja
<br />Z m 2 2 N 2 C D 0
<br />~Z~Y�cNO3 aJi^�mbaaici'C
<br />e
<br />a
<br /><M m°2Fc°��.�.�01cVEWco
<br />C 0 0
<br />i-IL
<br />2: Q .Q N o f O G (6 O O a W O
<br />LD 071
<br />.00 N U 2 Y) C l0 S-. m`
<br />1i '-' a T W
<br />of Z O „j d_ON_ N O C
<br />O
<br />w
<br />O N
<br />O LII g F C
<br />0 V
<br />W 5 w o
<br />l0 N�
<br />E
<br />�y�� W��o��W
<br />H ZaE
<br />UJ
<br />UJ
<br />CN
<br />LU
<br />••
<br />•
<br />UJ
<br />•
<br />UJ
<br />ui
<br />UJ
<br />0#4
<br />LU
<br />•
<br />V)
<br />00
<br />•
<br />(y)
<br />PROJECT NO.
<br />200202
<br />DESIGNED BY
<br />TL
<br />DRAWN BY
<br />TL & RM
<br />CHECKED BY
<br />TL
<br />SHEET NO.
<br />A2
<br />PRINT DATE 9/23/2020 8:15:59 AM
<br />
|