5UILDING CODE <br />20 16 INTERNATIONAL BUILDING CODE <br />FLOOR LOAD <br />DEAD LOAD, 12 p5f <br />LIVE LOAD. 40 p5T' <br />ROOF� LOAD <br />DEAD LOAD: 15 p5f <br />I'LAT ROOF SNOW LOAD: 25 p5f <br />SNOW EXPOSURE FACTOR (Cc): 1. 1 <br />SNOW LOAD IMPORTANCE FACTOR (15). 1.0 <br />THERMAL FACTOR (Ct):, 1. 1 <br />WIND DE51GN DATA <br />I � BASIC WIND SPEED: I 10 MPH <br />2. WIND IMPORTANCE FACTOR (1w)- I �O <br />BUILDING CATEGORY: �l <br />3. WIND FXPO5URE:5 <br />4� Kzt = 1.38 <br />5. INTERNAL PRESSURE COFf FICIENT: NA <br />G. APPLICA5LF_ WIND PRESSURE FOR <br />COMPONENTS AND CLADDING: NA <br />5E51MIC DESIGN DATA <br />I. SEISMIC IMPORTANCE- FACTOR. 1.0 <br />SEISMIC USE GROUP-. 1 <br />2. SPECTRAL RESPONSE ACCELERATION (55): 125.2% G <br />3� 51TE CLASS: D (ASSUMED) <br />4. SPECTRAL RESPONSE COEFFICIENTS (5D5)� 83�4%G, <br />5. SEISMIC DESIGN CATEGORY: D <br />G� BASIC 5EI5MIC-FORC[--RE5I5TING SYSTEM: SMEARWALL5 <br />7. DESIGN BASE SHEAR.: SEE CALCULATIONS <br />8. 5EISM IC RESPONSE CO'Ef f ICIENT (C5): 0* 126 <br />3. RESPONSE MODIff ICATION FACTOR (R). G. 5 <br />10. ANALY515 PROCEDURE USED: EQUIVALENT LATERAL FORCE <br />PROCEDURE <br />ffRAMING LUM5ER <br />I . FRAMING LUMBER SHALL BE HEM-fiR NO� 2. GRADES ARE TYPICAL <br />UNLESS OTHERWISE NOTED ON PLANS. LUMBER TO 5E GRADE MARKED <br />PER WCL15 SPECIFICATIONS. <br />2. STRUCTURAL 5HEAThING,5hALL BE APA RATED PLYWOOD, EXPOSURE <br />I SHEATHING CONFORMING TO EITHER, COMMERCIAL STANDARDS <br />t"51-83, APA PRP- � 08, OR VOLUNTARY PRODUCT STANDARD P5E-02, <br />PROVIDE A MINIMUM Of Y,5" EDGE D15TANCF ON ALL NAILS ANDY,5" <br />EXPANSION JOINT BETWEEN ALL PANEL EDGES. MINIMUM SHEATHING <br />REQUIREMENTS ARE AS FOLLOWS: <br />ROOF SHEATHING TO BE%2" INT-APA RATED PLYWOOD OR 7/1,s" 05,B <br />WITH EXTE-RiOR. GLUE, P�I. 2410. NAIL WITH 8cl NAILS AT C-11 ON <br />CENTER AT PANEL EDGff5 AND 12" ON Cff NTER AT INTERMEDIATE <br />MEM5FR5. <br />SUB FLOORING TO 5E 3/4" TONGUE AND GROOVE C-D INT-APA <br />RATE[) PLYWOOD OR 055 WITH EXTERIOR GLUE, F.I. 45/24. GLUE <br />AND NAIL WITH I Ocl NAILS AT G" ON CENTER AT PANE-L EDGES AND <br />12" ON CENTER AT INTERMEDIATE MEMBERS. <br />3. NAILING SHALL CONFORM TO TABLE 2304.3. 1 OF THE <br />INTERNATIONAL BUILDING CODE UNLE55 NOTED OTHERWISE. USE <br />COMMON NAILS THROUGHOUT UNLE55 NOTED OTHERWISE. <br />4, NO STRUCTURAL MEMBER SHALL 5E CUT OR NOTCHED UNLESS <br />SPECIFICALLY DETAILED OR APPROVE[), IN WRITING BY THE STRUCTURAL <br />ENGINE ER. <br />5� PROVIDE PROPERLY 512ED WASHERS UNDER HEADS AND NUTS OF <br />ALL 5OLT5 AND LAG SCREW5 5EARING ON WOOD. <br />G. PROVIDE 3`x3NO.225" \N"ASHER5 AT ALL ANCHOR BOLTS, <br />7'. BOLT HOLES SHALL BE NOMINAL DIAMETER Of 13OLT PLUS UNLF55 <br />NOTED OTHERWISE, LAG BOLT PILOT HOLES SHALL BE PRE-DR�LLED TO <br />GO% OF THE NOMINAL DIAMETER Of THE LAG 5OLT UNLE55 NOTED <br />OTHERWISE. <br />ALL SILL PLATE5 SHALL BE BOLTED TO THE FOUNDATION WITH 5/8U <br />MINIMUM DIAMETER BOLTS 5PACED AT A MAXIMUM Off 45" ON CENTER, <br />BOLTS MU5T 5E EMBEDDED A MINIMUM OF 77" INTO CONCRETE OF,' <br />MASONRY. SEE PLANS AND DETAILS FOR 5PECIF�C REQUIREMENTS <br />WHERE APPLICA5LF. <br />a. RIM J015T 15 TO BE 114" L5L MINIMUM, <br />10. PROVIDE DOU13LE JOIST UNDER ALL PARALLEL PARTITION WALLS <br />AND SOLID BLOCKING UNDER PERPENDICULAR PARTITION WALL5. <br />I I. CONTACT THIS Off FICE PRIOR TO MAKING ANY CHANGES TO THESE <br />DETAIL5� <br />FOUNI)ATION5 <br />1. THE FOUNDATION DESIGN 15 BASED ON THE RffCOMMENDATION IN <br />THE GE-0 GROUP NORTHWEST, INC, REPORT G-3�G85, DATE 1) JULY 7, <br />2014� <br />2� THff FOUNDATION DE51GN 15 BASED ON THE FOLLOWING VALUES: <br />ALLOW. SOIL BEARING 1500 P_9ff <br />SOIL FR�CTION <br />EQUIV. FLUID PR�E55URF5 <br />ACTIVE PRESSURE* 35 PCff <br />PASSIVE PRESSURE 250 PCf <br />3. ALL FOOTINGS; SHALL BE FOUNDED AT LEAST 15" BELOW THE <br />UNDISTUR15ED GROUND SURFACE OR TO I`ROST DEPTH. ALL FOOTINGS <br />51-IALL 5E FOUNDED ON COMPACTED FILL OR UNDISTURBED NATURAL <br />GRADE UNLESS OTHffRV/15ff NOTED. <br />4. SEE GEOTE-CHNICAL REPORT FOP, FILL AND COMPACTION <br />REQUIREMENTS. <br />CONCRETE <br />1. ALL CONCRETE UNLF-55 OTHERW15E NOTED5HALL BE REGULAR <br />kh/T=lr�4-r 1-4 DM D#-W- <br />5. ANCHOR BOLTS, DOWELS AND OTHER EMBEDDED ITEMS SHALL BE <br />SECURE LY TIED IN PLACE 5EFOPff CONCRETE 15 POURED. 5LA5 ON <br />GRADE REINFORCEMENT 51-IALL BE PLACED AT Mil) -DEPTH OF SLAB AND <br />SHALL BE HELD SECURELY IN PLACE WITH MECHANICAL DEVICES DURING <br />PLACING OF THE CONCRETE, <br />F\00� TRU55 <br />I,, THE TRUSSES SHALL BE DE-51GNED BY THE FA5RICATOR TO FIT <br />DIMENSIONS AND LOADS INDICATED ON THE PLANS AND IN THE <br />STRUCTURAL NOTES. ALL DESIGNS SHALL BE IN ACCORDANCE WITH <br />ALLOWA15LE VALUES ASSIGNED 5Y THE BUILDING CODE. CONCENTRATED <br />MECHANICAL P\00f� LOADS SHALL DE INCLUDED IN THE DESIGN. VFRIFY <br />WFIGHT'5 AND LOCATIONS WITH THE ARCHITECT, SHOP DRAWINGS <br />MUST BF RETAINED AT THE JOB SITE AND AVAILA13LE TO THE BUILDING <br />INSPECTOR fOR, REFERENCE, THE TRUSS CALCULATION PACKAGE SHALL <br />BE DESIGNED UNDER THE DIRECT SUPERVISION Of A PROF E5510NAL <br />ENGINEff R LICE N5FD IN THE STATE OF WASHINGTON. THE TRU55 <br />ENGINEER SMALL A55UMF ALL RESPONSIBILITY FOP, THE WORK OF ALL <br />51-15ORDINATE5 INVOLVED IN THE FREPARATION Of THE TRUSS, <br />PLACEMENT PLANS AND THE TRUSS DESIGN DRAWINGS. <br />�\ " I L- k � �-JU I k�l ) k,7Q7Nl_0M I L 0Fl/--\LL �.,UN FU M I U <br />2. 511OF DRAWINGS AND CALCULATIONS SHALL BE 5U15MITTFD TO THE <br />A5TM C33 WITH PROVEN 5HRINKAGE CHARACTERISTICS OF LE55 THAN' <br />ENGINEER FOR APPROVAL PRIOR TO IABRICATION, DRAWINGS AND <br />0.05%. <br />CALCULAT01\15 5MALL 13E 5TAMPff D AND SIGNED BY A REGISTERED <br />2. ALL CONCRETE IDE51GN 15 BASED ON A 25 DAY COMPRESSIVE <br />PROF ESSIONAL ENGINEER. THE DRAWINGS SHALL SHOW ALL CRITICAL <br />STRENGTH (f'c) Off 2500 PSI. WHERE 3000 P51 CONCRETE 15 REQUIRED <br />DIMENSIONS AS WELL AS THE LOADS THE TRU55E5 ARE DESIGNED TO <br />BY THE BUILDING DEPARTMENT FOR WEATHERING PURPOSES ONLY, NO <br />SUPPORT. THE TRUSSES, ARE TO 15E FRECTED AND INSTALLED IN <br />SPECIAL IN5PECTION 15 REQUIRED. <br />ACCORDANCE WITH THE PLANS, APPROVED fADRICATOR, DRAWINGS, <br />AND INSTALLATION 5UGGff5TION5. CONTRACTOR SHALL GIVE <br />3. CEMENT SHALL CONFORM TO A5TM C 150, TYPE I, CSA NORMAL. <br />NOTIFICATION PRIOR TO ENCLOSING THE TRU55ES TO PROVIDE AN <br />OPPORTUNITY FOP, INSPECTION OF THE INSTALLATION. DESIGN AND <br />4. MAXIMUM SLUMP SHALL NOT EXCEED 4 INCHES IN FLATWORK, <br />PROVIDE BRIDGING BETWEEN THE TRUSSES, CONTINUOUS LATERAL <br />BRACING AND DIAGONAL BRACING PEP, TRUSS PLATE INSTITUTE <br />5. PLACEMENT Of CONCRETE SHALL BE IN CONFORMANCE WITH ACI <br />RECOM MEN DATI ON5. SHOP DRAWINGS MAY CONTAIN THE <br />301, <br />MANUFACTURERS ENGINEERING RESPON-91BILITY LIMITATIONS. <br />HOWEVER, THEY SMALL MAKE NO 5TATEMENT AS TO THE ff NGINFER Of <br />G. CONCRETE- SHALL 13E MAINTAINED IN A M015T CONDITION FOR A <br />RffCORD RESPONSIBILITIES. <br />MINIMUM OF FIVE (5) DAYS AFTER PLACEMENT. ALTERNATE METHODS <br />WILL 13E APPROVED IF SATISFACTORY PERFORMANCE CAN BE ASSURE D <br />GENEKAL <br />7. KEYED CONSTRUCTION JOINTS SHALL bff USED IN ALL CASF5. ALL <br />1, ALL MATERIALS AND WORKMANSHIP SHALL CONFORM TO THE <br />CONSTRUCTION JOINT5 SMALL BE THOROUGHLY CLEANED AND ALL <br />CONTRACT DRAWINGS. <br />LAITANCE SHALL DE REMOVED. ALL VERTICAL JOINTS SHALL 13E <br />THOROUGHLY WETTED AND SLUSHED WITH A COAT OF NEAT CEMENT <br />2. DURING THE CONSTRUCTION PERIOD THE CONTRACTOR SMALL 5E <br />IMMEDIATE LY BE ffORff PLACING NEW CONCRETE. <br />RESPONSIBLE FOR THE SAFETY OF THE BUILDING. THE CONTRACTOR <br />SHALL PROVIDE ADEQUATE SHORING, BRACING AND GUYS IN <br />5U5MIT LOCATION OF POUR, JOINTS PRIOR TO PLACEMENT. POUR <br />ACCORDANCE WITH ALL NATIONAL, STATE AND LOCAL SAFETY <br />JOINTS SHALL BE LOCATED TO MINIMIZE EFFECTS Of SHRINKAGE AS <br />ORD�NANCE5. ANY DEVIATION MUST BE APPROVED PRIOR TO <br />WELL AS PLACED AT POINTS OF LOW STRESS. MAXIMUM AREA OF POUR <br />ERECTION. <br />JOI NT5 15 400 Sff <br />3. ALL ERECTION PROCEDURES 5HALLCONFORM TO OSHA STANDARD5, <br />0. MINIMUM CONCRETE COVEKAGE Off RE[NffORCING STEEL FOR <br />ANY DEVIATION MU5T BE APPROVE[) DY OSHA PRIOR TO ERECTION. <br />FORMED WORK SMALL BE A51FOLLOW5: <br />I NTFRIOR WALL. 3/4" <br />4. THE CONTRACTOR SHALL BE 50LELY RESPONSIBLE FOR ALL <br />EXTERIOR WALLS, EXF05ED TO WEATHER: I V2" <br />CONSTRUCTION PROCEDURE5 INCLUDING LAGGING, SHORING AND <br />EXPOSED TO FARTH OR WEATI-iff R (#5 OR SMALLER); I V2" <br />PROTECTION Of ADJACENT PROPERTY, STRUCTURES, STREETS AND <br />*NOTE: CONCRETE CAST AGAINST GROUND SHALL HAVE 3" MIN. <br />UTILITIES IN ACCORDANCE WITH ALL NATIONAL, STATE AND LOCAL <br />COVERAGE <br />5Af ETY ORDI NANCE5. <br />10. PIPES OTHER THAN ELECTRICAL CONDUITS 51-IALL NOT BE <br />5. THE CONTRACTOR SHALL BE RESPONSIBLE FOP\ COORDINATING THE <br />ffM5EDDFD IN STRUCTURAL CONCRETE EXCEPT WHERE SPECIFICALLY <br />WORK OF ALL TRADES AND SMALL CHECK ALL DIMFN5ION5. ALL <br />APPROVED, <br />DISCREPANCIES SHALL DE CALLED TO THE ATTff NTION Of THE ENGINEER <br />AND BE RESOLVED BEFORE PRO(,-,EEDING WITH THE WORK. <br />1 1. CONCRETE MIXff55HALL BE PROVIDED IN ACCORDANCE WITH ACI <br />3 15 (WHEN STRENGTH DATA f ROM TRIAL BATCHES OK f IELD <br />G. SHOP DRAWINGS FOR PREFADRICATED TRUSSES AND <br />EXPERIENCE- ARE NOT AVAILABLE). <br />MANUFACTURE[) FLOOR JOISTS SHALL BE 5U5MITTFD TO THE ENGINEER, <br />fOR REVIEW FRiOR, TO FABRICATION. <br />CEMENT CONTENT 5ACK5 <br />PER <br />7. DRAWINGS INDICATE GENERAL AND TYPICAL DETAILS Of <br />\r <br />L 5 -9 / C U b I C-, YAR, D CU51(11 (ARD <br />T C- A <br />CO�N5TRI " 11 ' <br />- ION. "/.HERE- CONDITION., ARE NOT SPECIFICALLY INDICATED <br />ff'c (PSI) (MINIMUM) <br />BUT ARE OF 51MILAR CHARACTER TO DETAILS SHOWN, SIMILAR DETAIL5 <br />(MINIMUM) <br />Of CONSTRUCTION SHALL BE USED SUBJECT TO REVIEW BY THE <br />2500 (no!5peciA m5pectm) 470 5 <br />ENGINEER. <br />SEE NOTE A <br />3000 517 51/2 <br />5. ALL DETAILS DESIGNATED AS STANDARD OR TYPICAL SHALL OCCUR IN <br />ADDITION TO ANY -OTHER SPECIFIC DETAIL CALLED OUT.' <br />MIXE55HALL BE PROPORTIONED TO PRODUCE A SLUMP OF 5" OR LLE_55� <br />NO MORE THAN A I " PLUS TOLERANCE SHALL BE ALLOWED. <br />9. COORDINATE WITH MECHANICAL, PLUMBING, AND ELECTRICAL <br />DRAWINGS FOR-517ff AND LOCATION Off ALL OPENINGS- REQUIRED FOP, <br />A) Whff RE SPECIAL INSPECTION 15 NOT RffQUIRED UNDER SECTION <br />DUCTS, PIPES, PIPF SLEEVES, ELECTRICAL CONDUITS, AND OTHER ITEMS <br />1704�4 OF THIff I.5.C., CONCRETE SHALL HAVE A MINIMUM CEMENT <br />TO BE EMBEDDED IN CONCRETE OR OTl­iERW15E INCORPORATED IN <br />CONTENT, OF 5 5ACK5 PEP, CUBIC YARD Of CONCRETE, <br />STRUCTURAL WORK, <br />b) DESIGN MIX (OTHER THAN A55PECIf �ED IN TH15 TABLE) SHALL BE <br />10. PROVIDE OPFMNG5 AND SUPPORTS, AS REQUIRED PER STANDARD <br />SUBMITTED TO THE 15UILD�NG Off IOAL TWO WEEKS PRIOR TO f IR,5T <br />DETAILS ffOR HEATERS, ME CHANICAL EQU�I`Mff NT. VENTS, DUCTS, <br />USE. <br />PIPING, ETC, ALL SUSPENDED MECHANICAL EQUIPMENT SHALL 5E SWAY <br />OR LATERALLY 5RACED, <br />Kff I N fORCI NG 5TEff L <br />I I. ARCHITECTURAL AND MECHANICAL PLANS ARF CONSIDERED A PART <br />1. ALL REINFORCING STEEL SHALL CONFORM TO A5TM AG 1, 5 GRADE GO <br />OF THE STRUCTURAL DESIGN DRAWINGS AND ARE TO 5E USED TO <br />Jy = GO K50 FOP, BAR 51ZE5 NO. 5 4 LARGEK; GRADE 40 (fy = 40 r,30 <br />DElf �Nff DETAIL CONf IGURATIONS INCLUDING, BUT NOT LIMITED TO <br />FOR NO. 3 AND NO. 4 BAR5� <br />RELATIVE LOCATION Of MEMBERS, ELEVATIONS, D�MENSIONS AND <br />LOCATIONS OF ALL OPENINGS, ETC. <br />2. ALL REINFORCING STEEL SHALL BE LAPPED AS NOTED ON THE PLANS. <br />WHERE LAP OR SPLICE LOCATIONS ARE NOT SPECIFICALLY INDICATE[) ON <br />THE CONSTRUCTION DOCUMENTS, LAPS AND/OR SPLICES SHALL BE 42 <br />BAR DIA AND BE WELL STAGGERED. <br />3. COMPLETE REINFORCING PLACEMENT DRAWI NGS PREPARED IN <br />ACCORDANCE WITH ACI 315 SHALL BE REVIE\Uff D 5Y THE ENGINEER AND <br />AVAILABLE ON THE JOB SITE PRIOR TO THE PLACING OF CONCRETE. <br />4� WELDED WIRE FABRIC SHALL CONFORM TO A5TM,,N&2 AND A � 85 <br />AND SHALL BE GxG W2. �AV2.1 UNLESS OTHERWISE NOTED. LAP <br />REINI'ORCEMENT G" MINIMUM. <br />DOUBLE TOP PLATE W/ EDGE NAILING <br />(Z HOLDOWN PER SCHEDULE AND <br />(STAGGER) <br />PLAN (HDQ8-SDS3 SHOWN) <br />(a) SHEARWALL EDGE NAILING AT ALL PANEL <br />(9 COORDINATE ALL STUD AND <br />EDGES. BLOCKING AT ALL PANEL EDGES <br />PLATE SIZES wl SHEARWALL <br />WHERE APPLICABLE. <br />QEDGE <br />SCHEDULE REQUIREMENTS <br />NAILING TO HOLDOWN POST (FULL <br />HEIGHT) STAGGER INTO DOUBLE STUDS <br />Q)EDGE NAILING TO POSTS, TRIM <br />QSTUDS @ 16"' ON CENTER <br />STUDS, AND KING STUDS <br />OPRESSURE TREATED SILL PLATE WITH <br />OBEARING STUD FOR HEADER <br />EDGE NAILING AND ANCHOR BOLTS PER <br />SHEARWALL SCHEDULE. <br />(DRIMJOIST TO BE ly2" MIN <br />(DTOP PLATE SPLICE NAILING TO BE (8) 16d <br />THICKNESS AT ALL <br />SINKERS (MIN). LAP 48" MINIMUM. CENTER <br />SHEARWALLS <br />SPLICE ON STUD. <br />-7-,,STD. SHEARWALL ELEVAT�ON W/ RIM <br />SCALE: Y2­=V-0 <br />-----CLEAR SPAN- <br />17 V2 MAXIMUM <br />CITY OF EVERETT <br />REVIEWED FOR PERMUT <br />At 4k- <br />N <br />L6 <br />Lu <br />> <br />E <br />< <br />U_j <br />C\j <br />u- <br />c <br />C) <br />oj <br />> <br />LLJ <br />Ln <br />Lu <br />(s) <br />(s) <br />Lu <br />z <br />