Laserfiche WebLink
I <br /> r <br /> 111 1. Indoor, ventilated, cast coil/encapsulated coil, with primary and secondary <br /> windings individually cast in epoxy; with insulation system rated at 185 deg C <br /> with an 80 deg C average winding temperature rise above a maximum <br /> ambient temperature of 40 deg C. <br /> C. Primary Connection: Air terminal compartment with removable door. Tin-plated <br /> copper bar for incoming line termination, predrilled to accept terminals for indicated <br /> conductors. <br /> GD. Secondary Connection: Air terminal compartment with removable door. Tin- <br /> plated copper bar for incoming line termination, predrilled to accept terminals for <br /> indicated conductors. <br /> TIE. Insulation Materials: IEEE C57.12.01, rated at 220 deg C. <br /> F. Insulation Temperature Rise: 150 deg C, maximum rise above 40 deg C. <br /> �G. Basic Impulse Level: 30 kV. <br /> G-H. Full-Capacity Voltage Taps: Four nominal 2.5 percent taps, 2 above and 2 below <br /> rated primary voltage. <br /> 4+I_Cooling System: Class AA, self-cooled, complying with IEEE C57.12.01. <br /> 14 Sound level may not exceed 50 dBa. <br /> 1bK. Impedance: 4.5 percent. <br /> Item 21 - SPECIFICATION 26 13 00, MEDIUM-VOLTAGE SWITCHGEAR, Page 4, <br /> Section 2.02.A. <br /> 1 Section 2.02.A.1 is REPLACED in its entirety with the following: <br /> 1. Square D; Schneider Electric. No substitutions will be permitted. <br /> Item 22 - SPECIFICATION 26 24 16, PANELBOARDS, Page 3, Section 2.01. <br /> Section 2.01 is REVISED as follows: <br /> 2.01 GENERAL REQUIREMENTS FOR PANELBOARDS <br /> A. Basis of Design Manufacturers: <br /> N Square D; Schneider Electric. No substitutions will be permitted. <br /> A B. Fabricate and test panelboards according to IEEE 344 to withstand seismic <br /> forces. <br /> I <br /> Addendum 3 to Evergreen Pump Station Modifications(WO#UP3747-3) Page 7/17 <br /> CITY OF EVERETT • 3200 Cedar Street • Everett, WA 98201 • (425) 257-8800 • Fax (425)257-8882 <br />