I <br /> Section 40 90 00 PROCESS CONTROL SYSTEM GENERAL PROVISIONS <br /> 3. Signal power for reference voltage (for example, PLC Input Signals, VFD I <br /> control circuits, and similar) shall be fast acting fuses 1/4"x 1-1/4" AGC or <br /> 13/32" x 1-1/2" Midget or CC type fuses. Fuses shall be rated at a <br /> minimum of 2 amperes. Fuses shall be manufactured by Cooper <br /> Bussmann or Littlefuse. <br /> Provide finger-safe terminal block, lever style Allen-Bradley 1492-FB <br /> series, Phoenix Contact UK series, Weidmuller WSI series, or equal. <br /> Plug-in fuse holders mounted to terminal blocks are not acceptable. <br /> 4. 5mm x 20mm fuses (for example, Cooper Bussmann GAS) are not <br /> acceptable for any application. <br /> 5. Provide three spare fuses of each type and size in each panel. Provide <br /> box secured to panel door interior for signal power fuses marked "SPARE <br /> FUSES". <br /> Provide specialty fuse holder for fuses, Cooper Bussmann 5TPM or <br /> similar for control power fuses. Mount to panel door interior. Label above <br /> each position the ampere rating of the fuse. <br /> B. MINIATURE CIRCUIT BREAKERS: Provide Rockwell Automation 1492-SP or <br /> equal. <br /> 2.06 WIREWAYS I <br /> A. Provide molded plastic wireways, slotted for wire connections for all wiring in the <br /> panels. Provide wireways in the color white unless otherwise noted. They shall <br /> be complete with covers. <br /> B. Wireways shall be a minimum of one inch wide and three inches deep, shall have <br /> removable snap on covers and perforated walls for easy wire entrance, shall be <br /> constructed of non-metallic materials with a voltage insulation in excess of the <br /> maximum voltage carried therein. Wireways shall be Panduit Type G, Panel <br /> Channel, or equal. <br /> C. DIN Rail incorporated wireways are acceptable. Provide a minimum of 3-inch- <br /> deep by three-inch wide wireway. Wireways shall be Panduit. I <br /> 2.07 SURGE PROTECTIVE DEVICE <br /> A. Provide surge protective device on incoming power within telemetry control I <br /> panel. Line power surge protective device shall be DIN rail mountable without a <br /> separate kit, shall have a listed surge current capacity of 45,000 amps, provide <br /> transient protection in all modes for a 20 ampere, 120 volt alternating current <br /> power circuit, and provide a form C relay output to signal surge arrestor problem. <br /> Provide Sola/HEVI-Duty STFE Elite DIN Rail STFE200-10N or equal. <br /> I <br /> City of Everett 40 90 00-10 January 2022 <br /> Evergreen Pump Station Modifications <br /> UP3747-3 <br /> Issued for Bid <br />